14

4-2-3 Boost function

1)  No. 22 Boost Mode (boost mode selection)

One of the following modes can be selected according to the load characteristics.

[1]  Manual: Manual boost

For the characcteristics, see 4-17 (torque

boost setting) and 4-1-10(V/F pattern

selection)

[2]  Auto:

Auto boost

Auto boost is validated when code No. 13 (V/F

pattern selection) is set to V/F constant character-

istics or V/F square law reduction characteristics.

The boost quantity is automatically controlled

based on the motor current and motor internal

constants.  See Figure 11 for the auto boost

characteristics.

4-2-4 Bend function

The V/F constant characteristics can be changed to the 2-stage bend according to the motor and load.  The bend

point voltage and bend point frequency are set as % of the ratings.

1)  No. 23

Bend-Point.V

(bend point voltage)

The bend point voltage is set as % of the rated

output voltage.

2)  No. 24

Bend-Point.F

(bend point frequency)

The inclination of the V/F constant characteristics

when starting the inverter can be increased or

decreased according to the load.
4-2-5 Torque limit function

1)  No. 25

Lim.Torq.SW (torque limit switch)

Whether the torque limit is provided can be selected in each operation area.

The torque limit can be selected from among the following

according to the load.

(1)  P-off, B-off

The torque limit is not provided for both the power

side and braking side.

(2)  P-on, B-off

The torque limit is provided only for the power side.

(3)  P-off, B-on

The torque limit is provided only for the braking

side.

(4)  P-on, B-on

The torque limit is provided for both the power

and braking side.

Содержание VF61

Страница 1: ...NVERTER FUNCTION MANUAL 12 10 96 REV 820 Lakeside Drive Gurnee IL 60031 1 800 DRIVCON 374 8266 PH 847 855 9150 FAX 847 855 9650 http www drivecon com Email drive sales drivecon com ULYHFRQ 0 2 7 2 5 5 9 6 1 2 1 7 5 2 6 ...

Страница 2: ... Items 1 5 3 Special Setting Items 2 5 4 Optional Setting Items 5 2 Alarm indication 7 3 Console Monitor Indications 8 4 Description of Functions 4 1 Basic Setting Items 9 4 2 Special Setting Items 1 13 4 3 Special Setting Items 2 25 4 4 Optional Setting Items 26 VF61 Series Function Manual 1 ...

Страница 3: ...HOHFWLRQ 1 0LQ VWDUW 0LQLPXP IUHTXHQF VWDUW D IUHH VWDUW UHH VWDUW E PSRVVLEOH D 6WRS PRGH 6WRS PRGH VHOHFWLRQ 1 GHFHO VWRS HFHOHUDWLRQ VWRS D IUHH VWRS UHH VWRS E PSRVVLEOH D XQFWLRQ XS 6HOHFWLRQ RI VSHFLDO VHWWLQJ LWHPV 1 6S VHW 6SHFLDO VHWWLQJ D 3RVVLEOH D 1 6S VHW 6SHFLDO VHWWLQJ E 2SWLRQ 2SWLRQDO VHWWLQJ F 6SHFLDO VHWWLQJV 6S VHW LP 8SSHU UHTXHQF OLPLW XSSHU LP WR PSRVVLEOH LP RZHU UHTXHQF OL...

Страница 4: ...lection Sec 10 Sec d Impossible a 39 Rotation Sel Rotation direction selection N A For Rev Both Both forward and reverse allowed a For only reverse rotation is inhibited b Rev only Forward rotation is inhibited c Impossible a 40 IPF Restart Restart after instantaneous power failure selection N A off ower failure lasting 10 seconds or less is a on assumed to be instantaneous power failure b Impossi...

Страница 5: ...unction selection Arrive Ref F Set value is reached a F Detect 1 F Frequency detection 1 b F Detect 1 F Frequency detection 1 c F Detect 1 F Frequency detection 1 d F Detect 2 F Frequency detection 2 e F Detect 2 F Frequency detection 2 f F Detect 2 F Frequency detection 2 g T Detect T Torque detection h OL Pre Alarm Overload Pre alarm i Under Volt Insufficient voltage j Reverse Now Reverse rotati...

Страница 6: ...d inverter capacity Impossible N A 18 Motor V Rated motor voltage V 400V class 320 to 480 Impossible 400V V 200V class 160 to 240 Impossible 200V 19 Motor I Rated motor current A 1 to Rated inverter current Impossible N A 20 Motor F Rated motor frequency Hz 30 to 400 Impossible 60Hz 21 Motor RPM Rated motor RPM rpm 300 to 24000 Impossible 1740rpm 22 Motor Pole Number of poles of the motor N A 2 4 ...

Страница 7: ...6 Thispagereservedforyournotes ...

Страница 8: ...ure Note 2 on Over Freq R Excess frequency on EXT Failure 1 Q External failure 1 for multifunctional input on EXT Failure 2 Q External failure 2 for multifunctional input on EXT Failure 3 Q External failure 3 for multifunctional input on EXT Failure 4 Q External failure 4 for multifunctional input on Panel Error 3Q U Console panel error on Option Error R3 U Internal option board error This occurs ...

Страница 9: ...minal check 1 bit on 1 Meaning of each bit is shown in Table 7 10 I2 term check Input terminal check 2 bit on 1 Meaning of each bit is shown in Table 7 11 O term check Output terminal check bit on 1 Meaning of each bit is shown in Table 7 12 Not used 13 Not used 14 Not used 15 ROM Version ROM version The XX XX portion of the ROM software version VF61 XX XX is indicated Alphabetic characters A B ho...

Страница 10: ...requency reference frequency and excess frequency can be set When the START key is pressed the motor rotates at the reference frequency 1 No 00 Ref set F reference frequency 2 No 05 Top F maximum frequency 3 No 11 Min F minimum frequency 4 No 21 OF Set excess frequency protection is performed 4 1 2 Jog frequency The jog frequency can be set 1 No 01 FOR JOG F forward jog frequency 2 No 02 REV JOG F...

Страница 11: ... No 07 Rated Out V rated output voltage Note The rated output voltage can be lowered than the rated motor voltage Motor V and used Note 1 For program operation three more points can be set for the acceleration deceleration time Four points in total Note 2 When the S shape acceleration deceleration is used time from 0 Hz to Top F and time from Top F to 0 Hz increase for the S shape 4 1 7 Torque boo...

Страница 12: ...rload counter decreases the value The overload pre alarm function can also be used to turn on the multifunction output terminal when the over load counter exceeds a specified value That is the overload protection can be prevented by detecting the pre alarm output to reduce the torque See 4 2 21 4 1 10 V F pattern selection 1 No 13 V F Pattern V F pattern selection The V F pattern characteristics c...

Страница 13: ...de start mode selection 1 Min F start minimum frequency start The inverter is started with the output frequency set as Min F Note When Min F Start is selected for restarting the inverter after instantaneous power failure the inverter is restarted at the frequency just before the instantaneous power failure has occurred 2 No 15 Stop Mode stop mode selection 1 decel stop deceleration stop When the s...

Страница 14: ... the reference frequency range is ignored and the plus side setting is used However reversal by using For Rev is possible 4 2 2 Output frequency characteristics 1 No 19 Ex RefF set selection of external frequency setting 1 When 10 0 10V is selected the frequency can be set using voltage 2 When 4 20mA is selected the frequency can be set using current When current is selected however the frequency ...

Страница 15: ...r and load The bend point voltage and bend point frequency are set as of the ratings 1 No 23 Bend Point V bend point voltage The bend point voltage is set as of the rated output voltage 2 No 24 Bend Point F bend point frequency The inclination of the V F constant characteristics when starting the inverter can be increased or decreased according to the load 4 2 5 Torque limit function 1 No 25 Lim T...

Страница 16: ...boost 15 4 2 6 DC brake function DC brake can be applied when stopping the inverter In this case set the voltage start fre quency an time for the DC brake The multi function input signal can be used to apply DC brake Turn off the start command and then turn on the selected multifunction input 1 No 28 DC br V DC brake voltage 2 No 29 DC Br F DC brake start frequency 3 No 30 DC Br Time DC brake time...

Страница 17: ...rse rotations are allowed 2 For only Reverse rotation is inhibited 3 Rev only Forward rotation is inhibited The rotation direction can be selected from among the three choices shown left The reverse rotation with Rev only selected or forward rotation with For only selected are limited to 0 Hz 4 2 10 Rotation direction selection Insufficient voltage lasting about 10 seconds or less is assumed to be...

Страница 18: ...ant square law reduction or bend characteristics are used for operation 2 Slip Compen Slip compensation control This is selected to compensate the slip amount of the motor corrects the output frequency so that the number of motor rotations is not reduced when the load increases 3 Freq Droop Frequency droop control This is selected to droop the frequency when the load increases 4 ASR Control ASR co...

Страница 19: ...equency 56 PGM1 Acc Dec Program operation 1 acceleration deceleration selection 48 PGM 1 Time Program operation 1 time 3 04 Preset2 F Preset 2 frequency 57 PGM2 Acc Dec Program operation 2 acceleration deceleration selection 49 PGM 2 Time Program operation 2 time 4 86 Preset3 F Preset 3 frequency 58 PGM3 Acc Dec Program operation 3 acceleration deceleration selection 50 PGM 3 Time Program operatio...

Страница 20: ... to switch between the console and terminal Terminal 33 34 voltage at the terminal is applied 35 34 current at the terminal is applied Console The reference frequency set in code No 00 Ref set F at the console Option 1 Signal from the optional board Option 2 Not used reserved for function extension Up Down Key Acceleration deceleration operation using the UP DOWN keys at the console Up Down Term A...

Страница 21: ...8 T Detect T Torque detection The torque can be set in code No 73 Detect Torq torque detection 9 OL Pre Alarm Overload pre alarm The specified value can be set in code No 95 OL Pre Alarm overload pre alarm setting 10 Under Volt Insufficient voltage This is when the inverter is stopped due to insufficient voltage 11 Reverse Now Reverse operation in progress This is output when DIR REM at the consol...

Страница 22: ...inal 27 5 No 78 Term 28 Sel terminal 28 6 No 79 Term 29 Sel terminal 29 When the same function is set at two or more terminals and any one of them is turned on the condition is assumed to be on OR condition The function which are not set at any terminal is assumed to be off Emergency stop B Emrg Stop B how ever is B contact operation When the selected terminal is opened emergency stop occurs Multi...

Страница 23: ...Output frequency acceleration Output Frequency deceleration Multifunction input terminals can be used to accelerate decelerate the output frequency Set code No 63 Ref F Sel to Up Down Term 8 9 10 11 Ext Failure 1 Ext Failure 2 Ext Failure 3 Ext Failure 4 External failure 1 External failure 2 External failure 3 External failure 4 Multifunction input terminals can be used Failure input to stop the i...

Страница 24: ...output voltage Vout Output voltage 7 5V 400V 400V Class 200V 200V Class Iout Output current 5V 100 rating for the inverter Torq Torque torque current 5V 100 rating for the inverter both and directions Fout Output frequency 10V Top F both and directions Internal mon Adjusting monitor for internal use 4 2 17 Multifunction analog output 1 No 91 Term 9 Sel multifunction analog output selection Output ...

Страница 25: ...ear alarm data set it to yes After the clearing it is automatically set back to no Table 16 Inverter LED indication No LCD Monitor indications Unit Remarks 0 Fout Output frequency Hz 1 Fref Reference frequency Hz 2 Iout Output current A 3 Vout Output voltage V 4 Torq out Torque torque current Current for the same phase as the output voltage is indicated 5 Vdc DC voltage V 6 Motor Speed Synchronous...

Страница 26: ...already set to Sp set 2 select Sp set 2 again to set those code numbers 4 3 1 Input of motor constants Before performing auto tuning input the following motor constants inscribed on the motor rating plate No Code No LCD Setting 1 No 17 Motor Cap Rated motor capacity 2 No 18 Motor V Rated motor voltage 3 No 19 Motor I Rated motor current 4 No 20 Motor F Rated motor frequency 5 No 21 Motor RPM Rated...

Страница 27: ...o the optional board No Code No LCD Setting 1 No 17 4 20out Sel 4 20mA output selection No Selection item No Selection item 1 Vout Output voltage 5 Fout Output frequency 2 Iout Ouput frequency 6 Internal Mon Adjusting monitor for internal use 3 Torq Torque 2 No 18 4 20out Gain 4 20mA output gain 3 No 19 4 20outOfset 4 20mA output offset 4 No 20 ISOin Gain Insulation input gain 5 No 21 ISOin Ofset ...

Страница 28: ...820 Lakeside Drive Gurnee IL 60031 1 800 DRIVCON 374 8266 PH 847 855 9150 FAX 847 855 9650 http www drivecon com Email drive sales drivecon com ULYHFRQ 0 2 7 2 5 5 9 6 1 2 1 7 5 2 6 ...

Отзывы: