Service Manual
rev 5.0 with software Ind1V022
-
measure main circuit diodes and IGBT
transistors
-
If the fault comes again, change the power
unit.
F 8
System fault
System
fault due to component failure or faulty
operation
.
Reset: switch power off and restart after the lamps
of keypad are off.
Check:
If the fault comes again, change the D2V.
F 9
Undervoltage
DC-bus voltage has dropped below 333Vdc
In case of temporary supply voltage break, reset the
fault and start again. Check mains input.
F 10
Input line
supervision
One input line phase is missing.
F 11
Output phase
supervision
Current supervision has sensed that one of the
motor phases has no current
Check:
F 12
Braking chopper
supervision
Braking chopper or braking resistor circuit has
failed. Test pulse measures transistor collector
voltage. Fault appears if
Reset: switch power off and restart after the lamps
of display are off.
Check:
F 13
Inverter
undertemperature
Temperature of heat sink is below acceptable
operating level (-10°C /14°F)
Check
F 14
Inverter
overtemperature
Temperature of heat sink is over acceptable
operating level
+90°C (194°F).
Overtemperature warning is issued when the heat
sink temperature e85°C (185°F)
Check:
F 22
F 23
EEPROM checksum
fault
Parameter save error
After power off the inverter will automatically load
factory default parameter settings. D2T does not
work properly nor enable driving after this fault.
Check:
F 24
Changed data
warning
Changes may have occurred in the different counter
data due to mains interruption
No special actions required. Take a critical attitude
to the counter data.
F 25
Microprocessor
watchdog-fault
Reset: switch power off and restart after the lamps
of display are off.
If the fault comes again, contact service.
F 26
Power Unit Fault
F 32
Fan cooling fault
Cooling fan of the frequency converter do not work,
when ON command has been given
If the fault comes again, contact authorized
service.
F 35
Application fault
Run-time exception in the application program
Contact authorized service.
F 36
Control Unit
Faulty Control Unit.
Contact authorized service.
F 37
Device changed
Option board changed.
Reset the fault
F 38
Device added
Option board added.
Reset the fault
F 39
Device removed
Option board removed.
Reset the fault
F 40
Device unknown
Unknown option board or drive.
Check board and drive type.
F 41
IGBT tempetature
Too high temperature in IGBT transistors.
Reset: switch power off and restart after the lamps
of keypad are off.Check:
-
read fault extension code and contact
authorized service
-
mains supply voltage interrupted
-
If mains supply is correct, an internal failure
has occurred.
-
inverter fault can also cause an undervoltage
trip
-
Contact authorized service.
-
external fault during run may cause an
undervoltage trip
Check:
-
supply voltage
-
mains connection.
-
motor cable connections
-
measure motor phase currents and compare
to display value
-
braking resistor is broken
-
braking resistor and insulation resistance
-
braking chopper is broken
-
measure braking transistor IGBT and free
wheeling diodes
-
braking resistor is not installed
-
If resistor is OK, then the chopper is broken
-
Contact authorized
service
-
ambient temperature
-
cubicle heating
-
ambient temperature
-
inverter cooling fan operation
-
cooling air flow through heat sink
-
heat sink is not dusty
-
interference fault
-
component failure (control unit)
-
all parameter settings.
-
+24V voltage output loading
-
If the fault comes again, contact authorized
service.
-
interference fault
-
component failure (control unit)
-
long duration overload
-
motor parameters
-
lowered cooling
-
u/f curve settings
-
high environment temperature
-
motor loading
-
brake operation
48/58
Drivecon Inc. reserves the right to alter or amend the above information without notice.