22
DPMS XPQ User Manual
3-Phase 4-Line 2PT mode (2LN)
In some 3-Phase 4-Line Wye systems, 2PT Wye mode is often used as in
fig 2.12. It is supposed that the 3 phases of the power system are balanced. The
voltage of V2 is calculated according to V1 and V3. The voltage input mode of
the DPMS XPQ should be set to 2LN for 2PT voltage input wiring mode.
Fig 2.12 2LN with 2PTs
3-Phase 3-Line open Delta Mode (2LL)
Open delta wiring mode is often used in high voltage systems. V2 and
Vn connect together in this mode. The voltage input mode of the DPMS XPQ
should be set to 2LL for voltage input wiring mode.
Fig 2.13 2LL with 2PTs
Содержание XPQ
Страница 1: ...POWER INSTRUMENTS DPMS XPQ Multi Function Power Meter User Manual 1087 332...
Страница 2: ......
Страница 7: ...Chapter 1 Introduction Purpose Application Area Functions DPMS XPQ Series 5...
Страница 13: ...Chapter 2 Installation Appearance and Dimensions Installation Method Wiring 11...
Страница 28: ...26 DPMS XPQ User Manual 2 3LN 3CT with 2 CTs Fig 2 19 3LN 3CT with 2 CTs 3 2LN 2CT Fig 2 20 2LN 2CT...
Страница 29: ...27 POWER INSTRUMENTS 4 2LN 1CT Fig 2 21 2LN 1CT 5 2LL 3CT Fig 2 22 2LN 3CT Acuvim X Fig 2 21 2LN 1CT...
Страница 30: ...28 DPMS XPQ User Manual 6 2LL 2CT Fig 2 23 2LL 2CT 7 2LL 1CT Fig 2 24 2LL 1CT...
Страница 59: ...Chapter 4 Function and Software Functionality and Utility Software 57...
Страница 68: ...66 DPMS XPQ User Manual Here is an example Fig 4 7 Demand Here is to set demand...
Страница 90: ...88 DPMS XPQ User Manual Fig 4 20 Voltage Eligibility Ratio...
Страница 126: ...124 DPMS XPQ User Manual...
Страница 127: ...125 Appendix Appendix A Technical Data and Specifications Appendix B Ordering Information...
Страница 133: ......