101
ED900
02-2020
08125330
dormakaba ED900 Installation Instructions – Double egress door
Appendix A
Parameter
Value
range
Units
Factory
setting Description
Door preload prior to unlocking
1. Door preload prior to unlocking; force with which door is pushed in the "closed"
direction before door is opened.
2. The door may need to be pushed in closing direction (preload) in order to release
electric strike to insure door opens.
3. Preload time is set by parameter
Ud,
delayed opening time for locking mechanism.
4. To maintain long service life, set preload force only as high as necessary.
15
0 - 9
0
Power reserve module SVP-PR 12 test
16
0 - 1
0
0
Test off
1
1. SVP-PR 12 power reserve module test is performed once every 24 hours, or
10 minutes after AC power has been turned on. In event of an error:
• Unlocking is not performed and no automatic door movements are initiated.
• Error code
E 25
is displayed, Appendix B, troubleshooting error codes.
2. SVP-PR 12 power reserve module can be used but must be tested on a regular
basis if using:
• SVP-2000 DCW® emergency escape motor lock with automatic latching action.
• M-SVP 2000 DCW® emergency escape lock.
3. Test is automatically activated if a fire protection module is recognized in
conjunction with SVP-2000 DCW® or M-SVP 2000 DCW® locks.
TS
Static force in opening direction
1. Static force in opening direction (basic parameter for wind load control). Static force
on door closing edge can be changed using this parameter.
2. Internal monitoring system checks if parameter setting is admissible. If setting exceeds
admissible value, the setting is alternately displayed with the permissible value.
3. After parameter set, verify setting meets ANSI/BHMA standard A156.19 (low energy).
See Chapter 30.
4. ED900 low energy operator: static force range is reduced.
17
2- 15
*10
N
6
*10
.45- 3.4
*10
lbf
1.35
*10
Static force in closing direction
1. Static force in closing direction (basic parameter for wind load control). Static force on
door closing edge can be changed using this parameter.
2. Internal monitoring system checks if parameter setting is admissible. If setting exceeds
admissible value, the setting is alternately displayed with the permissible value.
3. After parameter set, verify setting meets ANSI/BHMA standard A156.19 (low energy).
See Chapter 30.
4. ED900 low energy operator: static force range is reduced.
18
2- 15
*10
N
6
*10
.45- 3.4
*10
lbf
1.35
*10
Motor driven latching action, automatic
mode
1. System offers a motor driven latching action in automatic mode in addition to
mechanical latching action.
2. The
EP
parameter setting is designed to increase static force on door to insure proper
closing despite resistance caused by door seals or locking devices.
3. Setting should be increased step by step from a low setting so as to avoid damage to
the system. Use the lowest possible setting.
4. Ensure that both the door itself and the arm or track installation are suitable for the
additional, permanent forces.
19
0 - 9
0
A.1.1 Driving parameters detail.