STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Mounting
bracket
See Table 28-1
Secure and seal escutcheon plates
Escutcheon plate
Level
Steam jacket piping
(See Note 6 on Page 38)
x
x
x
x
DC-1072
Secure end of tube to duct using
support bracket (0.421" dia. [11
mm] holes in top, bottom, and end of
bracket)
12" (305 mm) min.
4" (100 mm)
min.
Dispersion tubes
(see Note 4 on Page 38)
Maxi-bank option field piping
MAXI-BANK HUMIDIFIER
NOTES:
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer; right-hand discharge shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Maxi-bank option piping notes” on Pages 38 and 39, and see Pages 14 and 15 for more
information about trap types and trap piping.
Same size as separator inlet
From
steam
source
Factory-supplied header and
interconnecting piping
Steam valve and actuator
(see Note 4)
Separator
3/4" pipe thread
(DN20)
12" (305 mm) min.
Trap (See Note 8
on Page 39)
4" (100 mm) min.
Header trap by installer (see
y (see y note above)
x (See Table
29-1 for
minimum tube
spacing)
y = 4½" (114 mm)
min. Center
assembly in
duct. See Note
10 on Page
39.
Install strainer within 3'
(1 m) of humidifier (see
Note 4)
Isolation valve
(by others)
Steam jacket trap (see Note 8 on Page 39)
mc_040611_1550
FIGURE 40-1: MAXI-BANK OPTION, TOTAL TUBE LENGTH LESS THAN OR EQUAL TO 45' (13.7 M)