Skyroute CL3050  Standalone Wireless Communicator

10

[02]

Mode 2 - (2) 24-Hour Zones

In this mode, both the YEL and 
GRN terminals on the Skyroute 
CL3050 will be used as zone 
inputs.  These zones will support 
the DSC standard EOL configura-
tion and loop response.  Pro-
gramming sections will allow the 
installer to change the default 
zone types and attributes. The 
Skyroute CL3050 will continu-
ously monitor these zones and transmit any alarms that occur to the central sta-
tion.

[03]

Mode 3 - (8) 24-Hour Zones

In this mode, the Skyroute 
CL3050 is connected to a 
PC5108 zone expander using 
the corresponding RED, BLK, 
YEL and GRN terminals.  The 
Skyroute CL3050 will drive the 
Keybus to communicate with 
the PC5108.  A +12V

DC

 sup-

ply connected to the RED and 
BLK terminals is required 
when using this mode. The Programming sections will allow the installer to 
change the default zone types and attributes.  The Skyroute CL3050 will continu-
ously monitor these zones and transmit any alarms that occur to the central     
station.

Note:

 

This configuration can not be used with an AC supply.

Note: 

Jumpers on the PC5108 must be set as follows:

J1
J2
J3

ON
OFF
ON

J4
J5
J6

OFF
OFF
ON

Default - 

[01 -03]  dependant on start up configuration

[11] Skyroute CL3050 Configuration Options 1

Option 1 - A Channel Selected/ B Channel Selected. 

All Modes

This Option determines whether cellular channel 

“B” 

or channel 

“A”

 is used

. In 

Canada, Channel B is used (Default). In the USA refer to the SID list for the chan-
nel of the cellular service provider in your area. 

Default -

 Channel B

Option 2 - Normally Closed Loops/ End-of-line Resistors                

Mode 2, 3

Normally Closed Loops can be wired as shown. Multiple 
Normally Closed contacts can be wired in series. For Double 
or Single EOL resistors this option must be set to 

OFF

Default -

 Normally Closed (N/C) Loops.

Option 3 - Double EOL Resistors/Single EOL Resistors

Mode 2, 3

This option selects Double EOL resistors (ON) or Single EOL resistors (OFF) wired 
as indicated

Input Voltage
9-12V

 or V

AC

DC

Zone 1 Input

Zone 2 Input

Zone Common
Trouble Output

RED    BLK   YEL  GRN  COM  PGM

To Keybus
Connections
on PC5108

System Common
Trouble Output

RED    BLK   YEL  GRN  COM  PGM

Содержание Skyroute CL3050

Страница 1: ...PowerSeries keypads Installation Programming Guide WARNING This manual contains information on limitations regarding product use and function and information on the limi tations as to liability of the...

Страница 2: ...ocation may be required STEP 2 CONNECT NECESSARY WIRING See Section 6 Mount the Skyroute determine the desired mode of oper ation and connect the appropriate control panel zone or Keybus wiring as det...

Страница 3: ...found on the authorized Installer Card sent with the Dealer Confirmation Form Installer PIN Number 4 digits I___I___I___I___I Each Installer provided a 4 digit PIN number on the Dealer Enrollment Form...

Страница 4: ...riel brouilleur du Canada IC 160A CL3050 The term IC before the radio certification number only signifies that Industry Canada technical specifications were met Limited Warranty DSC warrants that for...

Страница 5: ...gramming Descriptions 9 01 Zone 1 2 Definitions 9 02 Zone 3 8 Definitions 9 03 Zone 1 2 Loop Response 9 10 Skyroute CL3050 Mode of Operation 9 11 Skyroute CL3050 Configuration Options 1 10 12 Skyroute...

Страница 6: ...ii...

Страница 7: ...of the con trol panel The system identifies the Bell Output cadence and transmits the corre sponding Fire or Burglar alarm reporting code to Connect 24 Refer to the appropriate control panel Installat...

Страница 8: ...erSeries Keypads PC5508 KP5508Z 8 Zone LED keypad PC5516Z KP5516Z 16 Zone LED keypad PC5532Z KP5532Z 32 Zone LED keypad LCD5500Z KPL5500Z Programmable Message LCD Keypad LCD5501Z KP5501Z Fixed Message...

Страница 9: ...ming Descriptions section 10 for zone wir ing details Note Generally the higher the location and the closer that the Skyroute CL3050 is to an outside wall the better the signal strength will be 3 Chec...

Страница 10: ...s will send a test transmission to the central station via Connect 24 Refer to Enrol Button in Section 3 Controls and indicators for test transmission details Mode 1 Disable the telephone line connect...

Страница 11: ...h a series of flashes as indicated below No of Flashes Indication 1 2 3 4 5 6 7 8 9 No trouble conditions present Low battery Input supply failure Not enrolled at Connect 24 No service available Radio...

Страница 12: ...ce will display the detailed RSSI status indicated above Holding this button down for a period of 2 seconds continuously will cause the Skyroute CL3050 to send a test transmission to Connect 24 this l...

Страница 13: ...found it will automatically configure itself for mode 3 If no Keybus modules are present the Skyroute CL3050 will power up in mode 1 During the first 15 seconds of power up any zone scanning will be s...

Страница 14: ...ered down 1 Connect keypad Keybus connections to the RED BLK YEL and GRN termi nals of the Skyroute CL3050 2 Connect a 12VDC supply across the RED and BLK terminals Upon detecting the keypad on power...

Страница 15: ...ffect zones on a PC5108 zone expander card Default 05 0 5 seconds 01 FF Hex x 0 1 seconds 10 Skyroute CL3050 Mode of Operation 01 Mode 1 Bell Follower Operation In this mode the YEL terminal is con ne...

Страница 16: ...that occur to the central station Note This configuration can not be used with an AC supply Note Jumpers on the PC5108 must be set as follows J1 J2 J3 ON OFF ON J4 J5 J6 OFF OFF ON Default 01 03 depen...

Страница 17: ...r the Skyroute CL3050 to resume communications Default Not Enrolled Options 7 8 System Use All Modes Caution Do NOT change these settings unless it is requested by DSC technical support personnel Defa...

Страница 18: ...rvice Available All Modes This trouble is indicated If the system is unable to detect cellular service Default ON Option 5 Radio Failure All Modes This trouble is indicated if there is an internal fau...

Страница 19: ...fic volume when selecting test transmission times select a time that is not on the 30 minute mark e g 02 24 04 07 18 Test Transmission Day All Modes When the Skyroute CL3050 is powered up for the firs...

Страница 20: ...Zones Modes 2 3 The Skyroute CL3050 supports generic and detailed zone alarm reporting By default the Skyroute CL3050 will be in generic zone reporting mode When in this mode all zone types are divide...

Страница 21: ...system will send a restore Default ON Option 3 Skyroute CL3050 Tamper All Modes Removing the cover on the Skyroute CL3050 will send a tamper reporting code to Connect 24 Default OFF Option 4 PC5108 Mo...

Страница 22: ...lt 05 I___I___I Zone 1 05 I___I___I Zone 2 10 Skyroute CL3050 Mode of Operation Default 01 I___I___I 01 Bell Follower 02 2 Zone 03 8 zone PC5108 11 Skyroute CL3050 Configuration Options 1 Default Opt...

Страница 23: ...59 Hrs Mins 16 System Day Default Opt Option On Option Off ON I___I 1 Sunday Disabled OFF I___I 2 Monday Disabled OFF I___I 3 Tuesday Disabled OFF I___I 4 Wednesday Disabled OFF I___I 5 Thursday Disab...

Страница 24: ...es Disabled ON I___I 7 System Maintenance Events Disabled ON I___I 8 Generic Zone Reporting Detailed Zone Reporting 21 System Event Communication Options Default Opt Option On Option Off ON I___I 1 In...

Страница 25: ...ndication This value is transmitted to Connect 24 during the periodic test transmission and can be viewed after power up by pressing the enroll button SID System Identification Number ID Number of the...

Страница 26: ...AXX E154 Water Zone WHXX R154 Freezer Zone ZAXX E140 Freezer Zone ZHXX R140 Sprinkler Zone SAXX E110 Sprinkler Zone SHXX R110 Hold up Zone HAXX E122 Hold up Zone HHXX R122 Zone Fault Alarms Zone Fault...

Страница 27: ...X E137 Water Zone TRXX R137 Freezer Zone TAXX E137 Freezer Zone TRXX R137 Sprinkler Zone STXX E200 Sprinkler Zone SJXX R200 Hold up Zone TAXX E137 Hold up Zone TRXX R137 Generic Zone Events System Eve...

Страница 28: ...2002 Digital Security Controls Ltd Toronto Canada 1 800 387 3630 www dsc com Printed in Canada 29034531r001 Forward comments about this manual to pubs dsc com...

Отзывы: