14
DPMS XPQ User Manual
The meter should be installed in a dry and dust free environment and avoid
heat, radiation and high electrical noise sources.
Maximum Altitude:
2,000m
Site Requirement:
Indoor Use
Installation Steps
Normally, meters are installed on the panel of switch gear.
1. First, cut a square hole on the panel of the switch gear. The cutting size
is in fig 2.3 Unit (mm)
Fig 2.3 Panel Cutting
2. Second, remove the clips from the meter and insert the meter into the
square hole from the front side.
Fig 2.4 Put the meter into the square hole
Cut
panel
90±
0.5
0.0
90±
0.5 0.0
Содержание XPQ
Страница 1: ...POWER INSTRUMENTS DPMS XPQ Multi Function Power Meter User Manual 1087 332...
Страница 2: ......
Страница 7: ...Chapter 1 Introduction Purpose Application Area Functions DPMS XPQ Series 5...
Страница 13: ...Chapter 2 Installation Appearance and Dimensions Installation Method Wiring 11...
Страница 28: ...26 DPMS XPQ User Manual 2 3LN 3CT with 2 CTs Fig 2 19 3LN 3CT with 2 CTs 3 2LN 2CT Fig 2 20 2LN 2CT...
Страница 29: ...27 POWER INSTRUMENTS 4 2LN 1CT Fig 2 21 2LN 1CT 5 2LL 3CT Fig 2 22 2LN 3CT Acuvim X Fig 2 21 2LN 1CT...
Страница 30: ...28 DPMS XPQ User Manual 6 2LL 2CT Fig 2 23 2LL 2CT 7 2LL 1CT Fig 2 24 2LL 1CT...
Страница 59: ...Chapter 4 Function and Software Functionality and Utility Software 57...
Страница 68: ...66 DPMS XPQ User Manual Here is an example Fig 4 7 Demand Here is to set demand...
Страница 90: ...88 DPMS XPQ User Manual Fig 4 20 Voltage Eligibility Ratio...
Страница 126: ...124 DPMS XPQ User Manual...
Страница 127: ...125 Appendix Appendix A Technical Data and Specifications Appendix B Ordering Information...
Страница 133: ......