58
YES
Remo
ve
all liquid
from connector
.
Check for leaks. R
epair all leaks.
Replace Control Module
Replace R
eturn W
ater
Sensor
Is correct harness connected to return
sensor (2 Brown Wires)?
YES
NO
Correct wiring
Unplug molex connector on return
sensor
. Is there moisture or liquid on
metal pins? Liquid might be w
ater or
antifreez
e solution.
NO
Is Heat Ex
changer Pump
properly oriented?
(Pump arrow pointing down?)
YES
NO
Disconnect harness from
Return W
ater Sensor
. Measure
resistance using digital ohm meter
. Is resistance between
950 to 33,000 ohms?
Install Heat
Ex
changer Pump in
proper orientation
YES
NO
13 - TROUBLE SHOOTING
g
n n
Replace
Control
Module