
13
[2] Interior Loop
is normally used with interior motion detectors
and has the standard exit delay time. The loop also has the
standard entry delay time provided that a delay loop has
been tripped first. If the premises are entered without
coming through a “delay” entrance, and a type [2] loop is
tripped, an immediate alarm will be generated.
[3] Interior Home-Away Loop
operates the same as the
type [2] loop with the following exception. If the system is
armed and the delay loop is NOT tripped during the exit
delay time, the type [3] loop will be bypassed. Instead of
the interior portion of an interior Home-Away loop, a
Home-Away loop can have a delay equal to the standard
entry and exit delay when section [32], light 3 is ON. This
will affect all Home-Away zones when they are not
bypassed by [
∗
][1][
∗
][9] arming, or by arming and not
leaving the premises. If Home-Away zones are
automatically bypassed or [
∗
][9] arming bypassed and
the user then enters [
∗
][1], the Home-Aways will then
have a delay.
[4] 24 Hour Bell Loop
is active at all times and will create an
alarm if the panel is armed or disarmed. This loop will
always activate the bell/siren output.
[5] 24 Hour Bell/Buzzer
operates as the type [4] except the
bell/siren output is activated only when the panel is armed
and only the keypad buzzer is activated while the panel
is disarmed.
[6] 24 Hour Buzzer
operates as the type [4] except only the
buzzer will be activated in the armed or disarmed mode.
[7] Auxiliary Delay Loop
operates the same as the type [0]
loop except the entry/exit times can be independently
set in section [18]. This loop type is useful when a loop
with an entry and/or exit time is required that is different
from the standard times as established for type [0]
zones in section [17]. If section [32], light 5 is ON it will
enable the system to be armed even if the auxiliary delay
loop is open (“Ready” light ON). Also, the system can be
armed with the auxiliary delay loop closed and then it
can be opened before the auxiliary exit delay has
expired. In both cases the auxiliary delay loop will not
become active until both the auxiliary exit delay has
expired and the loop is closed.
[8] Fire Loop
Although a common fire signal is reported,
any number of the 6 zones may be programmed as a fire
loop. A fire loop is a supervised (N.O. alarm initiating
contacts), end-of-line resistor circuit designed to accept
latching 4-wire smoke detectors. See the fire circuit
installation drawing.
On alarm, fire loop shorted, the bell / siren will sound
using the temporal fire pattern or will pulse to indicate
that a fire zone has been activated. Transmission by the
digital communicator is delayed 30 seconds. If the
alarm is acknowledged before the 30 second delay has
expired, pressing the [#] key will silence the alarm and
abort the transmission. If the alarm is NOT acknowledged
within the 30 second period, transmission will proceed
and cannot be aborted. If the alarm has been silenced
and all smoke detectors are not restored to normal, the
alarm will re-sound after 90 seconds; 30 seconds after
that, the communicator will transmit. If the alarm re-
sounds, it may again be silenced by pressing the [#] key
and the communicator transmission will be aborted if the
alarm is silence within the 30 second transmission delay
period. Temporal fire pattern is:
0.5 sec. ON, 0.5 sec. OFF,
0.5 sec. ON, 0.5 sec. OFF,
0.5 sec. ON, 1.5 sec. OFF.
To restore the smoke detectors to normal, clear all
products of combustion from the detectors and perform
a reset by pressing the [
∗
] then [7] keys. See section
[24] for programming the PGM terminal for smoke
detector reset. Pressing [
∗
][7] will remove power from
the smoke detectors for 5 seconds; if the detectors are
clear of smoke, they will return to normal. If the detectors
still have smoke in them, the alarm will re-sound and the
sequence described above will repeat.
For an open on any loop programmed for fire, the
“Trouble” light will come ON and the keypad sounder will
beep every 10 seconds. The keypad trouble buzzer will
sound and the “Trouble” light will come ON regardless
of whether the panel is armed or disarmed. The
communicator will transmit the trouble condition if
programmed in section [09]. The audible trouble
indication may be silenced by pressing the [#] key. The
“Trouble” light will only go OFF when all the fire loop
troubles are cleared. To determine the type of trouble,
press [
∗
][2].
Section [11], Digit #2 Summary:
[0] = Standard delay loop
[1] = Instant loop
[2] = Interior Loop
[3] = Interior... home / away loop
[4] = 24 hour... bell loop
[5] = 24 hour... bell / buzzer loop
[6] = 24 hour... buzzer loop
[7] = Auxiliary delay loop
[8] = Fire Loop
[12]
1st System Option Code
The 1st System Option Code is set using the zone lights as
shown in the table below. Once section [12] is entered, the
6 zone lights will indicate the status of each option. Press a
number key corresponding to the zone light number to turn
the option ON and OFF. Pressing [0] will turn all the zone
lights OFF and the options will be set as shown against “Light
Off”.
ZONE
LIGHT
[1]
ON =
Communicator disabled
• OFF =
Communicator Enabled
[2]
ON =
Transmission per 24 hour period
• OFF =
Transmission per armed period
[3]
• ON =
Alarm display while armed
OFF =
No alarm display while armed
[4]
• ON =
DTMF dialling
*
OFF =
Pulse dialling
[5]
ON =
N.C. loops (except fire loops)
• OFF =
End-of-line resistor loops
[6]
• ON =
Keypad [P]anic audible
OFF =
Keypad [P]anic silent
• Factory default settings
*
DTMF dialling will default to pulse dialling after 2
unsuccessful DTMF dialling attempts.