78
ED900
02-2020
08125330
dormakaba ED900 Installation Instructions – Double egress door
Chapter 24
24.1 Separately commission active and inactive doors
24 Double door first commissioning
24.1.1 Commission active door first.
1. Refer to Chapter 23 and commission active door.
24.1.2 Commission inactive door.
1. Refer to Chapter 23 and commission inactive door.
24.2 Set operator parameters for double door operation
24.2.1 Full width cover option –
Active door, set parameter PS to 1.
1. Set program switch to CLOSE
Step 1
Press
Press and hold PRG > 3 s to enter
program mode, AS parameter
displayed.
Step 2
Press
Scroll to
PS
(Program switch type)
parameter.
Step 3
Press
Displays "00" , factory setting.
Step 4
Press
"00" starts flashing.
Step 5
Press
Scroll to select parameter value "1",
External mechanical program switch
connected to operator terminal board.
Fig. 24.2.1 Single program switch located on active door.
CAUTION
Full width cover option – single program
switch.
Parameter
PS
on active door must be set to 1.
Reference Para. 23.2.1.
Automatic
Close
Permanent open
Step 6
Press
Saves value entered. Display stops
flashing.
Step 7
Press
Returns to program switch parameter.
Step 8
Press
Exits program mode.