STS INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION
OM-933
Optional set of four legs and hardware
OM-947
DriSteem optional wall
brackets (two required)
B
A
DC-1454
STS model
A
B
in.
mm
in.
mm
25 and 50
15.5
394
24
610
100
21
533
30
762
Due to size and weight, STS models
200, 400, and 800 must be mounted
on H-legs.
mc_010511_1740-tap
mc_010511_1741-tap
mc_010511_1743-tap
mc_010511_1744-tap
Tap/softened water model shown
Tap/softened water model shown
Tap/softened water model shown
Mounting methods
Notes:
1. Secure rods to overhead construction.
2. 3/8" (M10) threaded rod of length required.
3. Angle or channel sized to properly support
humidifi er.
4. Humidifi er drain to appropriate building
waste. Do not drain humidifi er directly into
drip pan. Install water seal as shown on
Pages 22 through 25.
5. Drip pan (by installer) recommended in
overhead installations to prevent possible
water damage to equipment below.
Provide 18"
(457 mm)
minimum
clearance
above cover
DC-1453
See Note 1
See Note 2
See Note 3
See Note 4
25%
larger than
humidifi er
1¼" (DN32)
minimum
See Note 5
Tap/softened water model shown
FIGURE 8-1: SUPPORT LEGS, STS MODELS 25, 50, AND 100 ONLY
FIGURE 8-2: TRAPEZE HANGER, STS
MODELS 25, 50, AND 100 ONLY
FIGURE 8-3: WALL BRACKETS, STS MODELS 25, 50, AND 100 ONLY
FIGURE 8-4: H-LEGS, STS MODELS 200, 400, AND 800 ONLY