background image

17

diameter  hole must be cut through the wall.

3.  Install Wall Thimble:

 Insert the black  

section of the Wall Thimble into the opening 

in the wall from inside the room, and align 

the nail holes with the studs. 

 (Figure 26)

.  

Do not nail the black thimble section at this 

time.  Attach the Tee to a 9-inch or 12-inch 

Chimney Section by twisting until it is firmly 

locked.  If the wall is less than 6 inches thick, 

use a 9-inch Chimney Section; if the wall is 

between 6 and 9 inches thick, use a 12-inch 

Chimney Section.  From outside the building, 

insert the Chimney Section into the hole until 

the vertical part of the Tee is 2 inches away 

from the outside of the wall, and the black 

portion of the Wall Thimble and the Chimney 

Section protrude into the room at least 2 

inches.  

iMPORTAnT: in order to make a 

safe connection, the female end of the 

Chimney Section must fully contact the 

inside face of the Wall Thimble. 

Remove the 

Figure 26

5/16 x 3” LAG 

SCREWS (6 REq) 

NOT FURNISHED

14 1/2”

14 1/2”

8-PENNY NAILS (4) REq

SHIMS TO 

MAINTAIN 

CIRCULARITY 

OF THIMBLE 

(2) REq (NOT 

FURNISHED, 

MAY BE MADE 

OF WOOD)

2 INCHES MINIMUM

DURA PLUS 

CHIMNEY PIPE

TEE 

SDP-T

2 INCHES MINIMUM 

CLEARANCE

INTERIOR 

PORTION OF 

WALL THIMBLE 

SDP-WT (BLACK)

OUTSIDE

VIEW FROM OUTSIDE

Figure 27

NOTE: IF SYSTEM ExITS 

THRU WALL INTO GARAGE, AN 

ENCLOSURE ISREqUIRED.

VENTILATED FLASHING 

MUST BE USED

2 INCHES MINIMUM

ENCLOSURE

GARAGE

2 INCHES 

MINIMUM

ACCESS DOOR 

FOR CLEANING

Tee and Chimney Section from the wall, and 

nail the Wall Thimble’s black  section to the 

studs with four 1-inch roofing nails.  If the Wall 

Thimble is going through a concrete wall, and 

no framing members are available to which to 

nail the black portion of the Wall Thimble to, 

use masonry anchors to attach it.  If a Tee-

Supported installation is being installed in a 

garage, it must be enclosed.  

(Figure 27)

.   

4.  Seal Outside:

 From the outside, insert 

the galvanized section of the Wall Thimble 

through the wall and into the black section.  

If it does not reach the black section, an 

extension tube can be locally made from  .018” 

thick galvanized steel.  Seal the flange of the 

galvanized portion of the Wall Thimble to the 

outside wall, using non-hardening waterproof 

sealant, and fasten it to the wall with screws.   

From the outside, slip the Chimney Section, 

which is attached to the Tee, into the Thimble. 

 

neVeR inSTALL SinGLe WALL STOVePiPe 

ThROUGh The WALL ThiMBLe! 

5.  Install Tee Support:

 Remove the two 

screws from the Tee Cleanout Cap, and detach 

it from the Tee.   Attach the Tee Support Straps 

to the base with the nuts and bolts provided.  

Содержание duraplus

Страница 1: ...DuraPlus All Fuel Chimney System Installation Instructions...

Страница 2: ...manufacturer s warranty and may have an effect on your homeowner s insurance and UL listing status Keep these instructions for future reference This booklet also contains instructions for installing a...

Страница 3: ...7 Offset Elbow Installation 12 Offset Chart 13 Extended Roof Bracket Installation 14 Roof Supported Installations 15 Tee Supported Installations 16 Masonry Fireplace Installations 18 Zero Clearance Fi...

Страница 4: ...ct your local Building Official or Fire Official regarding permits restrictions and installation inspections in your area DuraPlus APPLICATIONS Use DuraPlus with wood stoves fireplaces furnaces boiler...

Страница 5: ...building within ten feet Figure 1 DuraPlus may be installed up to 35 feet high If a chimney is installed higher than 35 feet a supporting Elbow Strap must be placed every 8 feet If the chimney extend...

Страница 6: ...elow pertain to all stoves or other appliances installed with DuraPlus chimney systems Choice Choose a stove that is listed by a recognized testing laboratory is appropriate for your needs and is not...

Страница 7: ...and mark this center point on the ceiling Refer to Table 2 for specific framing and clearance dimensions Mark appropriate cutting lines around the center point Cut a square hole in the ceiling for a...

Страница 8: ...passes through additional floors and ceilings install Firestop Radiation Shields Where the chimney passes through an attic Firestop Radiation Shields and Insulation Shields must be installed 4 Frame O...

Страница 9: ...tibles is not required when the chimney passes through Close Clearance Shields When using Close Clearance Shields Ventilated Flashing must be installed Refer to Figure 10 which pictures both Ventilate...

Страница 10: ...outer liner 8 Install Attic Insulation Shield Install the Attic Insulation Shield where the chimney passes into an attic It s purpose is to prevent debris and insulation from getting too close to the...

Страница 11: ...ermit sliding the next Chimney Section up through the Flashing Always insure the chimney remains vertical and that at least a 2 inch clearance to combustible materials is maintained all around Install...

Страница 12: ...t furnished by DuraVent 11 Enclosures Enclose chimneys where they pass through occupied spaces including closets Always maintain at least a 2 inch clearance between the chimney and any combustible sur...

Страница 13: ...s band around the angled portion of the top Elbow then tighten the nut and bolt until the clamp is firm Wrap the Elbow Strap end over an adjacent joist or rafter and secure it with at least two 8 pen...

Страница 14: ...il heads carefully with a non hardening waterproof sealant 3 Attach Conduit Flatten 1 inch and drill a 1 4 inch hole at each end of both pieces of conduit Bolt each conduit to the Pipe Band and Roof B...

Страница 15: ...from combustibles etc 2 Cut Openings Cut a roof opening directly above the appliances flue outlet collar just as in a Ceiling Supported Installation Steps 1 thru 5 If a separate ceiling and roof exis...

Страница 16: ...e s flue outlet collar For new construction prior to sheetrock or other covering of the wall studs is applied frame a square opening between the studs as specified in Table 2 Figure 25 Should it be ne...

Страница 17: ...tion of wall thimble sdp wt black outside view from outside Figure 27 note if system exits thru wall into garage an enclosure isrequired ventilated flashing must be used 2 inches minimum enclosure GAR...

Страница 18: ...enclosure has been constructed installing the chase cover requires some special considerations The chase must be ventilated at the top and a 1 2 inch air gap must be established between the cover and...

Страница 19: ...10 Refer to Figure 1 and Table 4 for chimney height requirements Always maintain at least 2 inches of clearance to combustible materials and enclose the chimney where it passes through occupied areas...

Страница 20: ...20 Table 4...

Страница 21: ...ip connector slips into the hole in the ceiling support or wall thimble Align the tabs on the slip connector with the notches in the face of the support or wall thimble push the connector in and twist...

Страница 22: ...leaning unscrew the four screws that attach the cap s support legs to the cap base The Tee Cleanout Cap can be removed once the screws are unscrewed Remember to replace the cap when you are finished c...

Страница 23: ...23...

Страница 24: ...case of a chimney fire the chimney must be inspected and approved by a certified Chimney Sweep before reuse After each annual inspection maintenance and cleaning the certified Chimney Sweep must fill...

Отзывы: