Program Data Review

• Enter the section you wish to program by entering the 2-

digit section number.

• The first 4 zone LEDs will represent the value, in binary

format, of the first digit in that section.

• Each press of the [F] key will advance the display to the

next digit.

• At the end of the section, the keypad will beep several times

and then return to the program mode so that another
section can be selected for review or programming.

NOTE: 

     Only sections [01] through [11], [20] through [24]

and [26] through [28] can be reviewed using the method
described above.  Sections [15], [17], [18], [19] and [25]
cannot be reviewed.

Sections [12], [13], [14], [16], [31], [32], [34]

These sections use the zone lights to indicate which functions
are active and which number key to press to turn them ON and
OFF.  When one of these sections is entered, zone lights 1 to
6 will display which functions are currently ON.  Pressing the
key number corresponding to the zone light number will
alternately turn the function ON and OFF, and the zone light will
correspond to this.  All functions can be turned OFF at once by
pressing [0].  When the correct selections have been made,
press [#] to save the selections in memory and return to the
program mode where another section can be selected.

Binary Data Display

Zone lights 1 through 4 are used to display the value, in
binary format, of the data as shown in the table below.

PROGRAMMING GUIDE

Introduction

The PC1510 is fully programmable from the keypad and uses an
EEPROM memory which can be reprogrammed thousands of
times. The EEPROM memory will not lose the program data even
on total loss of power. The essential information which defines the
operation of the control panel is stored in a section of the
EEPROM memory which is accessible using the Installer’s
Programming code or via downloading.  If the Installer’s code
is forgotten, the EEPROM may be reset to the factory default
code.  See Section [30], Reset to Factory Default.

Programming

With the panel in the disarmed mode, enter [

][8][1500].  The

panel can only be programmed while it is in the disarmed
mode.  The default installer’s code is 1500; the installer’s code
can be changed.  See Section [20], New Installer’s Code.

Once the installer’s command is entered, the “Armed” light
will come ON steadily and the “Memory“,  “Bypass” and
“Trouble” lights will flash.  This indicates that the panel is
ready for programming.  

NOTE:  

If no key entry is made for

2 minutes, the panel will return to the Ready mode and the
complete installer’s command will have to be entered before
programming can be resumed.

With the “Armed” light ON steadily, enter 2 digits for the
section you wish to program.  The sections for the PC1510
panel range from [01] to [36], and each section can be
programmed independently.  Section [00] is reserved for
binary programming which is normally done on instruction
from factory technical personnel.

Once the 2 digits for the section you wish to program are
entered, the “Armed” light will go OFF, the “Ready” light will go
ON steadily, and the keypad sounder will beep 3 times.  The
keypad is now ready to accept data for the selected section.

Most sections contain groups of 2-digit entries and the keypad
buzzer will beep twice after each 2-digit group is entered.

When the section is first entered, the first 4 zone lights will
indicate, in a binary format, the value of the first digit in that
section (see binary display section on this page).  If you wish
to change that digit, simply enter the new digit from the
keypad.  If you wish to keep that digit unchanged, you can
enter the same number or skip the digit by pressing the [F]
key.  Once the first digit has been entered or skipped, the
4 zone lights will display the value of the second digit.  After
each digit is entered or skipped, the zone lights show the
value of the next digit in the binary format.

When the required data for the section being programmed
is completely entered, the keypad sounder will beep several
time and the “Armed” light will come ON to indicate that the
expected data has been entered.

At this point, while still in the program mode, enter the
section number for the next section to be programmed.

It is not necessary to program all 2-digit pairs in any given
section.  A section can be entered and selectively programmed
by going only to the digit(s) you wish to change and then
pressing [#] to return to the programming mode where you can
then enter another section number for programming.  For 2-
digit pairs, both digits must be programmed before pressing
the [#] key.  Only the data entered before pressing the [#] key
will be changed in the EEPROM.

HEX Data Programming

Certain programming entries may require the entry of data in
HEX (hexadecimal, or base 16) format.  HEX numbering uses
the digits 0 through 9 and the letters A through F.

The letters A through F are represented by the number keys
1 through 6.  To enter data in HEX format, first press the [

]

key.  The “Ready” light will flash.  Enter the HEX value, then
press the [

] key again to return to the normal entry mode.

The “Ready” light will stop flashing.

To enter HEX numbers:

A

Enter [

][1][

]

B

Enter [

][2][

]

C

Enter [

][3][

]

D

Enter [

][4][

]

E

Enter [

][5][

]

F

Enter [

][6][

]

Enter [

before 

and 

after 

each digit.  The last digit in each

section does not require the final asterisk ([

]) to be

entered.

Value

Zone 1
Zone 2
Zone 3
Zone 4

Light On
Light Off

*

See Hex Data Entry instructions

Hex Data Entry*

Содержание PC1510

Страница 1: ...N G This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read Software Version 4 1 DLS 1 V6 5 and up ...

Страница 2: ...his unit is 2 AVIS L étiquette de l Industrie Canada identifie le matériel homologué Cette étiquette certifie que le matériel est conforme à certaines normes de protection d exploitation et de sécurité des réseaux de télécommunications Industrie Canada n assure toutefois pas que le matériel fonctionnera à la satisfaction de l utilisateur Avant d installer ce matériel l utilisateur doit s assurer q...

Страница 3: ...ditions 7 Alarm Memory 7 Downloading Callup Command 7 User Programming Commands 7 EEPROM Reset 8 User Function Commands 8 Setting the Clock 6 Master Code 1 8 Set Auto Arm Time 6 Master Code 2 8 Quick Arm ON OFF 6 Master Code 4 8 Auto Arm ON OFF 6 Master Code 5 8 Door Chime ON OFF 6 Master Code 6 8 Bell Test 6 Master Code 8 9 Installer s Test ON OFF 6 Master Code 0 9 Utility Output Command 7 or 7 A...

Страница 4: ... Option Code 14 14 3rd System Option Code 14 15 Communication Variables 14 16 Zone Bypass Mask 14 17 System Times 14 18 Auxiliary Delay Loop Entry Exit Times 15 19 System Clock Times 15 20 New Installer s Code 15 21 New Master Code 15 22 2nd Master Code 15 23 Communication Formats 15 24 Programmable Output Options PGM Terminal 16 25 Communicator Call Directions 17 26 Downloading Telephone Number 1...

Страница 5: ...delay Six access codes Master key code All zones programmable as fire zones Temporal fire bell pattern Programmable test transmission Zone bypass from the keypad Six zones Bell Siren zone Programmable output Four programmable options Three dedicated keys Fire Emergency Panic Backlit aesthetically pleasing keypad PC1510 Control Panel Six fully programmable zones EOL resistor 30 EOL supervised optio...

Страница 6: ...all wiring to the control panel before applying AC power or connecting the battery Mounting the Keypad Keypads should be located close to the designated Entry Exit door s and mounted at a height convenient for all users NOTE Complete all wiring to the control panel before applying AC power or connecting the battery Auxiliary Power Connection The auxiliary power supply can be used to power keypads ...

Страница 7: ...hart Z1 COM Z2 NC NO NC NC 5600Ω 0 5W END OF LINE RESISTOR 5600Ω 0 5W END OF LINE RESISTOR EOL RESISTOR LOOPS USING NO NC DEVICES EOL RESISTOR LOOPS USING NC DEVICES ONLY Zone Wiring Chart Figures based on maximum loop resistance of 100 ohms Wire Gauge Max Run Length to AWG End of Lineresistor 24 1900 579m 22 3000 914m 20 4900 1493m 19 6200 1889m 18 7800 2377m Thewiringtablegivesthewirerunlengthfr...

Страница 8: ...from the alarm panel communicator RED BATTERY CHARGE CURRENT IS 360 mA MAX 12 VOLT 4 Ah GEL CELL BATTERY CAPACITY FOR EMERGENCY STANDBY IS AT LEAST 4 HOURS IF THE TOTAL LOAD BELL AUX OUTPUTS IS 800 mA OR LESS BLK Battery Connection If the battery is reverse connected the 5 A fuse will blow The battery charging voltage is factory set and normally needs no adjustment Ifthebatterychargingvoltageisout...

Страница 9: ...iving unit living unit Smoke Detector mounting Dead Air Space The smoke Smoke Detector mounting Dead Air Space The smoke Smoke Detector mounting Dead Air Space The smoke Smoke Detector mounting Dead Air Space The smoke Smoke Detector mounting Dead Air Space The smoke from a fire generally rises to the ceiling spreads out from a fire generally rises to the ceiling spreads out from a fire generally ...

Страница 10: ...ed when the panel is disarmed KEYPAD FUNCTIONS Introduction The PC1500RK remote keypad provides complete information and control of the PC1510 control panel The panel can be fully programmed from the keypad The 6 zone lights provide alarm and status indication for the alarm circuits Each zone can be programmed to be a burglary zone or a fire zone The five function lights guide the user in operatin...

Страница 11: ...it from the trouble view mode 5 Fire Alarm Circuit Trouble An open circuit on the zone programmed as a fire loop will initiate a trouble See Zone Definitions section 11 for fire loop zone assignment 6 Loss of Time on System Clock When the PC1510 is powered up or reset the internal time of day clock needs to be reset to the correct time The trouble is cleared after entering the trouble view mode th...

Страница 12: ...fter use This function will turn off automatically on arming Items 4 5 6 and 0 turn ON and OFF various features When the item key is pressed and the feature is being turned ON the keypad sounder will beep 3 times If the feature is being turned OFF the sounder will give one long beep Pressing item 8 gives a 2 second Bell Siren and Keypad Light and Buzzer test Setting the Clock 6 Master Code 1 The S...

Страница 13: ...passed Note that the 1 command will not remove bypasses from zones that have been manually bypassed Quick Exit Command 0 when Armed Entering 0 when the system is armed will allow the user to exit the premises through any delay zone without altering the status of the system if the Quick Exit feature is enabled The Quick Exit feature can be enabled by turning on option 4 in programmingsection 32 For...

Страница 14: ...ter 2 digits for the section you wish to program The sections for the PC1510 panel range from 01 to 36 and each section can be programmed independently Section 00 is reserved for binary programming which is normally done on instruction from factory technical personnel Once the 2 digits for the section you wish to program are entered the Armed light will go OFF the Ready light will go ON steadily a...

Страница 15: ...factory technicalpersonnelforspecializedprogrammingnotcovered by the standard programming instructions 01 1st Phone Number This is the first telephone number the Communicator will dial See Section 25 Communicator Call Direction After entering section 01 for programming enter the telephone number the same way you would dial it on a touch tone phone Press after the last digit to complete the telepho...

Страница 16: ...e F A and P keys will only take place if the appropriate sections in 09 are programmed with a reporting code 10 Maintenance Alarms and Restorals These reporting codes are used by the communicator to transmit the following list of alarms and restorals See section 05 as a guide to programming Low battery alarm AC failure alarm Fuse failure alarm Low battery restore AC failure restore Fuse failure re...

Страница 17: ...municator is delayed 30 seconds If the alarm is acknowledged before the 30 second delay has expired pressing the key will silence the alarm and abort the transmission If the alarm is NOT acknowledged within the 30 second period transmission will proceed and cannot be aborted If the alarm has been silenced and all smoke detectors are not restored to normal the alarm will re sound after 90 seconds 3...

Страница 18: ...ng data The first 2 digit number defines the number of attempts alarm and restoral pairs perzonethatthecommunicatorwillmakebeforeitshuts downforthatzone swingershutdown Thenumberofattempts is for the period as defined in the 1st System Option Code Section zone light 2 The number of attempts may be programmedfrom 00 to 99 where 00 meansthecommunicator will never shut down The fire zone cannot be sh...

Страница 19: ... 0 through 9 as numbers in the code do not press the or keys If an error is made entering the code complete entry of the 4 digits then enter the section number again to enter the correct code Do not press or while entering the code 22 2nd Master Code Once the section number has been entered 20 21 or 22 enter a new 4 digit code Only use digits 0 through 9 as code numbers Do not press the or keys If...

Страница 20: ... option is selected the PGM output is normally low That is it is just the reverse of all other options which are normally high and go low when activated This option is normally used as the negative return for power to 4 wire smoke detectors positive comes from the AUX terminal To activate this output to reset smoke detectors enter the 7 command The PGM terminal will go high open circuit and thus r...

Страница 21: ...ng machine connected to the same phone line 30 Reset to Factory Default Software Entering 30 will perform a software reset to the factory default values Once this command is entered the keypad buzzer will beep several times The Trouble LED will be ON during the reset sequence Hardware Iftheinstaller scodeisforgottenandasoftwareresetcannotbe performed thepanelcanberesettothefactorydefaultvalues wit...

Страница 22: ... the keypad will sound a constant tone during the Entry Delay During the last 10 seconds of the Entry Delay the keypad will sound a pulsing tone to warn that the delay is about to expire When the urgency option is selected for the audibile Exit Delay the keypad will sound a pulsing tone during the Exit Delay During the last 10 seconds of the Exit Delay the keypad will sound a faster pulsing tone t...

Страница 23: ..._________________________________ ZONES Zone Type Protected Area 1 _____________________________ __________________________________________________________________ 2 _____________________________ __________________________________________________________________ 3 _____________________________ __________________________________________________________________ 4 _____________________________ ______...

Страница 24: ...the digit 0 in the account code For a 3 digit code enter 0 for the 4th digit 03 2nd Phone Number Page 11 04 2nd Account Code Page 11 05 Zone Alarm Reporting Codes Page 11 For single digit reporting codes enter 0 as the second digit Enter 1 HEX A to transmit a zero Zone 1 Alarm Zone 2 Alarm Zone 3 Alarm Zone 4 Alarm Zone 5 Alarm Zone 6 Alarm 06 Zone Restoral Reporting Codes Page 11 For single digit...

Страница 25: ...g if an alarm occured during the previous armed period Access Code 1 Access Code 2 Access Code 3 Access Code 4 Access Code 5 Access Code 6 After Alarm Code 09 Priority Alarms and Restorals Page 12 Actuation of the F A or P keys will immediately transmit both an alarm and restoral code There is no delay on the restoral code transmission Fire Loop Trouble Keypad P anic Alarm Keypad F ire Alarm Keypa...

Страница 26: ... 0 2 Zone 4 0 2 Zone 5 0 8 Zone 6 First Digit Second Digit 0 Slow Audible 0 Standard Delay 1 Slow Silent 1 Instant 2 Fast Audible 2 Interior 3 Fast Silent 3 Interior Home Away 4 24 Hour Bell 5 24 Hour Bell Buzzer 6 24 Hour Buzzer 7 Aux Delay Uses Auxiliary Entry Exit Times 8 Fire Any one zone may be set as a FIRE zone 12 1st System Option Code Page 13 Default Zone Light ON Zone Light OFF OFF Zone ...

Страница 27: ...e Light OFF OFF Zone Light 1 User code required for bypass Code not required OFF Zone Light 2 4 Enabled 4 Disabled OFF Zone Light 3 Periodic downloading Periodic test transmit OFF Zone Light 4 4 access code required 4 no code required ON Zone Light 5 P anic audible buzzer P anic silent buzzer OFF Zone Light 6 Partial closing identified Not identified 15 Communication Variables Page 14 Default 0 3 ...

Страница 28: ...smission delay minutes 0 5 0 Slow loop response time x 10 ms 0 3 0 Test transmission cycle or auto download cycle time days Valid entries are 001 to 255 Do not enter 000 Do not enter 000 Do not enter 000 Do not enter 000 Do not enter 000 18 Auxiliary Delay Loop Entry Exit Times Page 15 Default 0 4 5 Entry Time seconds 1 2 0 Exit Time seconds Valid entries are 001 to 255 19 System Clock Times Page ...

Страница 29: ...hake 3 1 4 1 and 4 2 non extended formats 1 SESCOA FRANKLIN DCI VERTEX 20 BPS 2300 Hz handshake 3 1 4 1 and 4 2 non extended formats 2 SILENT KNIGHT FAST 20 BPS 1400 Hz handshake 3 1 4 1 and 4 2 non extended formats 3 RADIONICS 2300 1400 Hz handshake 3 1 4 2 non extended formats 4 RADIONICS 2300 1400 Hz handshake 3 1 4 2 non extended with parity format 5 DO NOT USE 6 DO NOT USE 7 DO NOT USE 8 SILE...

Страница 30: ...e Alarms and Restorals 0 No transmissions for this group 1 Access Code Openings and Closings 1 Call 1st number and backup to 2nd number 1 Priority Alarms and Restorals 2 Call 2nd phone number only 1 Maintenance Alarms and Restorals 3 Always call both phone numbers Section 13 Light 1 OFF and 2nd phone number must be programmed 26 Downloading Telephone Number Page 17 This telephone number is used by...

Страница 31: ... Hz AC 60 Hz OFF Zone Light 6 Restore on bell time out Restore as follower If zone light 4 is ON bypass status will always be shown If zone light 4 is OFF bypass status is shown only when the panel is disarmed 32 5th System Option Code Page 18 Default Zone Light ON Zone Light OFF OFF Zone Light 1 AC excluded from trouble AC included OFF Zone Light 2 No bell during auto arm Bell during auto arm ON ...

Страница 32: ...uawk during Entry Delay No Bell Squawk during Entry Delay OFF Zone Light 6 F Key disabled F Key enabled 35 For Future Use Page 18 36 Keypad Lockout Control Page 18 Default 0 0 Number of Invalid Codes before lockout 0 0 Lockout Duration minutes Enter 2 2 digit numbers in the range of 00 to 99 Program the Number of Invalid Codes as 00 to disable the lockout feature 90 Installer s Lockout Enable Page...

Страница 33: ...EPHONE PLUG WHT Battery capacity for emergency standby is at least 4 hours if the total load BELL AUX O P is 800mA or less Recommended battery is Yuasa MNP4 12 Do not connect transformer to a receptacle controlled by a switch Temperature Range 0 C 47 C 32 F 120 F Maximum Humidity 85 R H BATT 5A BELL 5A AUX 1A WARNING For continued protection against the risk of fire replace only with the same type...

Страница 34: ... of attempts will be limited to a replacement of the product as the exclusive remedy for breach of warranty Under no circumstances shall Digital Security Controls Ltd be liable for any special incidental or consequential damages based upon breach of warranty breach of contract negligence strict liability or any other legal theory Such damages include but are not limited to loss of profits loss of ...

Страница 35: ...m may not properly alert occupants of a fire for a number of reasons some of which follow The smoke detectors may have been improperly installed or positioned Smoke may not be able to reach the smoke detectors such as when the fire is in a chimney walls or roofs or on the other side of closed doors Smoke detectors may not detect smoke from fires on another level of the residence or building Every ...

Страница 36: ... 1999 Digital Security Controls Ltd Toronto Canada www dscgrp com Printed in Canada 29004757 R001 ...

Отзывы: