Service Manual
rev 5.0 with software Ind1V022
7.1 Standard
settings
002 – 005
007 – 011
7.1.1 Settings for sensor bearing
The table below indicate the SSU settings for standard cases. Motors with nominal frequency 100Hz or 120Hz
are equipped with bearing sensor. After adjustment, check that parameters V 4.8.1 Overspd Lim 1 and V 4.8.2
Overspd Lim 2 have value between 115% and 125%.
Max Freq S2 is normally set to 120Hz, also when nominal frequency and Max freq S1 are 100Hz. Check that
parameters P 2.2.2. Motor Nom Freq and P 2.2.3. Motor Nom Speed have correct values from motor type
plate.
Settings for sensor bearings
D2L
015 - 055
P 2.2.11, Max Freq S2
120
120
120
P 2.2.14 Pulse Number
32
64
80
Rotary switch S1
1 A D
Switch S2-1
ON ON ON
Switch S2-2
OFF OFF OFF
Switch S2-3
OFF OFF OFF
Switch S2-4
ON ON ON
Rotary switch S3
1 A D
1
2
3
4
ON OFF
S1
S2
S3
7.1.2 Settings for pulse wheel speed sensor or encoder (24 ppr)
The table below indicate the SSU settings for standard cases. Motors with nominal frequency 50Hz or 60Hz
are equipped with pulse wheel speed sensor or encoder. After adjustment, check that parameters V 4.8.1
Overspd Lim 1 and V 4.8.2 Overspd Lim 2 have value between 115% and 125%.
Check that parameters P 2.2.2. Motor Nom Freq and P 2.2.3. Motor Nom Speed have correct values from
motor type plate.
Settings for pulse wheel sensor or encoder (24 ppr)
D2L
002 – 055
002 – 055
P 2.2.11, Max Freq S2
50 / 100
60 / 120
P 2.2.14 Pulse Number
24
24
Rotary switch S1
4 7
ON ON
Switch S2-2
ON ON
Switch S2-3
OFF OFF
Switch S2-4
ON ON
Rotary switch S3
4 7
1
2
3
4
ON OFF
S1
S2
S3
Switch S2-1
40/58
Drivecon Inc. reserves the right to alter or amend the above information without notice.