13

Openings “B”

i.e. B2 = opening by user 2

Closings “C”

i.e. C4 = closing by user 4

Troubles “F”

i.e. F5 = trouble from source 5

Miscellaneous “D”

i.e. D1 = partial closing

[24]

Programmable Output Options
(PGM Terminal)

The PGM output can be programmed in this section to operate in
response to various panel operations. The output pulse connects
the PGM terminal to the negative power rail.

[01] Ground Start Pulse

This option provides a 2-second output pulse before dialling
begins to obtain the dial tone on Ground Start telephone
equipment.

[02] Utility Output, no Access Code

When activated by entering the [

*

][7] command, the PGM

output will go low for 5 seconds and the keypad buzzer will
sound.

[03] Utility Output, any Access Code

The same as [02], except the command is [

*

][7] [any valid

access code].

[04] 5-Second Reset Pulse

When this option is selected, the PGM output is normally low.
That is, it is just the reverse of all other options which are
normally high and go low when activated. This option is
normally used as the negative return for power to 4-wire
smoke detectors (positive comes from the AUX + terminal). To
activate this output (to reset smoke detectors), enter  [

*

][7].

The PGM terminal will go high (open circuit), and thus remove
power from the devices connected. The keypad buzzer will
sound for the 5-second period.

[05] Courtesy Pulse

This option provides an output which follows the entry and exit
times. It can be used to turn on a courtesy light near the exit
door for the duration of the entry / exit times.

[06] Keypad Buzzer Follow Mode

The PGM output will go low as long as the keypad buzzer is
ON for “24 Hour Buzzer Zone”, “Door Chime”, “Entry Delay”
and “Auto-Arm Alert”.

[07] System Status (Armed / Disarmed)

The PGM output switches to and remains at ground as long as
the panel is armed. The output goes high (open) while the
panel is disarmed.

[08] Strobe Output (Latched Alarm Output)

The PGM switches to ground on an alarm and remains low
until the panel is disarmed. It can be used to indicate that an
alarm has occurred before entering the premises.

[09] Failure to Communicate

The PGM output switches to ground if the systems fails to
communicate after 8 attempts to each phone number that will
be tried according to the communicator call direction options.
The output remains low until a successful communication
takes place or until trouble #4 is cleared from the keypad. This
option can be used to tie two systems together so that if one
fails to communicate, the other system will report the failure.

[0A] PGM ON during Entry Delay

The PGM output will be switched on for the duration of the
Entry Delay. This option may be used to provide lighting in the
entrance area, or to activate a device when the Entry Delay
begins.

[0B] PGM ON during Exit Delay

The PGM output will be switched on for the duration of the Exit
Delay. This option may be used to provide lighting in the exit
area, or to activate a device when the Exit Delay begins.

[0C] LINKS1000 Interface

This option configures the system for use with the LINKS1000
Cellular Alarm Communicator. Refer to the LINKS Installation
Manual for further programming instructions.

[25]

Communicator Call Directions

This section requires four single digit entries using digits 0 to 3 only.
This section defines how the communicator will call the telephone
numbers programmed in sections [01] and [03] to report the
following events:

Zone Alarms and Restorals

Access Codes Openings and Closings

Priority Alarms and Restorals

Maintenance Alarms and Restorals

Enter ONE digit from the list below for each of the above categories.
Factory default = 1 for all 4 code groups.

[0]

Disables the function (no transmission for the group)

[1]

Call 1st phone number and back-up to the 2nd phone

number when section [13] light 1 is set to OFF and the panel
has made 8 unsuccessful tries on the 1st phone number.

[2]

Call the 2nd phone number only

[3]

Always call both phone numbers

If [#] is pressed during data entry, you will be returned to the
installer’s programming mode and data for this section will NOT be
saved.

[26]

Downloading Telephone Number

This telephone number is used by the panel to call the downloading
computer when a request to call is make by entering [

*

][4] or for

an auto-download. See section [14] 3rd System Option Code, lights
2 and 3. See section [01] 1st Phone Number for instructions on
programming the downloading telephone number.

[27]

Downloading Access Code

This 4-digit code allows the panel to confirm that it is communicating
with a valid downloading computer. Enter 4 digits using the numbers
0 through 9 only. The factory default code is [1515].

[28]

Panel Identification Code

This 4-digit code allows the downloading computer to confirm the
identity of the control panel. Enter 4 digits using the number keys
0 through 9 only. The factory default code is [1501].

[29]

Number of Rings Before Answering

Section [29] is used to set the number of rings before the panel will
pickup and answer the call. See section [31] for information on
using the panel with an answering machine connected to the same
phone line.

[30]

Reset to Factory Default

Software

Entering [30] will perform a software reset to the factory default
values. Once this command is entered, the keypad buzzer will
beep several times. The “Trouble” LED will be ON during the reset
sequence.

Hardware

If the installer’s code is forgotten and a software reset cannot be
performed, the panel can be reset to the factory default values with
the following method.

1. Remove all power, AC and battery, from the panel.

2. Short the pads on the panel labelled EEPROM RESET.

3. While maintaining the short, power-up the panel and wait for at

least 10 seconds before removing the short.

4. Upon removal of the short, the keypad buzzer will beep and the

panel will be reset to the factory default values.

[31]

4th System Option Code

Содержание PC1550

Страница 1: ...9 04 2nd Account Code 9 05 to 10 Reporting Codes 9 05 Zone Alarm Reporting Codes 9 06 Zone Restoral Reporting Codes 9 07 Closing Arming Reporting Codes Partial Closing Reporting Code 9 08 Opening Disa...

Страница 2: ...peration Download Upload capability Programmable auto downloading Swinger shutdown Transmission delay Six access codes Master key code All zones programmable as fire zones Programmable test transmissi...

Страница 3: ...witched AC source and close to the telephone line connection Remove the printed circuit board the mounting hardware and the keypad from the cardboard retainer inside the cabinet Before attaching the c...

Страница 4: ...fire generally rises to the ceiling spreads out across the ceiling surface and begins to bank down from the across the ceiling surface and begins to bank down from the across the ceiling surface and...

Страница 5: ...before going to bed and is useful for users who have a keypad outside areas protected by the interior zones Arming Without Entry Delay To eliminate Entry Delay arm the system using 9 access code An ex...

Страница 6: ...aster Code The installer may choose to not allow the user to program the Master Code section 13 option 2 The 6th code may be changed from a regular code into a One time Use code or Maid s Code section...

Страница 7: ...ammable section 14 option 5 for feedback 3 beeps or silent no buzzer feedback If programmed for audible the buzzer will sound once the key input is accepted keep time When the panel is powered up the...

Страница 8: ...mode For2 digitpairs bothdigitsmustbeprogrammed before pressing the key Only the data entered before pressing the key will be changed in the EEPROM Program Data Review Enter the section you wish to pr...

Страница 9: ...2 digit code 31 TRANSMISSION SENT 1234 31 3 1 FORMAT Extended reporting requires 3 digit Account Code in section 02 or 04 i e Enter 1230 for code 123 Format Code 8 9 A B C depending on receiver type i...

Страница 10: ...ny loop programmed for fire the Trouble light will come ON and the keypad sounder will beep every 10 seconds Thekeypadtroublebuzzerwillsoundandthe Trouble light will come ON regardless of whether the...

Страница 11: ...r zone definitions 2 Exit delay time 001 to 255 seconds This value determines the standard Exit Delay time The factory default exit time is 120 seconds For zone definitions see Section 11 3 Bell cut o...

Страница 12: ...the type of format which will be sent to each of the two telephone numbers programmed in section 01 and 03 For each telephone number enter one digit from the list below See the HEX data programming se...

Страница 13: ...he Exit Delay This option may be used to provide lighting in the exit area or to activate a device when the Exit Delay begins 0C LINKS1000 Interface This option configures the system for use with the...

Страница 14: ...Squawk during Entry Delay OFF No Bell Squawk during Entry Delay 6 ON F Key disabled OFF F Key enabled Factory default When Light 3 is ON Audible Exit Fault When the system is armed and a Standard Del...

Страница 15: ...__________________________________ ZONES Zone Type Protected Area 1 _____________________________ __________________________________________________________________ 2 _____________________________ ___...

Страница 16: ...Closing Arming Reporting Codes Partial Closing Reporting Code Page 9 Access Code 1 Access Code 4 Access Code 2 Access Code 5 Access Code 3 Access Code 6 Partial Closing Code 08 Opening Disarming Repo...

Страница 17: ...sistor loops ON Zone Light 6 Keypad P anic audible bell Keypad P anic silent bell 13 2nd System Option Code Page 11 Default Zone Light ON Zone Light OFF ON Zone Light 1 Call 1st phone only Backup to 2...

Страница 18: ...Light 6 17 System Times Page 11 Default Default 0 3 0 Entry Delay seconds 0 3 0 AC fail transmission delay minutes 1 2 0 Exit Delay seconds 0 5 0 Slow loop response time x 10 ms 0 0 4 Bell Cut off mi...

Страница 19: ...econds 7 08 Strobe Output latched alarm output 03 Utility Output Any Access Code 5 seconds 7 09 Failure to Communicate Output follows trouble 4 04 5 Second Reset Pulse 7 0A PGM ON during Entry Delay 0...

Страница 20: ...liary delay Auxiliary delay normal ON Zone Light 6 60 s bypass on power up Zones active on power up 33 Answering Machine Double Call Timer Page 14 Default 0 6 0 Valid entries are 001 to 249 34 6th Sys...

Страница 21: ...ay consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all the devices does not exceed 100 The Load Number of this unit is 2 AVIS L tiquette de...

Страница 22: ...ds of the Entry Delay to warn that the Entry Delay is about to expire Zone Light 5 Bell Squawk During Entry Delay The bell siren will squawk during the Entry Delay If Zone Light 4 is on the bell siren...

Страница 23: ......

Страница 24: ...l communications peut demander l utilisateur de d brancher un appareil la suite de r parations ou de modifications effectu es par l utilisateur ou cause de mauvais fonctionnement Pour sa propre protec...

Отзывы: