Skyroute CL3050 Standalone Wireless Communicator
4
5
Mount Unit
•
Remove the front cover if required
•
Disconnect flying leads from battery and power leads from the RED and BLK
terminals (if connected).
•
Remove two screws securing battery clamp. Remove battery
•
Mount backplate of unit to wall or over electrical junction box using the
four screws provided.
Note:
DO NOT
connect the battery to the flying leads and AC or DC power
to the terminal strip until all other wiring connections are completed.
•
Route wiring through the access holes provided and connect to terminal
strip.
•
power up unit by connecting battery and power source.
6
Enroll Unit
Call Connect 24 and Enroll the Skyroute CL3050. Refer to
page (ii)
for contact
information and a list of information required to complete the enrollment with
the Connect 24 Voice Response Unit.
2.2
Testing
Program Mode:
If you have wired the unit to power up in the programming
mode. Follow the steps outlined in
Section 6, Programming Descriptions
and
record the program settings in
Section 7, Programming Worksheets.
Test Transmission -
Pressing and holding the enroll button for 2 seconds will
send a test transmission to the central station via
Connect 24.
Refer
to
Enrol
Button
in
Section 3, Controls and indicators
for test transmission details.
Mode 1:
Disable the telephone line connected to the control panel. Simulate
Burglar and Fire Zone violation. Verify that the Skyroute CL3050 transmits the
events to the central station.
Mode 2 & 3:
Simulate Faults, Tampers, and Zone violations in accordance with
the settings outlined in
Sections 6, Programming Descriptions
. Verify that the
Skyroute CL3050 transmits the events to the central station.
2.3
Resetting to Factory Defaults
Note:
Resetting to factory defaults is required to change mode of operation.
•
Remove Power from the Skyroute CL3050; disconnect battery and control
panel if applicable (mode 1).
•
Disconnect all wiring from the YEL and GRN terminals.
•
Connect a jumper wire between the YEL and GRN terminals.
•
Apply power to the system.
Note:
When the hardware default has been completed; the yellow, green
and red LEDs will flash on and off continuously.
•
Remove power from the system.
Note:
To resume communications with
Connect 24
,
Section [11], Option 6
must be set to ON. To do this; the system must be powered up in pro-
gramming mode. Refer to
Section 5 System Programming.
•
Reconnect all original wiring and reapply power to the system.
•
Test System - Refer to
Section 2.2
Содержание Skyroute CL3050
Страница 6: ...ii...