8 of 3
Die-out – Indicating that the handheld microphone is normal but it does not work.
6 ——
System Equipment LED Indicator Test (mainly test the LED of host/extended host and business microphone
panel)
Note: if there is an extended host or business microphone in the system configuration, it will enter LED test
model after pressing this key.
7 —— System Work Mode Indicator
Red Flash – Indicating the current system is in an emergency mode;
Die-out – Indicating the current system is in a normal mode;
Two Ways to Enter the Emergency Mode:
Manual Mode – under the normal mode, the red indicator light flashes after pressing this key, which indicates
that the system manually enters the emergency mode;
Automatic Mode – under the normal mode, after detecting the effective triggering signals at the rear row
“TriggerInputs” of the host or extended host, this indicator light will also flash, which indicates that the system works
in the emergency mode.
Two ways to exit the Emergency Mode:
Manual Mode – Under the emergency mode, the system exits from the emergency mode by pressing this key,
and meanwhile it stops the playing of EVAC voice message and the partition output;
Automatic Mode – under the emergency mode, it can exit from the emergency mode by way of direct short
circuit at 2 input ports of rear row “System Link Control” port 3, and meanwhile, it stops the playing of EVAC voice
message and the partition output.
Note
: no matter whether it is a manual entry (exit) or automatic entry (exit), its execution time and way can be
checked in the LOG of PAVA6000.
8 —— Multi-purpose Reset Key (ACK/RESET):
Answering System Status -
a. if various system modules work normally or when the diagnosis of system modules is abnormal but “FAULT”
indicator light does not flash, no treatment is made to the equipment after pressing this key;
b. If the diagnosis of system modules is abnormal and “FAULT” indicator light intermittently flashes, after
pressing this key, “FAULT” indicator light is ON and does not flash any longer, which indicates its fault status,
and the buzzer stops until the FAULT LED light re-flashes after abnormity is detected in new module and the
buzzer is started to prompt the user;
c. When there is any output from the current partitions, press this key to close the current audio output and
quickly end the broadcasting.
9
/
10
—— EVAC Voice Message Status Indicator
Green – “EVAC MSG/ALERT MSG” voice message is broadcasting;
Yellow - “EVAC MSG/ALERT MSG” voice message is lost or SD Card is lost;
Die-out (OFF) - “EVAC MSG/ALERT MSG” voice message is normal.
Note:
1. ”EVAC Voice Message” means the general designation of EVAC voice and ALERT Voice;
2. If any user wants to manually play the EVAC voice message, he/she shall enter the emergency mode and then
press the voice message key;
3. In the system default, the priority of “EVAC” Voice is higher than that of “ALERT” Voice. Of course, it can be altered
through the priority configuration of PAVA6000. If it is not a specific application need, please do not change it.