Parameter

 

Value

 

Auto close ½ open

 

 

00 =

 

No auto close from ½ open limit 

01 =

 

Auto close from ½ open limit

 

Notice:

Auto close must be activated in parameter 32. 

Safety edge selection

 

 

Note that actual edge must be connected but not activated before this setup. If 
the controller has observed a wrong edge select, the display will show ERR. 
Please note that nothing must be connected to X3 terminal 23

-

24 when param-

eter value 03 have been chosen. 

 

01 =

 

NCC edge or DW switch AU contact

 

02 =

 

8k2 electrical edge

 

03 = 

 

optical edge (Type FRABA)

 

04 =

 

DW switch (AG contact)

 

05 = 

 

Wireless safety edge with test function (X20)

 

After run

 

 

 

00 =

 

No after run 

 

> 00

 

After run active (after run time 0.01 –

 0.50 

sec.).

 

Monitoring of PNE/DW air switch safety edge is automatically selected when 
after run is active. When the door reaches the close limit switch, the door will 
continue to close until PNE/DW air switch activate or until the after run time 
exceeds.

 

Notice:

 

Can be used to prevent that the door reverses when it reaches the floor before 
the close limit gets activated –

 

for instance if there is dirt in the door opening or 

if the wires are getting longer.

 

Extra safety edge 

 

(X20 –

 

terminal 3

-

4)

 

 

 

00 = No extra safety edge 

 

01 = Extra safety edge works parallel with primary safety edge 

 

02 = Extra safety edge stops door in opening direction 

 

03 = Stop and short reversal in opening direction

 

05 = Slack rope switch

 

06 =  Slack rope switch (NC)

 

Содержание CONTROL V7E

Страница 1: ...04 2022 Version 1 DoorTec Deutschland www doortec online nderungen vorbehalten Subject to Modifications OPERATION MANUAL CONTROL V7E VERSION 29 22...

Страница 2: ...essarily to scale 2 2 Using the equipment for its intended purpose The control V7E is designed only for controlling gates and doors with mechanical or digital end position sys tems For other applicati...

Страница 3: ...om the power supply before commencing cabling work Take measures to ensure that the power sup ply remains disconnected for the duration of the work NOTICE For a three phase current a clockwise rotatin...

Страница 4: ...that the direction of rota tion of the gear motor is correct and that all protective devices are functioning 5 1 Electrical installation 5 2 HOW TO program The door will always run in hold to run mod...

Страница 5: ...age Operation mode 7 Reaction Failure on photo or Safety edge 7 Selection of limits 7 Learning Electronic Limit Open 8 Fine Tuning of electronic Limit Open 8 Learning Electronic limit CLOSE 8 Fine tun...

Страница 6: ...r Description Page Auto close 11 Car wash function 11 Forced closing 12 GO function Step 12 Interlock function ON OFF 12 Run time control 12 Reverse time safety edge 12 Reserve time photo 13 Service c...

Страница 7: ...hold to run mode when programming Reaction Failure on photo or Safety edge 00 Hold to run operation not possible when failure on photo or safety edge The door cannot close when there is an error on p...

Страница 8: ...e open 1 4 less open Press OPEN or CLOSE push button to change value If the value is changed Press STOP push button Display shows RUN Test the fine tuning by running the door up and down Press the STO...

Страница 9: ...o switch NC type in terminal 15 16 Short circuit terminal 15 16 parallel connected by mechanical switch to ON OFF this function Electronic limits Value 00 selected in parameter 11 ON OFF controlled by...

Страница 10: ...contact 05 Wireless safety edge with test function X20 After run 00 No after run 00 After run active after run time 0 01 0 50 sec Monitoring of PNE DW air switch safety edge is automatically selected...

Страница 11: ...ning from close to open posi tion The door will stop when the photo is no longer blocked and the control unit will change back to parameter number automatically Auto close Note that impulse close must...

Страница 12: ...s a connect ing bridge between X3 20 22 parameter 31 02 Interlock function Only when auto close is selected parameter 32 00 Interlock function OFF 01 Interlock function ON Run time control 00 No run t...

Страница 13: ...0 open cycles before service Reset for new countdown or selecting value Press STOP to select parameter value Press OPEN or CLOSE to select value Press STOP again minimum 2 sec CLR is shown 2 sec in di...

Страница 14: ...mming mode on DIL switch no 1 This will clear the SER error If the door is running again in 1 sec without command when power is on then the PCB is defect 4 Calculation error Check that parameter 11 va...

Страница 15: ...leshooting OPEN push button active Normal symbol as an aid in programming and troubleshooting Activation of loop detector will also show this symbol CLOSE push button active Normal symbol as an aid in...

Страница 16: ...emented to 0 Reset for new countdown Photo Failure in photo circuit Test cycle after last stop failed Press stop to start new test Safety edge Failure in edge circuit Test cycle after last stop failed...

Страница 17: ...o 999000 and the least significant digits 000 999 Example shown is 362 and 086 362086 door openings Press STOP to see last 10 errors or exit by switching DIL switch 2 to off Last 10 Errors Press OPEN...

Страница 18: ...dary safety edge D7 LED Power X5 Key pad X24 Power supply selection D10 LED Stop X6 Antenna radio receiver K1 Contactor OPEN D12 LED limit CLOSE X7 Plug in module radio receiver K2 Contactor CLOSE D13...

Страница 19: ...g required The supply voltage of the transmitter is switched off to test the photocell Without testing the sensor can not be used 10 CONNECTIONS X3 10 1 Command devices 6 wire connection The LED light...

Страница 20: ...grey 21 Input black 22 Input white 10 9 Additional photo beam Photo 1 X12 Parameter 31 01 10 10 Potential Free Contact K3 OPTION INFORMATION The polarity of the test signal must be considered The sig...

Страница 21: ...E terminals N X1 L1 L X1 L3 N linked with a wire Motor connection Phase open direction X2 U Phase close direction X2 V Common N X2 W 10 13 Light curtain P N P transistor OSE connection No Semiconduc t...

Страница 22: ...AC 4 kW Max motor load by 3 x 230V AC 2 3 kW Max motor load by 1 x 230V AC 1 5 kW Max motor current 8 5 A Operating duty cycle 60 at max 120 s runtime Consumption control Max 13 VA Control voltage 24...

Страница 23: ...been used EN 60335 1 2012 AC 2014 Household and similar electrical appliance Safety EN 60335 2 103 2015 Household and similar electrical appliance Safety Particular requirement for drives for gates do...

Страница 24: ...utschland www doortec online nderungen vorbehalten Subject to Modifications Chain Wheel Operators Controls Safety Systems Accessories DoorTec Sectional Door Rolling Shutter Operators Operators PRODUCT...

Отзывы: