background image

3

Z1

COM Z2

NC

NO

NC

NC

END OF LINE

RESISTOR

1k

0.5W

END OF LINE

RESISTOR

1k

0.5W

EOL RESISTOR

LOOPS USING

NO & NC

DEVICES

EOL RESISTOR

LOOPS USING

NC DEVICES

ONLY

Fire Zone Wiring

Any one of the 6 zones may be programmed as a Fire Loop. See
Programming Guide section [11].

Smoke detectors should be the latching type and have Normally
Open (N.O.) alarm initiating contacts. Power wiring from the AUX +
/ PGM terminals should be supervised using an RM-1 relay after the
last smoke detector. The RM-1 N.O. contacts (closed with power
applied) should be wired in series with the alarm initiating end-of-
line resistor so that should power to the detector(s) fail, a fire loop
trouble will be initiated.

Burglary Zone Wiring

Burglary zone definition, (eg. Delay, Instant, 24 Hr. etc.) is
programmed via the keypad. See the Programming Guide, section
[11].

Battery Connection

If the battery is reverse connected, the 5 A fuse will blow. The
battery charging voltage is factory set and normally needs no
adjustment. If the battery charging voltage is out of adjustment,
contact your service representative.

If AC power is OFF and the battery voltage is approximately 9.5V or
lower, the battery will be disconnected and the panel will power
down. To power up again, the AC will have to be re-established.

Telephone Line Wiring

NOTE:

Ensure that plugs and jacks meet the dimension, tolerance
and metallic plating requirements of 47 C.F.R. Part 68,
Subpart F.

WARNING

FCC restricts using this equipment on certain types of telephone
lines. Also, do not use this equipment on a telephone line equipped
with a “call holding” feature, as the tone generated may interfere
with the communicator operations.

Do not connect the alarm panel communicator to telephone
lines intended for use with facsimile (FAX) machines. These
lines may incorporate a voice filter which disconnects the line
if other than FAX signals are detected, resulting in incomplete
transmissions.

Installation

Mounting the Panel

Select a dry location close to an unswitched AC source and close
to the telephone line connection. Remove the printed circuit board,
the mounting hardware and the keypad from the cardboard retainer
inside the cabinet. Before attaching the cabinet to the wall, press
the four white nylon printed circuit board mounting studs into the
cabinet from the back. Once the cabinet is mounted to the wall, pull
all the cables into the cabinet and prepare them for connection. Use
a meter to test the wiring for opens, shorts and grounds. Press the
circuit board onto the white nylon mounting studs. Complete all
wiring to the control panel before applying AC power or connecting
the battery. Do not plug the transformer into an outlet that is
controlled by a switch.

NOTE: See Control Panel Wiring Diagram inside the back cover
for more information.

Mounting the Keypad

Keypads should be located close to the designated “Entry-Exit”
door(s) and mounted at a height convenient for all users.

NOTE:

  Complete all wiring to the control panel before applying AC

power or connecting the battery.

Auxiliary Power
Connection

The auxiliary power supply can be used
to power keypads, motion detectors and
other devices that require 11 V

DC

. See the

Fire Zone Wiring section for the
connection of 4-wire smoke detectors.
The total load for the auxiliary power
output must be calculated for all devices
connected across the AUX +/- terminals
and for devices connected between the
AUX + and PGM terminals. The output
current cannot exceed 475 mA. Allow 35
mA for each PC1500RK keypad
connected to the panel.

PGM Terminal Connections

The PGM terminal is a switched negative output which can be
controlled by various programming options (See Programming
Guide section [24]). Devices controlled by the PGM output must be
connected between the PGM terminal, which is (-) and the Aux. (+)
terminal.

Bell/Siren Connection

Observe polarity when connecting siren drivers, sirens and polarized
bells.

Keypad Wiring

Up to three keypads may be connected in parallel. Do not connect
multiple keypads on the same keypad wire run. For Standby
Loading purposes, use a current draw of 35 mA per keypad. This
represents the panel in the disarmed state with two zones open.

AUX

12VDC

FUSE

1 A

LOAD

LOAD

Содержание PC1550

Страница 1: ...9 04 2nd Account Code 9 05 to 10 Reporting Codes 9 05 Zone Alarm Reporting Codes 9 06 Zone Restoral Reporting Codes 9 07 Closing Arming Reporting Codes Partial Closing Reporting Code 9 08 Opening Disa...

Страница 2: ...peration Download Upload capability Programmable auto downloading Swinger shutdown Transmission delay Six access codes Master key code All zones programmable as fire zones Programmable test transmissi...

Страница 3: ...witched AC source and close to the telephone line connection Remove the printed circuit board the mounting hardware and the keypad from the cardboard retainer inside the cabinet Before attaching the c...

Страница 4: ...fire generally rises to the ceiling spreads out across the ceiling surface and begins to bank down from the across the ceiling surface and begins to bank down from the across the ceiling surface and...

Страница 5: ...before going to bed and is useful for users who have a keypad outside areas protected by the interior zones Arming Without Entry Delay To eliminate Entry Delay arm the system using 9 access code An ex...

Страница 6: ...aster Code The installer may choose to not allow the user to program the Master Code section 13 option 2 The 6th code may be changed from a regular code into a One time Use code or Maid s Code section...

Страница 7: ...ammable section 14 option 5 for feedback 3 beeps or silent no buzzer feedback If programmed for audible the buzzer will sound once the key input is accepted keep time When the panel is powered up the...

Страница 8: ...mode For2 digitpairs bothdigitsmustbeprogrammed before pressing the key Only the data entered before pressing the key will be changed in the EEPROM Program Data Review Enter the section you wish to pr...

Страница 9: ...2 digit code 31 TRANSMISSION SENT 1234 31 3 1 FORMAT Extended reporting requires 3 digit Account Code in section 02 or 04 i e Enter 1230 for code 123 Format Code 8 9 A B C depending on receiver type i...

Страница 10: ...ny loop programmed for fire the Trouble light will come ON and the keypad sounder will beep every 10 seconds Thekeypadtroublebuzzerwillsoundandthe Trouble light will come ON regardless of whether the...

Страница 11: ...r zone definitions 2 Exit delay time 001 to 255 seconds This value determines the standard Exit Delay time The factory default exit time is 120 seconds For zone definitions see Section 11 3 Bell cut o...

Страница 12: ...the type of format which will be sent to each of the two telephone numbers programmed in section 01 and 03 For each telephone number enter one digit from the list below See the HEX data programming se...

Страница 13: ...he Exit Delay This option may be used to provide lighting in the exit area or to activate a device when the Exit Delay begins 0C LINKS1000 Interface This option configures the system for use with the...

Страница 14: ...Squawk during Entry Delay OFF No Bell Squawk during Entry Delay 6 ON F Key disabled OFF F Key enabled Factory default When Light 3 is ON Audible Exit Fault When the system is armed and a Standard Del...

Страница 15: ...__________________________________ ZONES Zone Type Protected Area 1 _____________________________ __________________________________________________________________ 2 _____________________________ ___...

Страница 16: ...Closing Arming Reporting Codes Partial Closing Reporting Code Page 9 Access Code 1 Access Code 4 Access Code 2 Access Code 5 Access Code 3 Access Code 6 Partial Closing Code 08 Opening Disarming Repo...

Страница 17: ...sistor loops ON Zone Light 6 Keypad P anic audible bell Keypad P anic silent bell 13 2nd System Option Code Page 11 Default Zone Light ON Zone Light OFF ON Zone Light 1 Call 1st phone only Backup to 2...

Страница 18: ...Light 6 17 System Times Page 11 Default Default 0 3 0 Entry Delay seconds 0 3 0 AC fail transmission delay minutes 1 2 0 Exit Delay seconds 0 5 0 Slow loop response time x 10 ms 0 0 4 Bell Cut off mi...

Страница 19: ...econds 7 08 Strobe Output latched alarm output 03 Utility Output Any Access Code 5 seconds 7 09 Failure to Communicate Output follows trouble 4 04 5 Second Reset Pulse 7 0A PGM ON during Entry Delay 0...

Страница 20: ...liary delay Auxiliary delay normal ON Zone Light 6 60 s bypass on power up Zones active on power up 33 Answering Machine Double Call Timer Page 14 Default 0 6 0 Valid entries are 001 to 249 34 6th Sys...

Страница 21: ...ay consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all the devices does not exceed 100 The Load Number of this unit is 2 AVIS L tiquette de...

Страница 22: ...ds of the Entry Delay to warn that the Entry Delay is about to expire Zone Light 5 Bell Squawk During Entry Delay The bell siren will squawk during the Entry Delay If Zone Light 4 is on the bell siren...

Страница 23: ......

Страница 24: ...l communications peut demander l utilisateur de d brancher un appareil la suite de r parations ou de modifications effectu es par l utilisateur ou cause de mauvais fonctionnement Pour sa propre protec...

Отзывы: