12-2020
dormakaba Canada Inc. RAC5 MFC Installation Guide – PK3738 | 11
4.2 Installation and Wiring Procedures
1.
Mount the RAC5 MFC enclosure
a)
Install the enclosure in the desired location using the appropriate items from the hardware bag
NOTE:
For easier access, we recommend removing the access door prior to installation.
Figure 6 – Enclosure
2.
Mount the contactless card reader.
NOTE:
All readers are rated IP 54.
a)
Remove the back plate and use it to mark the holes for the cables and screws
NOTE:
Refer to Annex H of this manual for elevator panel preparation for mounting readers.
b)
Drill the holes in the wall according to the diameters indicated on the drilling template in Annex
H, based on the type of surface the reader is being installed on.
3.
Connect peripheral wiring.
Do not exceed the maximum cable length indicated by the manufacturer of the
products being connected. In addition, the wire used to connect the peripherals to
the controller PCB must be of the proper gauge and type as specified by the
manufacturer.
Every wire must pass through a strain relief as connected in the pre-installation
procedures. dormakaba Canada Inc. does not provide technical or field support
for third party locking devices. Please consult the device manufacturer for
support.
NOTE:
The maximum recommended wire length is the approximate wire length that causes a 5%
voltage loss in the wire, using a 12-volt locking device at the rated current included.
a)
Fire Alarm Panel
: Refer to Annex G, Figure 14 for detailed wiring
i.
Remove the jumper wire connected between pins 3 and 4 of connector J18 on the
controller PCB and complete the fire panel installation as per manufacturer’s
indications
b)
Tamper Switch to Premise Alarm System
i.
To wire the tamper switch to the premise alarm system, disconnect the wires on
controller PCB connected J7 pins 1 & 2 and run a 2-connector cable from the
switch to the premise alarm system
N
OR
L
M
A