42
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Mounting
bracket
Level
DC-1207
Secure end of tube to AHU using
support bracket (0.421" dia.
[11 mm] holes in top, bottom, and
end of bracket)
12" (305 mm) min.
4" (100 mm) min.
4" (100 mm) min.
Maxi-bank option field piping
MAXI-BANK HUMIDIFIER
See Table 28-1
Steam jacket piping
(See Note 6 on Page 38)
x
x
x
x
Dispersion tubes
(see Note 4 on Page 38)
NOTES:
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Maxi-bank option piping notes” on Pages 38 and 39, and see Pages 14 and 15 for more
information about trap types and trap piping.
Same size as
separator inlet
From
steam
source
Factory-supplied header and
interconnecting piping
Steam valve and actuator
(see Note 4)
Separator
3/4" pipe thread
(DN20)
12" (305 mm) min.
Header trap by installer (see
y (see y note above)
x (See Table
minimum tube
spacing)
y = 4½" (114 mm)
min. Center
assembly in duct.
See Note 10 on
Page 39.
Install strainer within 3'
(1 m) of humidifier (see
Note 4)
Isolation valve
(by others)
mc_050511_1456
Steam jacket trap (see Note 8 on Page 39)
Separator trap
(See Note 8
on Page 39)
FIGURE 42-1: MAXI-BANK OPTION, TOTAL TUBE LENGTH LESS THAN OR EQUAL TO 45' (13.7 M) IN AN AHU