4 Power up Sequence
7
PGM -
The PGM output is
dedicated for Skyroute
CL3050 trouble indica-
tions. If a control panel is
not monitoring the Sky-
route CL3050, an LED or a
buzzer can be connected
between this terminal and
the RED terminal for trouble
indication. The PGM termi-
nal switches low from an
open-collector state. Con-
nect to the control panel
using a Single EOL configu-
ration as shown
Note:
The PGM output can
sink 50 mA (maximum).
4 Power up Sequence
On first-time power up, the Skyroute CL3050 will generate a random test trans-
mission time and random day of the week to send it. The installer can then
change this information if required.
During power up, the Skyroute CL3050 will look for a keypad on the Keybus, if
one is found, it will go into programming mode. If no keypad is found, it will
look for a PC5108 zone expander module. If a zone expander is found, it will
automatically configure itself for mode 3. If no Keybus modules are present, the
Skyroute CL3050 will power up in mode 1. During the first 15 seconds of power
up, any zone scanning will be shunted. During this time the installer can momen-
tarily press the enroll button on the Skyroute CL3050 to toggle between mode 1
and mode 2. Upon power up the green LED will be flashing on and off. This will
indicate to the installer that he/she can change the mode to 1 or 2. The red LED
will indicate mode 1 and the yellow LED will indicate mode 2. If neither red or yel-
low LED is lit, then the Skyroute CL3050 has detected a PC5108 module, the
mode cannot be changed by pressing the enroll button if a PC5108 module is
connected to the Skyroute CL3050.
If a
keypad
is detected on Keybus, the green LED will stop flashing, and the red
LED will begin flashing to indicate that programming mode is active.
RED BLK YEL GRN COM PGM
LED 560
Ω
LED Output with
current limiting
resistor
Optional relay
driver output
+ Coil -
Relay
To External
Supply
NC Com
Skyroute CL3050