I NS TA LL AT IO N  MA NU AL

5.2 Connection

5.2.1 Gas connection

Place a gas tap in the gas pipe in accordance with the applicable regulations.
 

!Caution

Make sure there is no dirt in the gas pipes and connections.

No soldering may take place at the flexible gas hose(s), as this could cause leaks.

 
The following requirements apply to the gas connection:

use a gas pipe with the correct dimensions, so that no pressure loss can occur;

the gas tap must be approved (in the EU this will be the CE mark);

you should always be able to reach the gas tap.

5.2.2 Electric connection

In case of a 230 Volt electrical connection, provide proper grounding, if applicable.
Place this electrical connection away from the appliance, as low as possible in the chmney breast.
This has to do with the temperature development in the chimney breast.
If possible, place the receiver after any building work has been completed.
If this is not possible:

!Caution

Protect the receiver against dust and moisture created during the building process!

5.3 Placing the appliance

!Caution

Unless stated otherwise: always place the appliance with a minimum distance of 500 mm from combustible 
objects or materials;

Place the discharge pipes in such a way that situations with risk of fire can never occur;

Always place the appliance in front of a wall of non combustible and heat-resistant material;

Always maintain a minimum distance between appliance and back wall, if indicated in the dimensional 
drawing (Appendix 3, fig. 2);

Take sufficient measures to prevent high temperatures of a possible wall behind the chimney breast, 
including the materials and/or objects that are behind the wall;

Do not cover the appliance and/or do not wrap it in an insulation blanket or any other material;

Make sure that the appliance to be installed has a stable position. Attach the appliance, if applicable, to the 
wall using the wall brackets and/or fasten the extending legs with self-tapping screws.

!Caution

When installing an appliance that has to be built in, take the following into account:
The minimum construction dimensions according to Appendix 3, fig. 1 and 2.
 

Ø

Provide a gas connection at the location. For details (see section 5.2).

Ø

Make a passage for the flue gas discharge system or the concentric system with the following diameters; for 
details, see section 5.7 or 5.8:

the pipe di10 mm for a passage through non combustible material;

the pipe di100 mm for a passage through combustible material.

!Caution

Starting at section 5.9, you will find additional instructions that are specifically needed for the installation of your 
appliance.  

5.4 Placing a built in appliance

 (if applicable)

Not all DRU built in appliances are supplied with a control hatch. If not included in the delivery, this control hatch 
is available separately. In case of appliances with closed combustion (type C11/C31) we always recommend using 
the Dru control hatch. In case of appliances with open combustion (type B

11 AS/BS

), a control hatch is not required. 

In this section we assume an application with control hatch.

!Caution

If you do not use a recommended Dru control hatch, please strictly observe the safeguards and necessary 
instructions stated in chapters 5.4 to 5.6.
 
If you are not using the control hatch, please take the following into account as well:

the accessibility of components that are normally placed in the control hatch;

the maximum temperature of these components (maximum 55 °C).

 
The gas control is mounted under the appliance, at the burner mounting plate. It must be taken out and placed in 
the control hatch at a later time. For placing the gas control in the control hatch, see section 5.6.

6

Содержание Global Fires Global 55 CF RCE

Страница 1: ...E n g l i s h Store this document in a safe place Global 55 CF RCE Global 55XT CF RCE Installation manual DRU 790113 EN US 0418 2 G20 G25 G25 3 Natural gas G31 Propane EN 959 116 02 EN...

Страница 2: ...f the concentric system 5 8 3 Placing the concentric system 5 8 4 Connection existing chimney 5 9 Additional instructions 5 10 Placing the appliance 5 10 1 Connecting the appliance 5 10 2 Connecting t...

Страница 3: ...d at the back of this booklet in the appendix Please read and use this installation manual carefully and completely prior to installing this appliance If you use the DRU Powervent system or the DRU Sm...

Страница 4: ...re there is sufficient ventilation of the room where the appliance is installed according to legislation If you are installing an appliance with a closed combustion only use the concentric systems sup...

Страница 5: ...iance Check the appliance and accessories for damages during transport If necessary contact your supplier Never install an appliance that is damaged Remove any screws that are used to fix the applianc...

Страница 6: ...nket or any other material Make sure that the appliance to be installed has a stable position Attach the appliance if applicable to the wall using the wall brackets and or fasten the extending legs wi...

Страница 7: ...top of the chimney breast the material inside the chimney breast and the back wall of the chimney breast Make sure that the appliance is not carrying the weight of the chimney breast when using stone...

Страница 8: ...arter turn using a suitable spanner The pilot burner pipe must be protected against possible corrosive influences as a result of for example humidity cement that has fallen down dirt that has fallen d...

Страница 9: ...with the CE mark Caution Some heat resistant insulation materials contain volatile components that will spread an unpleasant smell during a longer period these are not suitable Place the flue gas disc...

Страница 10: ...cove it should be made with non combustible material all around it Use heat resistant insulation material when passing through combustible material The rosette of the wall terminal is too small to sea...

Страница 11: ...surrounding space is used to supply combustion air The following requirements apply when connecting to an existing chimney only allowed when used in combination with the special DRU chimney kit The in...

Страница 12: ...ion 5 12 1 Connect the appliance see section 5 10 1 Caution Do not ignite the appliance until it is fully installed Place the wood set see section 5 13 Place the glass pane see section 5 12 2 5 10 1 C...

Страница 13: ...res the restrictor in the flue spigot must be adapted see Appendix 2 tables 5 and 6 Remove the restrictor from the flue spigot see Appendix 3 fig 16 R Break the small ring A from the restrictor by mov...

Страница 14: ...uld remain free from glow material Tip Fasten the glow material under the chips and or wood set 5 14 Placing replacing the receiver s batteries The batteries should be placed in the special battery ho...

Страница 15: ...in order to avoid damaging the receiver Avoid formation of dust on or in the receiver cover it when performing work Place the receiver in its intended holder under the appliance or in the control hat...

Страница 16: ...ow position ignition and switching off Tip If the external control system has an intelligent clock function and or thermostat function the remote control supplied with the appliance should have the ma...

Страница 17: ...ches off after 22 seconds This happens because the appliance is equipped with a second thermocouple and the glass window has not been placed In this case you may presume that the main burner will cont...

Страница 18: ...he system as a result of pitting corrosion If required clean the following components the pilot burner malfunction search diagram Appendix 1 the space surrounding the pilot burner the glass pane s Cau...

Страница 19: ...door openers Instruct the user about the appliance and the remote control When the appliance is started for the first time point out that In order to avoid cracks in a chimney breast made of stone lik...

Страница 20: ...bend tip 1 mm higher Spark too weak thin and reddish Act as if no spark in box 2 05 and perform actions described for ignition cable and ignition electrode Pilot flame too weak dirty Remove injector r...

Страница 21: ...venly distributed across burner s chips on burner lack of combustion air See 2 15 cross lighting in low setting possible when thermostat function is used 2 15 Check Gas supply Supply pressure does not...

Страница 22: ...and brief noise of servomotor to confirm that communication code was set succesfully Remote control Battery 9V empty see indication on display Several After switching off going out the remote set is l...

Страница 23: ...ons conventional class 1 chimney Sealing tape Cellular rubber Debris shield Spare self tapping screws for mounting glass panes Socket spanner 8 mm Remote control with receiver 9V block battery Penlite...

Страница 24: ...x elmin elSB Ppilot EEI G25 G25 3 No 3 7 124 5 3 7 1 5 5 4 4 9 575 300 14 2 3 8 7x 0 78 1 40 2 77 9 61 7 78 C G25 G25 3 No 4 2 121 1 4 2 1 7 6 4 5 8 684 302 19 0 4 0 7x 0 78 1 40 2 73 8 67 3 74 D G20...

Страница 25: ...using G31 Total number of meters vertical pipe length N A Total number of meters horizontal pipe length excluding wall terminal N A Table 4 Conditions for setting the appliance See Figure N A Air inle...

Страница 26: ...length Total no of meters vertical and or sloping pipe length no bends 2 bends 3 bends 4 bends 5 bends Situation is not permissible min length 3 m angles in vertical direction of flue gas discharge s...

Страница 27: ...i s h INSTALLATION MANUAL Appendix 3 Figures 27 346 487 539 23 5 25 100 550 538 638 115 360 150 519 320 116 38C 2041 0 521 487 714 23 5 25 694 115 535 150 320 116 538 638 100 550 Global 55 CF Global 5...

Страница 28: ...42 min 640 min 340 min 115 max 100 min 500 V V Tot min 200 cm2 38c 2042 0 539 min 115 min 500 min 640 min 340 max 100 542 V Tot min 200 cm2 V 2 2 B 2 2 4x B Global 55 CF Global 55XT CF 4x 38c 2044 0 3...

Страница 29: ...E n g l i s h INSTALLATION MANUAL 29 3 8 C 2 1 0 5 0 60 45 100 65 25 40 38c 2048 0 38C 2102 0 38C 2103 0 38C 2104 0 13 9 10 11 12...

Страница 30: ...E n g l i s h INSTALLATION MANUAL 30 38C 2108 0 A X 6 m B X 6 m X R 38C 2106 0 38C 2107 0 16 14 15...

Страница 31: ...E n g l i s h INSTALLATION MANUAL 31 38P 0490 0 A B C 38P 0488 0 38P 0489 0 38p 0023 38P 0028 1 21 17 18 19 20...

Страница 32: ...E n g l i s h INSTALLATION MANUAL 32 38P 0491 0 A 38P 0492 0 B 38P 0493 0 C 22 23 24...

Страница 33: ...E n g l i s h INSTALLATION MANUAL 33 38p 0179 38p 0181 5mV 38p 0182 38c 2109 0 20 17 38c 2110 0 43 38 40 43b 41 42...

Страница 34: ...E n g l i s h INSTALLATION MANUAL 34 38C 1940 300 150 450 150 150 A B 38c 2111 0 45 44...

Страница 35: ...E n g l i s h INSTALLATION MANUAL 35...

Страница 36: ...E n g l i s h DRU Verwarming B V The Netherlands Postbus 1021 NL 6920 BA Duiven Ratio 8 NL 6921 RW Duiven EN...

Отзывы: