43
* A/R = alarms/restorals; O/C = openings/closings; O = other
** PPP = partition number; UUU = user number (user 1000=999); ZZZ = zone number
Ref. #
Reporting Code
Code Sent When...
Dialer
Direction*
Contact
ID
SIA Auto Rep
Codes**
[00040311]
Closing 129-1000
user code # 129-1000 used to arm partition
O/C
(4) A2
CL-UUU
[00040311]
Partial Closing
one or more zones intentionally bypassed
when partition armed
O/C
(4) 56
CW-000
[00040311]
Automatic (Scheduled) Clos-
ing
auto arming according to schedule
O/C
(4) A3
CA-000
[00040311]
Auto Arm Cancellation
auto arm cancelled
O/C
(4) A5
CE-000
[00040312]
Partition Closing
partition armed (partition number indicated)
O/C
(4) AA
CG-PPP
[00040313]
Openings
partition disarmed (user 001-128 indicated)
O/C
(4) A2
OP-UUU
[00040314]
Opening 129-1000
user code # 129-1000 used to disarm partition
O/C
(4) A2
OP-UUU
[00040314]
Special Opening
disarm with WLS909, Second Master code,
keyswitch, downloading or guard code
O/C
(4) A2
OP-000
[00040314]
Automatic (Scheduled)
Opening
auto disarming according to schedule
O/C
(4) A2
OA-000
[00040315]
Partition Opening
partition disarmed (partition number indi-
cated)
O/C
(4) AA
OG-PPP
[00040316]
Battery Trouble/Rest.
PC4020 battery is low
O
(3) A2
YT-000/YR-000
[00040316]
AC Line Trouble/Rest.
AC power to control panel is disconnected or
interrupted
O
(3) AA
AT-999/AR-999
[00040316]
Panel Bell Trouble/Rest.
open circuit detected across bell terminals
O
(3) 21
YA-999/YH-999
[00040316]
Panel Auxiliary Trouble/Rest.
aux voltage supply trouble
O
(3) AA
YP-999/YQ-999
[00040316]
Combus Trouble/Rest.
control panel loses communications with con-
nected module(s) or has low power
O
(3) 33
UT-999/UJ-999
[00040316]
TLM Failure/Rest.
telephone line 1 monitoring trouble (sent via
LINKS. Do not program if LINKS not used)
O
(3) 51
LT-001/LR-001
[00040316]
TLM Line2 Failure/Rest.
telephone line 2 monitoring trouble (sent via
LINKS. Do not program if LINKS not used)
O
(3) 52
LT-002/LR-002
[00040316]
FTC Restoral
control panel has restored communications to
central station (after TLM Fail)
O
(3) 54
YK-000
[00040316]
Buffer Near Full
printer not used or off-line for 450 events
O
None
JL-000
[00040316]
User System Test
[*][6] bell/communications test
O
(6) A1
RX-000
[00040316]
Periodic Test
periodic test transmission
O
(6) A2
RP-000
[00040316]
LINKS Test
LINKS test transmission
O
(6) A3
TX-000
[00040316]
Ground Fault/Rest.
EGND connection detects a ground fault
O
(3) 1A
US-000/UR-000
[00040316]
DLS Lead In
DLS Call Back feature only: downloading ses-
sion start
O
(4) 11
RB-000
[00040316]
DLS Lead Out
DLS Call Back feature only:
downloading session complete
O
(4) 12
RS-000
[00040316]
Installer Lead In
Installer code has been entered
O
(4) 58
LB-000
[00040316]
Installer Lead Out
Installer's programming complete
O
(4) 58
LS-000
[00040316]
Closing Delinquency
programmed number of days for delinquency
has expired without partition being armed
O
(4) 54
CD-000
[00040316]
Walk Test Enabled
walk test mode entered
O
(6) A7
TS-000
[00040316]
Walk Test Disabled
walk test complete
O
(6) A7
TE-000
[00040316]
General System Trouble/Rest.
indicates one or more of following:
PC4204/PC4820/PC4702 AC, battery and Aux
Supply troubles/rest., PC4400 troubles, auto-
mation fault, PC4164-RS RF jam
O
(3) 3A
YX-000
[00040316]
General Device Low Battery/
Rest.
Wireless zones/pendants (WLS908) 009-128;
handheld keypads (WLS910)
wireless keys (WLS909)
O
(3) 84
XT/XR-ZZZ
XT/XR-901-904
XT/XR-921-936
[00040316]
Gen Module Comm Fault/
Rest.
control panel loses communications with con-
nected module(s)
O
(3) 33
ET-000/ER-000