ZERO-CLEARANCE FIREPLACE 

INSTALLATIONS 

1.  Manufacturer’s Instructions: 

Carefully 

read and comply with the manufacturer’s 

installation instructions for your fireplace. Verify 

that DuraVent’s DuraPlus chimney is approved 

for use on your fireplace.

2.  Base Plate:

 Attach a Base Plate to the 

fireplace top with sheet metal screws.  

(Figure 

31)

.  A high temperature sealant may be used 

if desired.  

3.  Chimney Sections: 

Attach a Chimney 

Section to the Base Plate by twist-locking.  

4.  Completion:

 Install the remainder as 

instructed for a standard Ceiling-Supported 

installation, (less the Support Box).  Always 

maintain at least 2 inches of clearance to 

combustibles, and enclose the chimney where 

it passes through occupied areas. 

CONNECTION FROM APPLIANCE 

TO CHIMNEY SYSTEM

1.  Single Wall Stovepipe:

  DuraVent’s 

“DuraBlack” stovepipe is recommended, 

if single wall stovepipe is desired.  The 

connection to the ceiling support box, or 

wall thimble is made with a DuraBlack Slip 

Connector (Part# 1670, 1770, or 1870, for 

6-inch, 7-inch, or 8-inch pipe, respectively).  

The beaded end of the slip connector slips into 

the hole in the ceiling support or wall thimble.  

Align the tabs on the slip connector with the 

notches   in the face of the support or wall 

thimble, push the connector in, and twist to 

lock it in.  Further instructions for assembling 

the DuraBlack pipe are contained in their 

shipping cartons.  Remember, the minimum 

clearance to combustibles for single wall 

stovepipe is 18 inches.

2.  DVL: 

 DuraVent manufactures DVL, which 

is a double-wall connector pipe, which may 

be positioned within 6 inches to a combustible 

wall, and within 8 inches to a combustible 

ceiling, provided the appliance installation 

instructions permit this distance.  In order 

to join this type of connector to the ceiling 

support, or wall thimble, a Close Clearance 

Adaptor (Part #8674, 8774, or 8874, for 

6-inch, 7-inch, or 8-inch pipe, respectively), 

is required. The adaptor slips into the hole in 

the ceiling support, or wall thimble.  Align the 

tabs on the adaptor with the slots cut into the 

face of the ceiling support, or wall thimble, 

push in, and twist to lock it in place.  Detailed 

instructions for assembling the remainder of 

the close clearance system are included in the 

shipping cartons. 

Figure 31

CHIMNEY 

SECTION

SHEET 

METAL 

SCREWS

BASE PLATE

(SDP-BP)

ZERO-CLEARANCE FIREPLACE

Содержание duraplus

Страница 1: ...DuraPlus All Fuel Chimney System Installation Instructions...

Страница 2: ...manufacturer s warranty and may have an effect on your homeowner s insurance and UL listing status Keep these instructions for future reference This booklet also contains instructions for installing a...

Страница 3: ...7 Offset Elbow Installation 12 Offset Chart 13 Extended Roof Bracket Installation 14 Roof Supported Installations 15 Tee Supported Installations 16 Masonry Fireplace Installations 18 Zero Clearance Fi...

Страница 4: ...ct your local Building Official or Fire Official regarding permits restrictions and installation inspections in your area DuraPlus APPLICATIONS Use DuraPlus with wood stoves fireplaces furnaces boiler...

Страница 5: ...building within ten feet Figure 1 DuraPlus may be installed up to 35 feet high If a chimney is installed higher than 35 feet a supporting Elbow Strap must be placed every 8 feet If the chimney extend...

Страница 6: ...elow pertain to all stoves or other appliances installed with DuraPlus chimney systems Choice Choose a stove that is listed by a recognized testing laboratory is appropriate for your needs and is not...

Страница 7: ...and mark this center point on the ceiling Refer to Table 2 for specific framing and clearance dimensions Mark appropriate cutting lines around the center point Cut a square hole in the ceiling for a...

Страница 8: ...passes through additional floors and ceilings install Firestop Radiation Shields Where the chimney passes through an attic Firestop Radiation Shields and Insulation Shields must be installed 4 Frame O...

Страница 9: ...tibles is not required when the chimney passes through Close Clearance Shields When using Close Clearance Shields Ventilated Flashing must be installed Refer to Figure 10 which pictures both Ventilate...

Страница 10: ...outer liner 8 Install Attic Insulation Shield Install the Attic Insulation Shield where the chimney passes into an attic It s purpose is to prevent debris and insulation from getting too close to the...

Страница 11: ...ermit sliding the next Chimney Section up through the Flashing Always insure the chimney remains vertical and that at least a 2 inch clearance to combustible materials is maintained all around Install...

Страница 12: ...t furnished by DuraVent 11 Enclosures Enclose chimneys where they pass through occupied spaces including closets Always maintain at least a 2 inch clearance between the chimney and any combustible sur...

Страница 13: ...s band around the angled portion of the top Elbow then tighten the nut and bolt until the clamp is firm Wrap the Elbow Strap end over an adjacent joist or rafter and secure it with at least two 8 pen...

Страница 14: ...il heads carefully with a non hardening waterproof sealant 3 Attach Conduit Flatten 1 inch and drill a 1 4 inch hole at each end of both pieces of conduit Bolt each conduit to the Pipe Band and Roof B...

Страница 15: ...from combustibles etc 2 Cut Openings Cut a roof opening directly above the appliances flue outlet collar just as in a Ceiling Supported Installation Steps 1 thru 5 If a separate ceiling and roof exis...

Страница 16: ...e s flue outlet collar For new construction prior to sheetrock or other covering of the wall studs is applied frame a square opening between the studs as specified in Table 2 Figure 25 Should it be ne...

Страница 17: ...tion of wall thimble sdp wt black outside view from outside Figure 27 note if system exits thru wall into garage an enclosure isrequired ventilated flashing must be used 2 inches minimum enclosure GAR...

Страница 18: ...enclosure has been constructed installing the chase cover requires some special considerations The chase must be ventilated at the top and a 1 2 inch air gap must be established between the cover and...

Страница 19: ...10 Refer to Figure 1 and Table 4 for chimney height requirements Always maintain at least 2 inches of clearance to combustible materials and enclose the chimney where it passes through occupied areas...

Страница 20: ...20 Table 4...

Страница 21: ...ip connector slips into the hole in the ceiling support or wall thimble Align the tabs on the slip connector with the notches in the face of the support or wall thimble push the connector in and twist...

Страница 22: ...leaning unscrew the four screws that attach the cap s support legs to the cap base The Tee Cleanout Cap can be removed once the screws are unscrewed Remember to replace the cap when you are finished c...

Страница 23: ...23...

Страница 24: ...case of a chimney fire the chimney must be inspected and approved by a certified Chimney Sweep before reuse After each annual inspection maintenance and cleaning the certified Chimney Sweep must fill...

Отзывы: