 dormakaba Canada Inc. RAC5 MFC Installation Guide – PK3738 | 6 

 

2.2 Components 

Refer to Annex E for RAC5 MFC component breakdown. 

2.2.1 Controller Box 

Figure 2 – RAC5 MFC Controller Box 

 

(A)

 

RAC5 MFC Enclosure & Access Door: Holds the controller board (PCB), power supply and relay expansion 
board. Knockouts are available on 3 sides for routing of peripheral cables 

(B)

 

Power Supply: Provides the DC power required for operation of the controller PCB and all peripherals 

(C)

 

Controller Board: Controls all the features of the RAC5 MFC system 

(D)

 

Tamper Switch: Attached to the RAC5 MFC enclosure to generate an alarm if the box is opened during 
operation 

(E)

 

Power & Battery Status LEDs: Provides visual indication of the operational status of the RAC5 MFC 
system. Battery status LED is only used on battery back-up equipped systems 

(F)

 

Cam-lock with Key: To provide secure locking and to control access to the RAC5 MFC enclosure 

Optional Components: 

(G)

 

Relay Expansion Board: Interface board providing 8 relay outputs that can be used to control relay-
equipped equipment. For example, it can be used with an elevator to call the elevator or to provide access 
only to specific floors for certain guests and staff. Up to 8 expansion boards of 8 relays each giving up to 
64 individual control relays can be added

 

Not Shown: 

(H)

 

Cables: Cables required for connections of the LEDs, power supply and controller PCB. If equipped, will 
also include cable for connection of relay expansion board

 

 

 

 

Содержание RAC5 MFC

Страница 1: ...RAC5 MFC Installation Guide RAC Install Guide Covers qxp_Layout 1 2021 01 26 3 47 PM Page 1 ...

Страница 2: ... Reader s 7 3 1 5 Power Adapter 8 3 1 6 Installation Hard Bag 8 3 1 7 Tools Required not supplied 8 3 2 Exploded View 9 4 System Installation Overview 9 4 1 Pre installation Procedures 10 4 2 Installation and Wiring Procedures 10 5 Annex A Quick Troubleshooting Guide 15 5 1 Power Troubleshooting 15 5 2 Card Reading Troubleshooting 15 5 3 External Inputs Troubleshooting 16 5 4 Relay Expansion Board...

Страница 3: ...12 2020 dormakaba Canada Inc RAC5 MFC Installation Guide PK3738 2 11 Annex G Fire Alarm Panel Wiring 21 12 Annex H Reader Drilling Template 22 ...

Страница 4: ...tallation of card readers or other peripherals within elevators must only be done with prior consultation of the elevator manufacturer A technician from the elevator manufacturer should always be present for installation Do not connect to a receptacle controlled by a switch If installing the RAC5 MFC in an elevator cage environment or in proximity to any other equipment that may generate high leve...

Страница 5: ...t installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interfer...

Страница 6: ...s Card Reader can be mounted directly on the inside of the elevator car typically on the elevator call button panel For surface mount the surface area required for the contactless reader is 5 W x 5 H x 2 D 12 7 x 12 7 x 5cm 2 depth behind panel required The RAC5 MFC is an access control solution that can operate 2 individual card readers provides multiple relays and much more as per the feature li...

Страница 7: ...g operation E Power Battery Status LEDs Provides visual indication of the operational status of the RAC5 MFC system Battery status LED is only used on battery back up equipped systems F Cam lock with Key To provide secure locking and to control access to the RAC5 MFC enclosure Optional Components G Relay Expansion Board Interface board providing 8 relay outputs that can be used to control relay eq...

Страница 8: ... subject to change without notice For letter designations refer to Figure 4 3 1 1 RAC5 MFC Enclosure NOTE All items below come factory installed A RAC5 MFC enclosure with access door B Power Supply 24 VAC 24 VDC input 12 VDC output C Controller PCB D Tamper switch E 2 panel mounted LEDs green for power and battery status F Cam lock 3 1 2 Relay Expansion Board G 8 Relay expansion PCB boards includi...

Страница 9: ...z 3 1 6 Installation Hard Bag L 4x Philips wood screw 8 x 1 1 4 M 4x Nylon anchor 6 10 N 4x Concrete anchor 7 9 O 2x Strain relief connector with locking nut P Ring terminal connector Q 5x Steel flat washer 8 R 2x Crimp fork terminals 18 22 AWG 3 1 7 Tools Required not supplied Additional tools may be required dependent on the peripherals being installed The list below covers the installation of t...

Страница 10: ...ordered and materials tools required are available Ensure all cabling is available for the peripherals components being installed All installations and wiring of RAC5 MFC enclosure peripherals must comply with all applicable local building codes and regulations and National Electric Code ANSI NFPA 70 Do not connect power to the enclosure until the end of the installation IMPORTANT CAUTION ...

Страница 11: ...ld be installed in an obvious location at an ergonomic height near the access door or elevator being controlled The space to use the contactless reader must be large enough to allow for adequate clearance for the card being presented to the reader 3 Install strain relief Strain reliefs are provided in the hardware bag to secure the wires leading into the enclosure and to help prevent the possibili...

Страница 12: ...nected In addition the wire used to connect the peripherals to the controller PCB must be of the proper gauge and type as specified by the manufacturer Every wire must pass through a strain relief as connected in the pre installation procedures dormakaba Canada Inc does not provide technical or field support for third party locking devices Please consult the device manufacturer for support NOTE Th...

Страница 13: ...heral connected to the relays will then be either in a normally open NO or normally closed NC state depending on the wiring 5 Install elevator controller Each Expansion board contains 8 dry relay contacts Up to 8 expansion boards can be used for total control of 64 common areas The relay outputs are at the wiring input of each three terminal connector NO COM NC on the expansion PCB as well as bein...

Страница 14: ... PK3738 13 ii Route the wires out of the enclosure to the AC power source and secure the wires recommended with tie wraps iii Crimp the fork terminals supplied in the hardware bag to the end of the wires and connect them to the power adapter screw terminals ...

Страница 15: ...access door LEDs as indicated below and in Annex B Figure 8 NOTE The wires must be connected with the proper polarity Once the terminals are installed they are designed to have a tight fit so removal may damage the LEDs LED Description Location on Door Terminal Connection Terminal Connection Power Status Top Red Orange Battery Status Bottom Red Yellow Ensure that the proper connections are made e ...

Страница 16: ...ed RAC5 MFC enclosure s panel door Power Status LED is OFF Verify that the power supply is powered both AC ON and DC ON LEDs are on Verify the LED wiring to the power supply All RAC5 MFC LEDs are OFF Verify that the DC ON LED on the power supply is on Verify that the AC power is active for the wall mount adapter Verify that the RAC5 MFC controller is connected properly to the power supply as per A...

Страница 17: ...n the Relay Expansion Board should be off Verify that the RAC5 MFC is not in Passage Mode Relay Expansion Board relays do not activate Activate the manual bypass switches SW1 and SW3 on the Relay Expansion Board and verify that the relays are activated and the corresponding LEDs turn on De activate the manual bypass Verify that the RAC5 MFC controller is active Heartbeat LED D46 should be blinking...

Страница 18: ...E J5 TB 3 RD2 Data J12 pin 2 GREEN J5 TB 4 RD1 Data J12 pin 3 WHITE J5 TB 3 RD1 Data J12 pin 4 GREEN J5 TB 4 Controller Board RAC5 Reader Connections Controller Board Contactless Reader Wire connection to back of contactless card reader TB 1 BLACK TB 2 RED TB 3 WHITE TB 4 GREEN 12V GND Power Supply NO C NC NO C NC LOW BATT AC FAIL DC OUT BAT INPUT XFRM 1 2 3 4 1 2 3 4 1 2 3 4 J17 J3 J7 J8 J12 J1 J...

Страница 19: ...gramming shielded cables should be used and connections made as per the diagram below Figure 9 Shielded Cable Wall Pluggable Transformer RAC5 Enclosure RAC5 Main PCB Mounting Screw Ingress Reader Egress Reader Power Supply Electrical Connector Shield Wire of Cable Ground Wire Shield Wire of Cable To Ground 1 Use shielded cables for the readers 2 Connect the shield wire of the reader cables to the ...

Страница 20: ...12 2020 dormakaba Canada Inc RAC5 MFC Installation Guide PK3738 19 8 Annex D RAC5 MFC Components Figure 10 RAC5 MFC Components ...

Страница 21: ...D GND LOW_BATAC_FAIL 4 3 2 1 O N 1 2 3 4 DELAY0 DELAY1 DEVICES TESTMODE SW2 D46 D37 D48 SW1 Reset 10 Annex F Dual Reader Wiring Figure 12 Dual Reader Wiring RAC5 NFC Wall Reader Red Black White Green RAC5 NFC Wall Reader 1 2 3 4 1 2 3 4 1 2 3 4 J17 J3 J7 J8 J12 J1 J15 J16 J6 J18 J19 RAC5 MFC PCB NO NC CO M GND F IRE GND 12V _LCK 1 GND 1 2V NO NC CO M RE_UNL 2 GND RE_UNL 1 1 2 3 4 1 2 3 4 1 2 3 2 1...

Страница 22: ...5 Lite or RAC5 XT are connected to a Fire Alarm Panel it must be connected to a Normally Closed dry contact output 1 2 3 4 1 2 3 4 1 2 3 4 J17 J3 J7 J8 J12 J1 J15 J16 J6 J18 J19 RAC5 MFC PCB NO NC CO M GND F IRE GND 12V _LCK 1 GND 1 2V NO NC CO M RE_UNL 2 GND RE_UNL 1 1 2 3 4 1 2 3 4 1 2 3 2 1 1 2 3 12_LCK 2 GND 1 2 3 4 PWRGND GND PWR RD 1 RD 2 READER 2 READER 1 1 2 3 4 J11 REX2 GND TAMPER GND DOO...

Страница 23: ...12 2020 dormakaba Canada Inc RAC5 MFC Installation Guide PK3738 22 12 Annex H Reader Drilling Template Figure 15 Reader Drilling Template not to scale ...

Страница 24: ...dormakaba Canada Inc www dormakaba us RAC Install Guide Covers qxp_Layout 1 2021 01 26 3 48 PM Page 4 ...