[25] Communicator Call Directions

This section requires four single digit entries using digits 0 to 3
only.  This section defines how the communicator will call the
telephone numbers programmed in sections [01] and [03] to
report the following events:

Zone Alarms and Restorals
Access Codes Openings and Closings
Priority Alarms and Restorals
Maintenance Alarms and Restorals

Enter ONE digit from the list below for each of the above
categories.  Factory default = 1 for all 4 code groups.

[0]

Disables the function (no transmission for the group)

[1]

Call 1st phone number and back-up to the 2nd

phone number when section [13] light 1 is set to OFF
and the panel has made 8 unsuccessful tries on the
1st phone number.

[2]

Call the 2nd phone number only

[3]

Always call both phone numbers

If the [#] key is pressed during data entry, you will be returned
to the installer’s programming mode and data for this section
will NOT be saved.

[26]

Downloading Telephone Number

This telephone number is used by the panel to call the
downloading computer when a request to call is make by
entering [

][4] or for an auto-download.  See section [14] 3rd

System Option Code, lights 2 and 3. See section [01] 1st
Phone Number for instructions on programming the
downloading telephone number.

[27]

Downloading Access Code

This 4-digit code allows the panel to confirm that it is
communicating with a valid downloading computer.  Enter 4
digits using the numbers 0 through 9 only.  The factory default
code is [1515].

[28]

Panel Identification Code

This 4-digit code allows the downloading computer to confirm
the identity of the control panel.  Enter 4 digits using the
number keys 0 through 9 only.  The factory default code is
[1501].

[29]

Number of Rings Before

Answering

Section [29] is used to set the number of rings before the
panel will pickup and answer the call.  See section [31] for
information on using the panel with an answering machine
connected to the same phone line.

[30]

Reset to Factory Default

Software

Entering [30] will perform a software reset to the factory
default values.  Once this command is entered, the keypad
buzzer will beep several times.  The “Trouble” LED will be ON
during the reset sequence.

Hardware

If the installer’s code is forgotten and a software reset cannot be
performed, the panel can be reset to the factory default values
with the following method.

1.

Remove all power, AC and battery, from the panel.

2.

Short the pads on the panel labelled EEPROM RESET.

3.

While maintaining the short, power-up the panel and wait
for at least 10 seconds before removing the short.

4.

Upon removal of the short, the keypad buzzer will beep
and the panel will be reset to the factory default values.

[31]

4th System Option Code

Use the same method of programming as section [12].

ZONE

LIGHT

[1]

ON =

Able to answer call from downloading
computer

• OFF =

Cannot answer call from downloading
computer

[2]

ON =

Enable callback to downloading computer

• OFF =

Disable callback to downloading
computer

[3]

ON =

Enable answering machine over-ride

• OFF =

Disable answering machine over-ride

[4]

ON =

Show bypass status while armed or
disarmed

• OFF =

Show bypass status while disarmed only

[5]

ON =

Set for AC = 50 Hz

• OFF =

Set for AC = 60 Hz

[6]

ON =

Restore on bell time-out (if zone is
restored)

• OFF =

Restore as follower (when zone restores)

• Factory default

Downloading and Answering Machines

If zone light [3] is ON and the panel is called for 1 or 2 rings
only and then called back within a variable time from 1 to 249
seconds (this time set in section [33]), the panel will then
answer the second call on the first ring.

If zone light [3] is OFF, it is assumed that there is no
answering machine connected to the telephone line, and the
panel will capture the line after the set number of rings.

If zone light [3] is OFF and an answering machine is connected
and is set to answer before the panel, the panel will be unable
to receive a call from the downloading computer.  If the panel
is set to answer before the answering machine, the answering
machine will be unable to receive incoming calls.

Содержание PC1510

Страница 1: ...N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read Software Version 4 1 DLS 1 V6 5 and up ...

Страница 2: ...his unit is 2 AVIS L étiquette de l Industrie Canada identifie le matériel homologué Cette étiquette certifie que le matériel est conforme à certaines normes de protection d exploitation et de sécurité des réseaux de télécommunications Industrie Canada n assure toutefois pas que le matériel fonctionnera à la satisfaction de l utilisateur Avant d installer ce matériel l utilisateur doit s assurer q...

Страница 3: ...ditions 7 Alarm Memory 7 Downloading Callup Command 7 User Programming Commands 7 EEPROM Reset 8 User Function Commands 8 Setting the Clock 6 Master Code 1 8 Set Auto Arm Time 6 Master Code 2 8 Quick Arm ON OFF 6 Master Code 4 8 Auto Arm ON OFF 6 Master Code 5 8 Door Chime ON OFF 6 Master Code 6 8 Bell Test 6 Master Code 8 9 Installer s Test ON OFF 6 Master Code 0 9 Utility Output Command 7 or 7 A...

Страница 4: ... Option Code 14 14 3rd System Option Code 14 15 Communication Variables 14 16 Zone Bypass Mask 14 17 System Times 14 18 Auxiliary Delay Loop Entry Exit Times 15 19 System Clock Times 15 20 New Installer s Code 15 21 New Master Code 15 22 2nd Master Code 15 23 Communication Formats 15 24 Programmable Output Options PGM Terminal 16 25 Communicator Call Directions 17 26 Downloading Telephone Number 1...

Страница 5: ...delay Six access codes Master key code All zones programmable as fire zones Temporal fire bell pattern Programmable test transmission Zone bypass from the keypad Six zones Bell Siren zone Programmable output Four programmable options Three dedicated keys Fire Emergency Panic Backlit aesthetically pleasing keypad PC1510 Control Panel Six fully programmable zones EOL resistor 30 EOL supervised optio...

Страница 6: ...all wiring to the control panel before applying AC power or connecting the battery Mounting the Keypad Keypads should be located close to the designated Entry Exit door s and mounted at a height convenient for all users NOTE Complete all wiring to the control panel before applying AC power or connecting the battery Auxiliary Power Connection The auxiliary power supply can be used to power keypads ...

Страница 7: ...hart Z1 COM Z2 NC NO NC NC 5600Ω 0 5W END OF LINE RESISTOR 5600Ω 0 5W END OF LINE RESISTOR EOL RESISTOR LOOPS USING NO NC DEVICES EOL RESISTOR LOOPS USING NC DEVICES ONLY Zone Wiring Chart Figures based on maximum loop resistance of 100 ohms Wire Gauge Max Run Length to AWG End of Lineresistor 24 1900 579m 22 3000 914m 20 4900 1493m 19 6200 1889m 18 7800 2377m Thewiringtablegivesthewirerunlengthfr...

Страница 8: ...from the alarm panel communicator RED BATTERY CHARGE CURRENT IS 360 mA MAX 12 VOLT 4 Ah GEL CELL BATTERY CAPACITY FOR EMERGENCY STANDBY IS AT LEAST 4 HOURS IF THE TOTAL LOAD BELL AUX OUTPUTS IS 800 mA OR LESS BLK Battery Connection If the battery is reverse connected the 5 A fuse will blow The battery charging voltage is factory set and normally needs no adjustment Ifthebatterychargingvoltageisout...

Страница 9: ...iving unit living unit Smoke Detector mounting Dead Air Space The smoke Smoke Detector mounting Dead Air Space The smoke Smoke Detector mounting Dead Air Space The smoke Smoke Detector mounting Dead Air Space The smoke Smoke Detector mounting Dead Air Space The smoke from a fire generally rises to the ceiling spreads out from a fire generally rises to the ceiling spreads out from a fire generally ...

Страница 10: ...ed when the panel is disarmed KEYPAD FUNCTIONS Introduction The PC1500RK remote keypad provides complete information and control of the PC1510 control panel The panel can be fully programmed from the keypad The 6 zone lights provide alarm and status indication for the alarm circuits Each zone can be programmed to be a burglary zone or a fire zone The five function lights guide the user in operatin...

Страница 11: ...it from the trouble view mode 5 Fire Alarm Circuit Trouble An open circuit on the zone programmed as a fire loop will initiate a trouble See Zone Definitions section 11 for fire loop zone assignment 6 Loss of Time on System Clock When the PC1510 is powered up or reset the internal time of day clock needs to be reset to the correct time The trouble is cleared after entering the trouble view mode th...

Страница 12: ...fter use This function will turn off automatically on arming Items 4 5 6 and 0 turn ON and OFF various features When the item key is pressed and the feature is being turned ON the keypad sounder will beep 3 times If the feature is being turned OFF the sounder will give one long beep Pressing item 8 gives a 2 second Bell Siren and Keypad Light and Buzzer test Setting the Clock 6 Master Code 1 The S...

Страница 13: ...passed Note that the 1 command will not remove bypasses from zones that have been manually bypassed Quick Exit Command 0 when Armed Entering 0 when the system is armed will allow the user to exit the premises through any delay zone without altering the status of the system if the Quick Exit feature is enabled The Quick Exit feature can be enabled by turning on option 4 in programmingsection 32 For...

Страница 14: ...ter 2 digits for the section you wish to program The sections for the PC1510 panel range from 01 to 36 and each section can be programmed independently Section 00 is reserved for binary programming which is normally done on instruction from factory technical personnel Once the 2 digits for the section you wish to program are entered the Armed light will go OFF the Ready light will go ON steadily a...

Страница 15: ...factory technicalpersonnelforspecializedprogrammingnotcovered by the standard programming instructions 01 1st Phone Number This is the first telephone number the Communicator will dial See Section 25 Communicator Call Direction After entering section 01 for programming enter the telephone number the same way you would dial it on a touch tone phone Press after the last digit to complete the telepho...

Страница 16: ...e F A and P keys will only take place if the appropriate sections in 09 are programmed with a reporting code 10 Maintenance Alarms and Restorals These reporting codes are used by the communicator to transmit the following list of alarms and restorals See section 05 as a guide to programming Low battery alarm AC failure alarm Fuse failure alarm Low battery restore AC failure restore Fuse failure re...

Страница 17: ...municator is delayed 30 seconds If the alarm is acknowledged before the 30 second delay has expired pressing the key will silence the alarm and abort the transmission If the alarm is NOT acknowledged within the 30 second period transmission will proceed and cannot be aborted If the alarm has been silenced and all smoke detectors are not restored to normal the alarm will re sound after 90 seconds 3...

Страница 18: ...ng data The first 2 digit number defines the number of attempts alarm and restoral pairs perzonethatthecommunicatorwillmakebeforeitshuts downforthatzone swingershutdown Thenumberofattempts is for the period as defined in the 1st System Option Code Section zone light 2 The number of attempts may be programmedfrom 00 to 99 where 00 meansthecommunicator will never shut down The fire zone cannot be sh...

Страница 19: ... 0 through 9 as numbers in the code do not press the or keys If an error is made entering the code complete entry of the 4 digits then enter the section number again to enter the correct code Do not press or while entering the code 22 2nd Master Code Once the section number has been entered 20 21 or 22 enter a new 4 digit code Only use digits 0 through 9 as code numbers Do not press the or keys If...

Страница 20: ... option is selected the PGM output is normally low That is it is just the reverse of all other options which are normally high and go low when activated This option is normally used as the negative return for power to 4 wire smoke detectors positive comes from the AUX terminal To activate this output to reset smoke detectors enter the 7 command The PGM terminal will go high open circuit and thus r...

Страница 21: ...ng machine connected to the same phone line 30 Reset to Factory Default Software Entering 30 will perform a software reset to the factory default values Once this command is entered the keypad buzzer will beep several times The Trouble LED will be ON during the reset sequence Hardware Iftheinstaller scodeisforgottenandasoftwareresetcannotbe performed thepanelcanberesettothefactorydefaultvalues wit...

Страница 22: ... the keypad will sound a constant tone during the Entry Delay During the last 10 seconds of the Entry Delay the keypad will sound a pulsing tone to warn that the delay is about to expire When the urgency option is selected for the audibile Exit Delay the keypad will sound a pulsing tone during the Exit Delay During the last 10 seconds of the Exit Delay the keypad will sound a faster pulsing tone t...

Страница 23: ..._________________________________ ZONES Zone Type Protected Area 1 _____________________________ __________________________________________________________________ 2 _____________________________ __________________________________________________________________ 3 _____________________________ __________________________________________________________________ 4 _____________________________ ______...

Страница 24: ...the digit 0 in the account code For a 3 digit code enter 0 for the 4th digit 03 2nd Phone Number Page 11 04 2nd Account Code Page 11 05 Zone Alarm Reporting Codes Page 11 For single digit reporting codes enter 0 as the second digit Enter 1 HEX A to transmit a zero Zone 1 Alarm Zone 2 Alarm Zone 3 Alarm Zone 4 Alarm Zone 5 Alarm Zone 6 Alarm 06 Zone Restoral Reporting Codes Page 11 For single digit...

Страница 25: ...g if an alarm occured during the previous armed period Access Code 1 Access Code 2 Access Code 3 Access Code 4 Access Code 5 Access Code 6 After Alarm Code 09 Priority Alarms and Restorals Page 12 Actuation of the F A or P keys will immediately transmit both an alarm and restoral code There is no delay on the restoral code transmission Fire Loop Trouble Keypad P anic Alarm Keypad F ire Alarm Keypa...

Страница 26: ... 0 2 Zone 4 0 2 Zone 5 0 8 Zone 6 First Digit Second Digit 0 Slow Audible 0 Standard Delay 1 Slow Silent 1 Instant 2 Fast Audible 2 Interior 3 Fast Silent 3 Interior Home Away 4 24 Hour Bell 5 24 Hour Bell Buzzer 6 24 Hour Buzzer 7 Aux Delay Uses Auxiliary Entry Exit Times 8 Fire Any one zone may be set as a FIRE zone 12 1st System Option Code Page 13 Default Zone Light ON Zone Light OFF OFF Zone ...

Страница 27: ...e Light OFF OFF Zone Light 1 User code required for bypass Code not required OFF Zone Light 2 4 Enabled 4 Disabled OFF Zone Light 3 Periodic downloading Periodic test transmit OFF Zone Light 4 4 access code required 4 no code required ON Zone Light 5 P anic audible buzzer P anic silent buzzer OFF Zone Light 6 Partial closing identified Not identified 15 Communication Variables Page 14 Default 0 3 ...

Страница 28: ...smission delay minutes 0 5 0 Slow loop response time x 10 ms 0 3 0 Test transmission cycle or auto download cycle time days Valid entries are 001 to 255 Do not enter 000 Do not enter 000 Do not enter 000 Do not enter 000 Do not enter 000 18 Auxiliary Delay Loop Entry Exit Times Page 15 Default 0 4 5 Entry Time seconds 1 2 0 Exit Time seconds Valid entries are 001 to 255 19 System Clock Times Page ...

Страница 29: ...hake 3 1 4 1 and 4 2 non extended formats 1 SESCOA FRANKLIN DCI VERTEX 20 BPS 2300 Hz handshake 3 1 4 1 and 4 2 non extended formats 2 SILENT KNIGHT FAST 20 BPS 1400 Hz handshake 3 1 4 1 and 4 2 non extended formats 3 RADIONICS 2300 1400 Hz handshake 3 1 4 2 non extended formats 4 RADIONICS 2300 1400 Hz handshake 3 1 4 2 non extended with parity format 5 DO NOT USE 6 DO NOT USE 7 DO NOT USE 8 SILE...

Страница 30: ...e Alarms and Restorals 0 No transmissions for this group 1 Access Code Openings and Closings 1 Call 1st number and backup to 2nd number 1 Priority Alarms and Restorals 2 Call 2nd phone number only 1 Maintenance Alarms and Restorals 3 Always call both phone numbers Section 13 Light 1 OFF and 2nd phone number must be programmed 26 Downloading Telephone Number Page 17 This telephone number is used by...

Страница 31: ... Hz AC 60 Hz OFF Zone Light 6 Restore on bell time out Restore as follower If zone light 4 is ON bypass status will always be shown If zone light 4 is OFF bypass status is shown only when the panel is disarmed 32 5th System Option Code Page 18 Default Zone Light ON Zone Light OFF OFF Zone Light 1 AC excluded from trouble AC included OFF Zone Light 2 No bell during auto arm Bell during auto arm ON ...

Страница 32: ...uawk during Entry Delay No Bell Squawk during Entry Delay OFF Zone Light 6 F Key disabled F Key enabled 35 For Future Use Page 18 36 Keypad Lockout Control Page 18 Default 0 0 Number of Invalid Codes before lockout 0 0 Lockout Duration minutes Enter 2 2 digit numbers in the range of 00 to 99 Program the Number of Invalid Codes as 00 to disable the lockout feature 90 Installer s Lockout Enable Page...

Страница 33: ...EPHONE PLUG WHT Battery capacity for emergency standby is at least 4 hours if the total load BELL AUX O P is 800mA or less Recommended battery is Yuasa MNP4 12 Do not connect transformer to a receptacle controlled by a switch Temperature Range 0 C 47 C 32 F 120 F Maximum Humidity 85 R H BATT 5A BELL 5A AUX 1A WARNING For continued protection against the risk of fire replace only with the same type...

Страница 34: ... of attempts will be limited to a replacement of the product as the exclusive remedy for breach of warranty Under no circumstances shall Digital Security Controls Ltd be liable for any special incidental or consequential damages based upon breach of warranty breach of contract negligence strict liability or any other legal theory Such damages include but are not limited to loss of profits loss of ...

Страница 35: ...m may not properly alert occupants of a fire for a number of reasons some of which follow The smoke detectors may have been improperly installed or positioned Smoke may not be able to reach the smoke detectors such as when the fire is in a chimney walls or roofs or on the other side of closed doors Smoke detectors may not detect smoke from fires on another level of the residence or building Every ...

Страница 36: ... 1999 Digital Security Controls Ltd Toronto Canada www dscgrp com Printed in Canada 29004757 R001 ...

Отзывы: