22
WARNING
Vent extending through exterior wall shall not
terminate adjacent to wall or below building
extensions such as eaves, balconies, parapets or
decks. Failure to comply could result in death or
serious injury.
!
6.4 Vent Pipe Installation
• Minimum and maximum combustion air and vent pipe
lengths listed in Table 5. Pipe length counted from
combustion air connector to termination.
• Install
fi
eld-sourced 2" to 3" transition, if used, in vertical
section at combustion air inlet and vent connector.
• 90° elbows equivalent to 5.0 ft (1.6 m). 45° elbows
equivalent to 3.5 ft (1.1 m). 2" to 3" transition has no
equivalent length. See Table 6.
• Use
fl
exible Polyproplyene piping (PP) in a vertical
position only. Check PP pipe manufacturer for details.
Each foot of PP
fl
exible pipe is equivalent to 2
⅝
feet of
smooth pipe of same diameter.
• Slope vent pipes minimum 1/4" per foot (21 mm/m)
back toward boiler. Support horizontal sections to
prevent sags capable of accumulating condensate.
• Support piping in accordance with pipe manufacturer's
instruction and authority having jurisdiction. In absence
of manufacturer's instruction use pipe hooks, pipe
straps, brackets, or hangers of adequate and strength
located at intervals of 4 ft (1.2m) or less. Allow for
expansion/contraction of pipe.
• Combustion air and vent piping must be air tight and
water tight.
• Certi
fi
ed vent system components must NOT be
interchanged with other vent systems or unlisted pipe/
fi
ttings.
• Canadian installations only. All venting material, primer
and glue must be listed to ULC S636.
• Canadian installations only. First 3 ft (0.9 m) of
plastic vent pipe from vent connector must be readily
accessible for visual inspection.
6.5 Vent Termination
• Terminate combustion air and vent pipes with
fi
ttings or
concentric vent kit.
A. See "Parts, Kits and Optional Accessories" manual
for concentric vent kit part numbers.
B. Use horizontal pipe for vent and 90° elbow for
combustion air termination when using
fi
ttings.
• Terminate combustion air and vent pipes in same
atmospheric pressure zone through exterior sidewall or
roof.
• Locate combustion air termination as far as possible
from swimming pool, swimming pool pump house, and
other sources of airborne chlorine.
• Locate combustion air and vent terminals as required by
authority having jurisdiction.
Minimum/Maximum Vent Lengths
2” Pipe
3” Pipe
4” Pipe
Model
050
075/100
075/100
150/200
299
299
Min.
6 ft.
(1.8 m)
6 ft.
(1.8 m)
6 ft.
(1.8 m)
6 ft.
(1.8 m)
6 ft.
(1.8 m)
6 ft.
(1.8 m)
Max.
100 ft.
(30.5 m)
50ft.
(15.2 m)
100 ft.
(30.5 m)
100 ft.
(30.5 m)
25 ft.
(7.7 m)
100 ft.
(30.5 m)
Table 5 - Combustion Air and Vent Piping Length
For Example: Boiler can be installed on outside wall and vented with one 90° elbow and 1 ft (0.30 m) of vent pipe.
Table 6 -Equivalent Length of Venting Components
Equivalent Length of Venting Components
Component
Feet
Meters
90° Elbow
5
1.6
45° Elbow
3 1/2
1.1
2" x 4" Adapter
0
0
3" x 4" Adapter
0
0
Concentric Vent Kit
5
1.6
Polypropylene Flexible Pipe per Foot
2 5/8
0.8
6 - COMBUSTION AIR AND VENT PIPING
Содержание DKVLT-050
Страница 47: ...47 13 TROUBLE SHOOTING ...
Страница 51: ...51 13 TROUBLE SHOOTING ...
Страница 53: ...53 13 TROUBLE SHOOTING ...
Страница 62: ...62 Supply Water Temperature Sensor Resistance Chart 13 TROUBLE SHOOTING ...
Страница 64: ...64 14 WIRING DIAGRAM 14 1 Connection Diagram 050 075 100 150 200 MBH ...
Страница 66: ...66 14 WIRING DIAGRAM 14 3 Connection Diagram 299 MBH EXTERNAL PUMP RELAY LIMIT OF 1 AMP PER PUMP SEE SECTION 8 ...
Страница 83: ...83 NOTES ...
Страница 84: ...ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...