Display Points
Alarm Point
Description
Solution
11
56
NetDog 82 BW
DX 1 fail
NGDdx 1 Fail (Expansion shelf 1
communication link failure)
Under Ports > Options, verify the
number of configured NGDdx units.
Use EXP filter debug and port LEDs to
help diagnose the problem. Use
DB9M to DB9M with null crossover for
cabling. Verify the DIP addressing on
the back of the NGDdx unit.
57
NetDog 82 BW
DX 2 fail
NGDdx 2 Fail (Expansion shelf 2
communication link failure)
58
NetDog 82 BW
DX 3 fail
NGDdx 3 Fail (Expansion shelf 3
communication link failure)
59
GLD 1 fail
GLD address 1 is failed.
Connect just GLD unit 1 and attempt
to poll. Verify GLD is connected to
data port 8 and the hardware is
RS485, not RS232.
60
GLD 2 fail
GLD address 2 is failed.
Verify the GLD unit addressing, and
test GLD units individually on the GLD
communication bus.
61
GLD 3+ fail
One or more GLD units addressed 3
through 12 may be failed.
Reduce the number of connected
GLD units to determine which unit
may be causing the link to fail.
62
Chan. Port
Timeout
Chan. Port has not forwarded any
traffic in the time specified by the
Channel Timeout Timer. The channel
feature forwards data between two
ports so the NG may be used to
analyze serial traffic using CHAN filter
debug.
Change the data port type to OFF, or
set the Channel Timer to a different
setting.
63
Craft Timeout
The Craft Timeout Timer has not been
reset in the specified time. This
feature is designed so other machines
may keep the TTY link active. If the
TTY interface becomes unavailable to
the machine, then the Craft Timeout
alarm is set.
Change the Craft Timeout Timer to 0
to disable the feature.
64
Event Que Full
The Event Que is filled with more than
500 uncollected events.
Enable DCP timestamp polling on the
master so events are collected, or
reboot the system to clear the alarm.
Table A3 - System Alarms Descriptions (continued)