Skyroute CL3050 Standalone Wireless Communicator
12
.
Note:
A relay may be required for proper operation in other configurations.
See paragraph 3.3 Terminal Connections.
Option 1 - Low battery
All Modes
If the battery voltage drops below 5.72V
DC
a trouble will be indicated until the
battery voltage rises to 5.87V
DC.
Default -
ON
Option 2 - Input Supply Failure
All Modes
If AC power is absent or if DC power drops below 8.8V
DC
on the RED and BLK
terminals, this
trouble is indicated. Default
-
ON
Option 3 - Zone Fault/Tamper (DEOL Only)
Modes 2, 3
A trouble will be indicated if any zone reports a fault or tamper condition. In Sec-
tion [11], Option [2] must be set to
OFF
and Option [3] must be set to
ON
for this
option to be enabled.
Default -
OFF
Option 4 - No Service Available
All Modes
This trouble is indicated If the system is unable to detect cellular service.
Default -
ON
Option 5 - Radio Failure
All Modes
This trouble is indicated if there is an internal fault with the cellular radio.
Default -
ON
Option 6 - PC5108 Failure
Mode 3
This trouble is indicated if a PC5108 supervisory or Keybus fault occurs.
Note
The PC5108 tamper is communicated only, therefore it can only be
enabled by turning on section 20 option 7 and section 21 option 5.
There is no local annunciation for this event.
Default -
ON
Option 7 - Failure to Communicate (FTC)
All Modes
This trouble will be indicated if no acknowledgement has been received from
Connect 24
after three attempts.
Default -
ON
Option 8 - Skyroute CL3050 Tamper
All Modes
This trouble will be indicated if the cover is removed from the Skyroute CL3050
activating the on-board tamper switch.
Default -
OFF
Zx COM
Control Panel
RED BLK YEL GRN COM PGM
5.6K
Ω
Skyroute CL3050
Содержание Skyroute CL3050
Страница 6: ...ii...