27
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
From steam
source
Separator
Condensate
drain
12" (305 mm) min.
Secure and seal escutcheon plates
Dispersion tube with
noninsulated steam
jacket (see Note 4 on
Secure end of tube to duct using
support bracket (0.421" dia. [11 mm]
holes in both sides and end of bracket)
DC-1068
4" (100 mm) min.
Drip
3/4" pipe thread
(DN20)
Duct (minimum duct width is
9" [229 mm])
SINGLE-TUBE HUMIDIFIER
Install strainer
within 3' (1 m)
of humidifier (see
Note 4)
Piping downstream from strainer
should be same size as strainer.
Steam valve and actuator
(see Note 4)
NOTES:
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Piping notes” on Page 23, and see Pages 14 and 15 for more information about trap types and trap
piping.
Trap (see Note 7 on Page 23)
Airflow
Isolation valve
(by others)
mc_051011_0830
Field piping
FIGURE 27-1: VERTICAL DISPERSION TUBE INSTALLED IN A HORIZONTAL AIRFLOW