L Possible cause
Remedy
6)
✘
-
-
✘
✘
-
-
-
-
✘
-
-
Start-up pressure set too high
Check setting.
-
✘
-
-
✘
✘
-
✘
-
✘
-
✘ Pressure transmitter set incorrectly or
defective
Check setting.
-
-
-
-
-
-
-
✘
-
-
✘
✘ Pre-charge pressure of the accumulator
too low
Restore nitrogen cushion.
-
-
-
-
-
-
-
✘
-
-
✘
✘ Defective accumulator
Check integrity/replace, if necessary.
-
-
-
-
-
-
✘
-
-
-
-
-
Defective mechanical seal
Replace.
✘
-
-
-
-
-
-
✘
-
✘
-
-
Suction-side pressure switch set
incorrectly or defective
Check setting.
-
-
✘
✘
✘
-
-
✘
✘
✘
✘
-
Defective check valve in the pressure
booster system
Check, replace sealing element as
necessary.
-
-
-
-
✘
-
-
-
✘
✘
-
✘ Water extraction higher than stated in
the purchase order
Contact KSB.
-
✘
-
-
-
-
-
-
✘
-
-
✘ Motor protection switch triggered or set
incorrectly, or pump seized
Compare setting with the motor's rating
plate data.
-
-
-
-
-
-
-
-
-
-
✘
-
Delay setting too short
Check setting.
-
✘
-
-
-
-
-
-
-
-
-
-
Mains supply interrupted
Check and remedy defect/check fuse.
-
✘
-
-
-
-
-
-
-
-
-
-
Control current fuse tripped (control
cabinet)
Determine cause and reset.
-
✘
-
-
-
-
-
-
✘
-
-
-
Main fuse on (owner-supplied)
distribution board loose or blown; fuses
possibly too small or too fast
Check fuses and replace as necessary.
Measure the motor current.
-
-
-
-
-
-
-
-
✘
-
-
-
Intermittent voltage fluctuations
Press reset and fault acknowledgement
key.
-
✘
-
-
-
-
-
-
-
-
-
-
Phase failure
Check individual phases; replace fuse,
if necessary.
✘
-
-
-
-
-
-
-
-
-
-
-
Inlet tank empty or float switch
defective / disconnected
Check and remedy defect.