33
STEAM INJECTION INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
y
y
x
See Table 29-1 for
minimum tube spacing (x).
Level
Airflow
(see Note 11
Secure end of tube to duct using
support bracket (0.421" dia. [11
mm] holes in sides and end)
Dispersion tube
(see Note 11 on Page 30)
See Note 7 on Page 30
See Note 2 on Page 30
See Note 9 on Page 30
Pitch header 1/8"/ft (1%) toward
header trap drain
Condensate return
Trap
Separator
Same size as
separator inlet
From
steam
source
Secure and seal escutcheon plates
Duct
x
x
DC-1074
Field piping
MULTIPLE-TUBE HUMIDIFIER
Install strainer within
3' (1 m) of humidifier
(see Note 4)
Notes:
1. To avoid metal fatigue, allow for dispersion tube thermal expansion.
2. Dashed lines indicate provided by installer (see Maxi-bank option beginning on Page 36). Right-hand discharge
shown.
3. Dri-calc is DriSteem’s free sizing and selection software available at www.dristeem.com.
4. Steam valve and strainer sizes are provided by Dri-calc (Note 3).
5. See “Piping notes” on Page 30, and see Pages 14 and 15 for more information about trap types and trap
piping.
Isolation valve
(by others)
Steam valve and actuator
(see Note 4)
y = 4½" (114 mm) min.
Center assembly in duct.
See Note 10 on Page
mc_051011_0902
FIGURE 33-1: MULTIPLE-TUBE HUMIDIFIER INSTALLED IN A VERTICAL AIRFLOW