Continuous current
I
CONT
A
60 75 90 110
Fuse
A
63 80 100 125
Max motor cable length
m
50 50 75 75
Ft
160 160 240 240
Motor cable
40
o
C mm
2
16 25 35 35
104
o
F AWG
6 4 2 2
Braking resistor cable
40
o
C mm
2
10 10 16 16
104
o
F AWG
8 8 6 6
2.3.4 Cable
protection
To protect the supply cables against short circuit there must be fuses or motor circuit breakers (MCCBs)
installed at the mains end of the supply cable. Dimensioning of the fuses or MCCBs depends on the cable
used and on the type of primary fuses or MCCBs. If there are no other regulations, the values given in this
section can be used to dimension fuses (three phase 400V supply).
The overload protection of inverter protects both the supply and the motor cables. The fuses of the supply
provide the short circuit protection.