background image

4

Guidelines for Locating Smoke Detectors

Experience has shown that all hostile fires in family living units
generate smoke to a greater or lesser extent. Experiments using
typical fires in family living units indicate that detectable quantities
of smoke precede detectable levels of heat in most cases. For these
reasons, smoke detectors should be installed outside of each
sleeping area and on each additional story of the family unit.
The following information is for general guidance only and it is
recommended that the smoke detector manufacturer's literature be
used for detailed installation instructions.

It is recommended that additional smoke detectors beyond those
required be installed for increased protection. The added areas
include: basement, bedrooms, dining rooms, furnace room, utility
room and hallways not protected by the required detectors.

Bedroom

Bedroom

Basement

Living
Room

Dining

Room

Bedroom

Bedroom

Bedroom

Living Room

Kitchen

FIG. 1:  A smoke detector should be located between the

FIG. 1:  A smoke detector should be located between the

FIG. 1:  A smoke detector should be located between the

FIG. 1:  A smoke detector should be located between the

FIG. 1:  A smoke detector should be located between the
sleeping area and the rest of the family unit.

sleeping area and the rest of the family unit.

sleeping area and the rest of the family unit.

sleeping area and the rest of the family unit.

sleeping area and the rest of the family unit.

FIG. 3:  A smoke detector should be located on each story of

FIG. 3:  A smoke detector should be located on each story of

FIG. 3:  A smoke detector should be located on each story of

FIG. 3:  A smoke detector should be located on each story of

FIG. 3:  A smoke detector should be located on each story of
the living unit.

the living unit.

the living unit.

the living unit.

the living unit.

NEVER

HERE

Acceptable

here

Top of detector

acceptable here

12"

(0.3m)

Max.

4"

(0.1m)

Max.

4"

(0.1m)

Ceiling

Wall

NOTE: Measurements shown are to

the closest edge of the detector.

FIG. 4:  Smoke Detector mounting - “Dead” Air Space. The

FIG. 4:  Smoke Detector mounting - “Dead” Air Space. The

FIG. 4:  Smoke Detector mounting - “Dead” Air Space. The

FIG. 4:  Smoke Detector mounting - “Dead” Air Space. The

FIG. 4:  Smoke Detector mounting - “Dead” Air Space. The
smoke from a fire generally rises to the ceiling, spreads out

smoke from a fire generally rises to the ceiling, spreads out

smoke from a fire generally rises to the ceiling, spreads out

smoke from a fire generally rises to the ceiling, spreads out

smoke from a fire generally rises to the ceiling, spreads out
across the ceiling surface and begins to bank down from the

across the ceiling surface and begins to bank down from the

across the ceiling surface and begins to bank down from the

across the ceiling surface and begins to bank down from the

across the ceiling surface and begins to bank down from the
ceiling. The corner where the ceiling and wall meet is an air

ceiling. The corner where the ceiling and wall meet is an air

ceiling. The corner where the ceiling and wall meet is an air

ceiling. The corner where the ceiling and wall meet is an air

ceiling. The corner where the ceiling and wall meet is an air
space into which the smoke may have difficulty penetrating. In

space into which the smoke may have difficulty penetrating. In

space into which the smoke may have difficulty penetrating. In

space into which the smoke may have difficulty penetrating. In

space into which the smoke may have difficulty penetrating. In
most fires, this “dead” air space measures about 4 in. (0.1m)

most fires, this “dead” air space measures about 4 in. (0.1m)

most fires, this “dead” air space measures about 4 in. (0.1m)

most fires, this “dead” air space measures about 4 in. (0.1m)

most fires, this “dead” air space measures about 4 in. (0.1m)
along the ceiling from the corner and about 4 in. (0.1m) down the

along the ceiling from the corner and about 4 in. (0.1m) down the

along the ceiling from the corner and about 4 in. (0.1m) down the

along the ceiling from the corner and about 4 in. (0.1m) down the

along the ceiling from the corner and about 4 in. (0.1m) down the
wall as shown in Figure 4. Detectors should not be placed in the

wall as shown in Figure 4. Detectors should not be placed in the

wall as shown in Figure 4. Detectors should not be placed in the

wall as shown in Figure 4. Detectors should not be placed in the

wall as shown in Figure 4. Detectors should not be placed in the
dead” air space.

dead” air space.

dead” air space.

dead” air space.

dead” air space.

Family Room

Bedroom

Living
Room

Dining

Room

Kitchen

Bedroom

Bedroom

FIG. 2:  In the family living units with more than one sleeping

FIG. 2:  In the family living units with more than one sleeping

FIG. 2:  In the family living units with more than one sleeping

FIG. 2:  In the family living units with more than one sleeping

FIG. 2:  In the family living units with more than one sleeping
area, a smoke detector should be located to protect each

area, a smoke detector should be located to protect each

area, a smoke detector should be located to protect each

area, a smoke detector should be located to protect each

area, a smoke detector should be located to protect each
sleeping area.

sleeping area.

sleeping area.

sleeping area.

sleeping area.

Содержание PC1550

Страница 1: ...9 04 2nd Account Code 9 05 to 10 Reporting Codes 9 05 Zone Alarm Reporting Codes 9 06 Zone Restoral Reporting Codes 9 07 Closing Arming Reporting Codes Partial Closing Reporting Code 9 08 Opening Disa...

Страница 2: ...peration Download Upload capability Programmable auto downloading Swinger shutdown Transmission delay Six access codes Master key code All zones programmable as fire zones Programmable test transmissi...

Страница 3: ...witched AC source and close to the telephone line connection Remove the printed circuit board the mounting hardware and the keypad from the cardboard retainer inside the cabinet Before attaching the c...

Страница 4: ...fire generally rises to the ceiling spreads out across the ceiling surface and begins to bank down from the across the ceiling surface and begins to bank down from the across the ceiling surface and...

Страница 5: ...before going to bed and is useful for users who have a keypad outside areas protected by the interior zones Arming Without Entry Delay To eliminate Entry Delay arm the system using 9 access code An ex...

Страница 6: ...aster Code The installer may choose to not allow the user to program the Master Code section 13 option 2 The 6th code may be changed from a regular code into a One time Use code or Maid s Code section...

Страница 7: ...ammable section 14 option 5 for feedback 3 beeps or silent no buzzer feedback If programmed for audible the buzzer will sound once the key input is accepted keep time When the panel is powered up the...

Страница 8: ...mode For2 digitpairs bothdigitsmustbeprogrammed before pressing the key Only the data entered before pressing the key will be changed in the EEPROM Program Data Review Enter the section you wish to pr...

Страница 9: ...2 digit code 31 TRANSMISSION SENT 1234 31 3 1 FORMAT Extended reporting requires 3 digit Account Code in section 02 or 04 i e Enter 1230 for code 123 Format Code 8 9 A B C depending on receiver type i...

Страница 10: ...ny loop programmed for fire the Trouble light will come ON and the keypad sounder will beep every 10 seconds Thekeypadtroublebuzzerwillsoundandthe Trouble light will come ON regardless of whether the...

Страница 11: ...r zone definitions 2 Exit delay time 001 to 255 seconds This value determines the standard Exit Delay time The factory default exit time is 120 seconds For zone definitions see Section 11 3 Bell cut o...

Страница 12: ...the type of format which will be sent to each of the two telephone numbers programmed in section 01 and 03 For each telephone number enter one digit from the list below See the HEX data programming se...

Страница 13: ...he Exit Delay This option may be used to provide lighting in the exit area or to activate a device when the Exit Delay begins 0C LINKS1000 Interface This option configures the system for use with the...

Страница 14: ...Squawk during Entry Delay OFF No Bell Squawk during Entry Delay 6 ON F Key disabled OFF F Key enabled Factory default When Light 3 is ON Audible Exit Fault When the system is armed and a Standard Del...

Страница 15: ...__________________________________ ZONES Zone Type Protected Area 1 _____________________________ __________________________________________________________________ 2 _____________________________ ___...

Страница 16: ...Closing Arming Reporting Codes Partial Closing Reporting Code Page 9 Access Code 1 Access Code 4 Access Code 2 Access Code 5 Access Code 3 Access Code 6 Partial Closing Code 08 Opening Disarming Repo...

Страница 17: ...sistor loops ON Zone Light 6 Keypad P anic audible bell Keypad P anic silent bell 13 2nd System Option Code Page 11 Default Zone Light ON Zone Light OFF ON Zone Light 1 Call 1st phone only Backup to 2...

Страница 18: ...Light 6 17 System Times Page 11 Default Default 0 3 0 Entry Delay seconds 0 3 0 AC fail transmission delay minutes 1 2 0 Exit Delay seconds 0 5 0 Slow loop response time x 10 ms 0 0 4 Bell Cut off mi...

Страница 19: ...econds 7 08 Strobe Output latched alarm output 03 Utility Output Any Access Code 5 seconds 7 09 Failure to Communicate Output follows trouble 4 04 5 Second Reset Pulse 7 0A PGM ON during Entry Delay 0...

Страница 20: ...liary delay Auxiliary delay normal ON Zone Light 6 60 s bypass on power up Zones active on power up 33 Answering Machine Double Call Timer Page 14 Default 0 6 0 Valid entries are 001 to 249 34 6th Sys...

Страница 21: ...ay consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all the devices does not exceed 100 The Load Number of this unit is 2 AVIS L tiquette de...

Страница 22: ...ds of the Entry Delay to warn that the Entry Delay is about to expire Zone Light 5 Bell Squawk During Entry Delay The bell siren will squawk during the Entry Delay If Zone Light 4 is on the bell siren...

Страница 23: ......

Страница 24: ...l communications peut demander l utilisateur de d brancher un appareil la suite de r parations ou de modifications effectu es par l utilisateur ou cause de mauvais fonctionnement Pour sa propre protec...

Отзывы: