background image

English

INS T ALLAT I ON   M A N U A L 

2.12 Does appliance switch off 
exactly 22 sec after 
servomotor starts running?

2.19 

Replace gas control

(thermo-electric valve does not 
shut down quick enough because 
of some permanent magnetism).

2.14 Does main burner go out 
after 'some time'?

2.18 Can fire be switched off?

2.20 Perfect!
You have a well functioning 
fire

2.16 Is flame picture OK?

2.13 

Check cross lighting main 

burner and 2nd thermocouple 
system.
 
Measure voltage of 2nd 
thermocouple

-  Check voltage in mV, 22 sec after 

servomotor starts to run, c.q.  just 
before fire goes out. Glass window 
to be mounted!

-  Measure between black wire + earth 

point on gas control.

-  

Requirement:

 voltage >5 mV after 

rectification actions.

Voltage 0 mV

-  2nd couple defective.
-  Cross ligting main burner very slow. 

Take actions "Cross lighting too 
slow" (see  below), before taking any 
further action!!

Voltage <1,8 mV

-  Cross ligting main burner too slow. 

Take actions "Cross lighting too 
slow" (see below), before taking any 
further action!

-  2nd couple barred. Check:

- 2nd couple free of vermiculite, 
chips or pebbles;
- position of logs or pebbles;
- burner holes under 2nd couple 
open.

-  2nd couple defective (cross lighting 

OK, but voltage creeps up too slow).

-  Flames instable, see 2.15. Rectify, 

before any other action is taken!!

-  Burner pressure (too high or too 

low).

-  2nd couple not positioned correctly 

in flame.
Bend into correct position (see fig. 
43).

-  2nd thermocouple positioned 

correctly (see manual). Bend into 
flame (only if cross lighting and 
flame picture are OK!! See 2.17).

Voltage > 1,8 mV

-  Receiver defective. Replace.

Cross lighting of main burner too 
slow

Measure the time in sec from start 
running of servomotor till the flame 
reaches the 2nd couple.

Requirement:

 the flame must be in 

position at the 2nd couple <10 sec.
If not, check:
-  2nd couple free from vermiculite, 

chips or pebbles;

-  position of logs or pebbles;
-  burner holes (locally) blocked. 

Remove vermiculite dust.

-  vermiculite missing or not evenly 

distributed across burner(s);

-  chips on burner;
-  lack of combustion air. See 2.15.
-  cross lighting in low setting 

(possible when thermostat function 
is used).

2.15 Check

Gas supply

-  Supply pressure does not drop 

away as main burner (or other 
appliance) lights, causing pilot 
flame to shorten.

-  Burner pressure (too high or too 

low).

 

Flames instable (suffocating, lack 
of air).

Dancing flames on burner.
Lack of combustion air. Check:
-  flue system permissible;
-  proper flue terminal used, make 

should be 'DRU';

-  terminal correctly sited on roof or 

wall relative to obstructions;

-  integrity of flueing system (no 

interruptions, not barred, 
cobwebs);

-  air inlet guides;
-  flue restrictor/damper;
-  throttle rings.

See manual for specific 
requirements.

 

PowerVent®

Possibly not enough draught. Check 
if pressure difference set too high. 
Consult PowerVent® installation 
manual.
 

Pilot burner

-  Pilot burner dirty. Weak pilot 

flame being drawn away by 
flames main burner.
Clean with compressed air.
See 2.04.

2.17 Check

Flames: too low

-  Supply pressure does not drop 

away as main burner or other 
appliances in the building light, 
causing flames to shorten.

-  Burner pressure (too low).
-  False air: Check soundness glass 

window gasket/ soundness of the 
connection of the glass panes of 
two/three sided appliances (no 
slots allowed).

 

Flames: too high

-  Line pressure.
-  Burner pressure.
 

Flames: no even distribution or 
out on part of the burner(s) 

-  Position of logs or pebbles.
-  Burner holes (locally) blocked.

Remove vermiculite dust.

-  Vermiculite not distributed evenly 

across burner(s).

-  Adjustment of throttle ring(s).
 

Flames: too blue/too yellow or 
sooting

-  Air inlet guides.
-  Flue restrictor/damper.
-  Adjustment of throttle ring(s).
 

Flames: suffocating: lack of air

You see dancing flames on burner, 
seeking for air. See 2.15.
 

Flame picture 'restless'

Indication of too much draught. 
Check:
-  adjustment of appliance damper 

and air inlet guides);

-  vertical flue length allowed (<12 

m);

-  window glass not mounted gas 

tight.

 

PowerVent®? Check:

Possibly too much draught. Check:
-  Pressure difference set too high.
-  Silicon pressure measurement 

hoses leaking.

Consult PowerVent® installation 
manual for more info. 

no

no

yes

yes

no

yes

yes

no

21

Содержание Global Fires Global 55 CF RCE

Страница 1: ...E n g l i s h Store this document in a safe place Global 55 CF RCE Global 55XT CF RCE Installation manual DRU 790113 EN US 0418 2 G20 G25 G25 3 Natural gas G31 Propane EN 959 116 02 EN...

Страница 2: ...f the concentric system 5 8 3 Placing the concentric system 5 8 4 Connection existing chimney 5 9 Additional instructions 5 10 Placing the appliance 5 10 1 Connecting the appliance 5 10 2 Connecting t...

Страница 3: ...d at the back of this booklet in the appendix Please read and use this installation manual carefully and completely prior to installing this appliance If you use the DRU Powervent system or the DRU Sm...

Страница 4: ...re there is sufficient ventilation of the room where the appliance is installed according to legislation If you are installing an appliance with a closed combustion only use the concentric systems sup...

Страница 5: ...iance Check the appliance and accessories for damages during transport If necessary contact your supplier Never install an appliance that is damaged Remove any screws that are used to fix the applianc...

Страница 6: ...nket or any other material Make sure that the appliance to be installed has a stable position Attach the appliance if applicable to the wall using the wall brackets and or fasten the extending legs wi...

Страница 7: ...top of the chimney breast the material inside the chimney breast and the back wall of the chimney breast Make sure that the appliance is not carrying the weight of the chimney breast when using stone...

Страница 8: ...arter turn using a suitable spanner The pilot burner pipe must be protected against possible corrosive influences as a result of for example humidity cement that has fallen down dirt that has fallen d...

Страница 9: ...with the CE mark Caution Some heat resistant insulation materials contain volatile components that will spread an unpleasant smell during a longer period these are not suitable Place the flue gas disc...

Страница 10: ...cove it should be made with non combustible material all around it Use heat resistant insulation material when passing through combustible material The rosette of the wall terminal is too small to sea...

Страница 11: ...surrounding space is used to supply combustion air The following requirements apply when connecting to an existing chimney only allowed when used in combination with the special DRU chimney kit The in...

Страница 12: ...ion 5 12 1 Connect the appliance see section 5 10 1 Caution Do not ignite the appliance until it is fully installed Place the wood set see section 5 13 Place the glass pane see section 5 12 2 5 10 1 C...

Страница 13: ...res the restrictor in the flue spigot must be adapted see Appendix 2 tables 5 and 6 Remove the restrictor from the flue spigot see Appendix 3 fig 16 R Break the small ring A from the restrictor by mov...

Страница 14: ...uld remain free from glow material Tip Fasten the glow material under the chips and or wood set 5 14 Placing replacing the receiver s batteries The batteries should be placed in the special battery ho...

Страница 15: ...in order to avoid damaging the receiver Avoid formation of dust on or in the receiver cover it when performing work Place the receiver in its intended holder under the appliance or in the control hat...

Страница 16: ...ow position ignition and switching off Tip If the external control system has an intelligent clock function and or thermostat function the remote control supplied with the appliance should have the ma...

Страница 17: ...ches off after 22 seconds This happens because the appliance is equipped with a second thermocouple and the glass window has not been placed In this case you may presume that the main burner will cont...

Страница 18: ...he system as a result of pitting corrosion If required clean the following components the pilot burner malfunction search diagram Appendix 1 the space surrounding the pilot burner the glass pane s Cau...

Страница 19: ...door openers Instruct the user about the appliance and the remote control When the appliance is started for the first time point out that In order to avoid cracks in a chimney breast made of stone lik...

Страница 20: ...bend tip 1 mm higher Spark too weak thin and reddish Act as if no spark in box 2 05 and perform actions described for ignition cable and ignition electrode Pilot flame too weak dirty Remove injector r...

Страница 21: ...venly distributed across burner s chips on burner lack of combustion air See 2 15 cross lighting in low setting possible when thermostat function is used 2 15 Check Gas supply Supply pressure does not...

Страница 22: ...and brief noise of servomotor to confirm that communication code was set succesfully Remote control Battery 9V empty see indication on display Several After switching off going out the remote set is l...

Страница 23: ...ons conventional class 1 chimney Sealing tape Cellular rubber Debris shield Spare self tapping screws for mounting glass panes Socket spanner 8 mm Remote control with receiver 9V block battery Penlite...

Страница 24: ...x elmin elSB Ppilot EEI G25 G25 3 No 3 7 124 5 3 7 1 5 5 4 4 9 575 300 14 2 3 8 7x 0 78 1 40 2 77 9 61 7 78 C G25 G25 3 No 4 2 121 1 4 2 1 7 6 4 5 8 684 302 19 0 4 0 7x 0 78 1 40 2 73 8 67 3 74 D G20...

Страница 25: ...using G31 Total number of meters vertical pipe length N A Total number of meters horizontal pipe length excluding wall terminal N A Table 4 Conditions for setting the appliance See Figure N A Air inle...

Страница 26: ...length Total no of meters vertical and or sloping pipe length no bends 2 bends 3 bends 4 bends 5 bends Situation is not permissible min length 3 m angles in vertical direction of flue gas discharge s...

Страница 27: ...i s h INSTALLATION MANUAL Appendix 3 Figures 27 346 487 539 23 5 25 100 550 538 638 115 360 150 519 320 116 38C 2041 0 521 487 714 23 5 25 694 115 535 150 320 116 538 638 100 550 Global 55 CF Global 5...

Страница 28: ...42 min 640 min 340 min 115 max 100 min 500 V V Tot min 200 cm2 38c 2042 0 539 min 115 min 500 min 640 min 340 max 100 542 V Tot min 200 cm2 V 2 2 B 2 2 4x B Global 55 CF Global 55XT CF 4x 38c 2044 0 3...

Страница 29: ...E n g l i s h INSTALLATION MANUAL 29 3 8 C 2 1 0 5 0 60 45 100 65 25 40 38c 2048 0 38C 2102 0 38C 2103 0 38C 2104 0 13 9 10 11 12...

Страница 30: ...E n g l i s h INSTALLATION MANUAL 30 38C 2108 0 A X 6 m B X 6 m X R 38C 2106 0 38C 2107 0 16 14 15...

Страница 31: ...E n g l i s h INSTALLATION MANUAL 31 38P 0490 0 A B C 38P 0488 0 38P 0489 0 38p 0023 38P 0028 1 21 17 18 19 20...

Страница 32: ...E n g l i s h INSTALLATION MANUAL 32 38P 0491 0 A 38P 0492 0 B 38P 0493 0 C 22 23 24...

Страница 33: ...E n g l i s h INSTALLATION MANUAL 33 38p 0179 38p 0181 5mV 38p 0182 38c 2109 0 20 17 38c 2110 0 43 38 40 43b 41 42...

Страница 34: ...E n g l i s h INSTALLATION MANUAL 34 38C 1940 300 150 450 150 150 A B 38c 2111 0 45 44...

Страница 35: ...E n g l i s h INSTALLATION MANUAL 35...

Страница 36: ...E n g l i s h DRU Verwarming B V The Netherlands Postbus 1021 NL 6920 BA Duiven Ratio 8 NL 6921 RW Duiven EN...

Отзывы: