13
STS INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION
Table 13-1:
Outdoor Enclosure dimensions*
Item
Description
STS model
25–100
200–800
inches
mm
inches
mm
A
Enclosure height
56.00
1422
66.00
1676
B
Enclosure width
36.00
914
46.00
1168
C
Pipe chase position
4.50
114
4.50
114
D
2.00
57
3.50
89
E
Pipe chase size
20.00
508
32.00
312
F
8.00
203
10.00
254
G
Steam pipe position
6.00
152
8.50
216
H
18.63
473
22.00
559
J
14.50
368
20.50
521
K
12.25
311
11.00
279
L
Enclosure length
60.00
1524
78.00
1981
* See drawings in Figures 12-1 and 13-1.
mc_012611_1015
Outdoor Enclosure
DC-1478
B
Standard steam outlet (exits enclosure here)
Intake ven ti la tion fan
D
C
Pipe chase extending 1" (25 mm) above enclosure fl oor
STS hu mid i fi er
Elec tri cal and cleanout access door
Control panel heater
Control panel
Enclosure drain
F
E
Optional steam outlet
(exits enclosure through pipe chase)
Valve access door:
• Models 25-100 have one access door
• Models 200-800 have two access doors
Intake ventilation fan
Valve section heater
Valve access door
J
H
mc_012611_0837
Table 13-2:
STS Outdoor Enclosure electrical
specifications
Voltage
Current
Maximum
disconnect
Outdoor
Enclosure
without
heater
package
120 Vac,
50/60 Hz
3.5 A
10 A
Outdoor
Enclosure
with heater
package
120 Vac,
50/60 Hz
13.5 A
20 A
FIGURE 13-1: OUTDOOR ENCLOSURE, TOP VIEW