44
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Valve
Pipe size same as inlet to
separator
Separator
See Note 2 on Page
Secure and seal escutcheon plates
Airflow (see Note 5 on Page 38)
Dispersion tube (see Note 5
on Page 38)
Pitch supply header
1/8"/ft (1%) toward drain
Level
Header trap
(see Note 9 on Page 39)
DC-1075
Secure end of tube to duct using support bracket (0.421" dia.
[11 mm] holes in both sides and end of bracket)
x
x
x
x
x
y
From steam source
Maxi-bank option field piping
mc_040711_1805
MAXI-BANK HUMIDIFIER
Install strainer
within 3' (1 m)
of humidifier
(see Note 4)
NOTES:
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Maxi-bank option piping notes” on Pages 38 and 39, and see Pages 14 and 15 for more
information about trap types and trap piping.
See Table 29-1 for minimum
tube spacing (x). See Note 10
on Page 39.
y = 4½" (114 mm) min.
Center assembly in
duct. See Note 10 on
Page 39.
Isolation valve (by others)
y
FIGURE 44-1: MAXI-BANK OPTION INSTALLED IN A DUCT VERTICAL AIRFLOW