background image

18

Use (2) 5/16 inch, 3-inch long lag screws to 

attach the straps to the wall.  Replace the Tee 

Cleanout Cap and screws, once the Tee is 

installed.  

6.  Complete Chimney:

 Attach the Chimney 

Sections as in Step 7 of the Ceiling Supported 

Installation section.  Secure the chimney to 

the wall with Wall Straps at 4-foot intervals 

to maintain at least 2 inches of clearance to 

combustible materials.  Slip the Wall Straps 

around the chimney, tighten the bolts, and 

fasten the Wall Straps to the wall with (2) 

5/16-inch, 3-inch long lag screws.  Snap the 

Chimney Cap into the top of the chimney, 

once it is at the height specified in Figure 1.  If 

the chimney penetrates an overhang, frame 

for at least 2 inches of clearance, and install 

Figure 28

WALL STRAP

ALLOW A MINIMUM OF 

2 INCHES AIR SPACE 

ON ALL SIDES

2 INCHES MINIMUM

2 INCHES MINIMUM

a Flashing and Storm Collar as described 

in Steps 8, 9 and 10 for Ceiling Supported 

Installations.  Another option is to cut away 

the overhang for a 2-inch clearance.   

 (Figure 

28)

.  If the chimney extends more than 4 feet 

above the top Wall Band, or Flashing, use an 

Extended Roof.

7.  Install Chase Cover.

   If a chase enclosure 

has been constructed, installing the chase 

cover requires some special considerations.

The chase must be ventilated at the top 

and a 1/2-inch air gap must be established 

between the cover, and the framed chase 

top.  In addition,  a 1/2-inch air gap should 

exist between the hole in the cover, and the 

Chimney Pipe Sections.  

Figure 29

 displays 

in some detail, how these air gaps are 

established with locally fabricated spacers and 

covers.  These are not furnished by DuraVent, 

but may be made from 28 gage or heavier 

sheet metal.  Should the installer elect to use 

Flat Roof Flashing, (which is a stock item), the 

air spaces are still required.  When installing 

the Storm Collar, do not push it down all the 

way to the cover, but allow an air space for 

flow between the Chimney Pipe and the hole 

in the cover. 

MASONRY FIREPLACE 

INSTALLATIONS 

1.  Determine Chimney Size: 

Use 

Table 4

 

to determine the correct diameter chimney for 

your fireplace.  

2.  Mount Anchor Plate:

 Chimneys for 

masonry fireplaces begin with an Anchor Plate.  

Center the Anchor Plate on a brick or concrete 

base over the masonry flue opening.  Seal the 

Anchor Plate with a high-temperature sealant, 

and secure with (4) 1/4-inch masonry anchors.   

(Figure 30)

.  Be sure it is level.  The Anchor 

Plate is available in two styles.  One contains 

the perforated Starter Section,  which is used 

Содержание duraplus

Страница 1: ...DuraPlus All Fuel Chimney System Installation Instructions...

Страница 2: ...manufacturer s warranty and may have an effect on your homeowner s insurance and UL listing status Keep these instructions for future reference This booklet also contains instructions for installing a...

Страница 3: ...7 Offset Elbow Installation 12 Offset Chart 13 Extended Roof Bracket Installation 14 Roof Supported Installations 15 Tee Supported Installations 16 Masonry Fireplace Installations 18 Zero Clearance Fi...

Страница 4: ...ct your local Building Official or Fire Official regarding permits restrictions and installation inspections in your area DuraPlus APPLICATIONS Use DuraPlus with wood stoves fireplaces furnaces boiler...

Страница 5: ...building within ten feet Figure 1 DuraPlus may be installed up to 35 feet high If a chimney is installed higher than 35 feet a supporting Elbow Strap must be placed every 8 feet If the chimney extend...

Страница 6: ...elow pertain to all stoves or other appliances installed with DuraPlus chimney systems Choice Choose a stove that is listed by a recognized testing laboratory is appropriate for your needs and is not...

Страница 7: ...and mark this center point on the ceiling Refer to Table 2 for specific framing and clearance dimensions Mark appropriate cutting lines around the center point Cut a square hole in the ceiling for a...

Страница 8: ...passes through additional floors and ceilings install Firestop Radiation Shields Where the chimney passes through an attic Firestop Radiation Shields and Insulation Shields must be installed 4 Frame O...

Страница 9: ...tibles is not required when the chimney passes through Close Clearance Shields When using Close Clearance Shields Ventilated Flashing must be installed Refer to Figure 10 which pictures both Ventilate...

Страница 10: ...outer liner 8 Install Attic Insulation Shield Install the Attic Insulation Shield where the chimney passes into an attic It s purpose is to prevent debris and insulation from getting too close to the...

Страница 11: ...ermit sliding the next Chimney Section up through the Flashing Always insure the chimney remains vertical and that at least a 2 inch clearance to combustible materials is maintained all around Install...

Страница 12: ...t furnished by DuraVent 11 Enclosures Enclose chimneys where they pass through occupied spaces including closets Always maintain at least a 2 inch clearance between the chimney and any combustible sur...

Страница 13: ...s band around the angled portion of the top Elbow then tighten the nut and bolt until the clamp is firm Wrap the Elbow Strap end over an adjacent joist or rafter and secure it with at least two 8 pen...

Страница 14: ...il heads carefully with a non hardening waterproof sealant 3 Attach Conduit Flatten 1 inch and drill a 1 4 inch hole at each end of both pieces of conduit Bolt each conduit to the Pipe Band and Roof B...

Страница 15: ...from combustibles etc 2 Cut Openings Cut a roof opening directly above the appliances flue outlet collar just as in a Ceiling Supported Installation Steps 1 thru 5 If a separate ceiling and roof exis...

Страница 16: ...e s flue outlet collar For new construction prior to sheetrock or other covering of the wall studs is applied frame a square opening between the studs as specified in Table 2 Figure 25 Should it be ne...

Страница 17: ...tion of wall thimble sdp wt black outside view from outside Figure 27 note if system exits thru wall into garage an enclosure isrequired ventilated flashing must be used 2 inches minimum enclosure GAR...

Страница 18: ...enclosure has been constructed installing the chase cover requires some special considerations The chase must be ventilated at the top and a 1 2 inch air gap must be established between the cover and...

Страница 19: ...10 Refer to Figure 1 and Table 4 for chimney height requirements Always maintain at least 2 inches of clearance to combustible materials and enclose the chimney where it passes through occupied areas...

Страница 20: ...20 Table 4...

Страница 21: ...ip connector slips into the hole in the ceiling support or wall thimble Align the tabs on the slip connector with the notches in the face of the support or wall thimble push the connector in and twist...

Страница 22: ...leaning unscrew the four screws that attach the cap s support legs to the cap base The Tee Cleanout Cap can be removed once the screws are unscrewed Remember to replace the cap when you are finished c...

Страница 23: ...23...

Страница 24: ...case of a chimney fire the chimney must be inspected and approved by a certified Chimney Sweep before reuse After each annual inspection maintenance and cleaning the certified Chimney Sweep must fill...

Отзывы: