33
FIGURE 7-2 Manual Main Gas Shutoff Valve Outside
Boiler Jacket
7.3 Leak Check Gas Piping
Pressure test boiler and gas connection before placing
boiler in operation.
• Pressure test over 1/2 psig (3.5 kPa). Disconnect
boiler and its individual gas shutoff valve from
gas supply system.
• Pressure test at 1/2 psig (3.5 kPa) or less.
Isolate boiler from gas supply system by closing
manual gas shutoff valve. See
fi
gure 7-2.
• Locate leakage using gas detector, noncorrosive
detection
fl
uid, or other leak detection method
acceptable to authority having jurisdiction. Do
not use matches, candles, open
fl
ames, or other
methods that can provide ignition source.
• Correct leaks immediately and retest.
Manual Main Gas
Shutoff Valve
FIGURE 7-3 Gas Shutoff Valve - 050/075/100/150/200
DANGER
Fire Hazard. Do not use matches, candles, open
fl
ames, or other methods providing ignition source.
Failure to comply will result in death or serious
injury.
!
n Gas
alve
Gas shutoff valve
(shown in closed
position)
FIGURE 7-4 Gas Shutoff Valve - 299
Gas shutoff valve
(shown in open
position)
G
7 - GAS SUPPLY PIPING
Содержание DKVLT-050
Страница 47: ...47 13 TROUBLE SHOOTING ...
Страница 51: ...51 13 TROUBLE SHOOTING ...
Страница 53: ...53 13 TROUBLE SHOOTING ...
Страница 62: ...62 Supply Water Temperature Sensor Resistance Chart 13 TROUBLE SHOOTING ...
Страница 64: ...64 14 WIRING DIAGRAM 14 1 Connection Diagram 050 075 100 150 200 MBH ...
Страница 66: ...66 14 WIRING DIAGRAM 14 3 Connection Diagram 299 MBH EXTERNAL PUMP RELAY LIMIT OF 1 AMP PER PUMP SEE SECTION 8 ...
Страница 83: ...83 NOTES ...
Страница 84: ...ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...