No.
Function indication
Explanation
14
P-Timer Next
Go to the next PGM operation step
When this is selected, you can go to the next program operation step before the
current program operation step is finished.
The operation can be performed by inputting the 1-shot contact at the
multifunction input terminal.
15
16
Emerg.Stop-A
Emerg.Stop-B
Emergency stop A contact
Emergency stop B contact
When emergency stop A contact is input at the multifunction input terminal
during inverter operation, output from the inverter can be turned off.
Emergency stop B contact can also be turned off output from inverter.
Table 15 Multifunction input items 3
Selection Items
Analog output voltage
Vout
Output voltage
7.5V=400V (400V Class)
200V (200V Class)
Iout
Output current
5V=100% (rating for the inverter)
Torq
Torque (torque current)
± 5V=100% (rating for the inverter)
(both + and - directions)
Fout
Output frequency
± 10V=Top.F (both + and - directions)
Internal mon
Adjusting monitor for
internal use
4-2-17 Multifunction analog output
1) No. 91 Term-9.Sel (multifunction analog output selection)
Output the following selection items to output terminals (9) and (10)
(Accuracy: ± 10%)
4-2-18 Carrier frequency
The carrier frequency for the inverter can be changed.
1) No. 92 Carrier.F (carrier frequency)
4-2-19 Line speed indication adjustment
1) No. 93 L-SP.Adjust (line speed indication adjusting gain)
The line speed indication at the inverter LED and the console can be adjusted. Set the line speed used for
Top.F operation.
4-2-20 STB adjustment
1) No. 94 STB.Adjust (STB adjustment)