Hold open time
1.5 sec
2.5 sec
5
sec
8
sec
10 sec
15 sec
20 sec
25 sec
30 sec
Adjustment via PDA > 30 sec
Opening speed:
0.4 in./sec
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
2.8
3.0
in./sec
in./sec
in./sec
in./sec
in./sec
in./sec
in./sec
in./sec
in./sec
in./sec
in./sec
in./sec
in./sec
Closing speed
0.4
0.6
0.8
1.0
1.2
in./sec
in./sec
in./sec
in./sec
in./sec
Temper block
Temper block activated
block de-activated
Temper
Locking in program switch setting:
setting “OFF“
setting “OFF“ and “EXIT ONLY”
Battery mode
no Battery
Emergency closing
Emergency opening
Battery Emergency mode
Interlock type:
No interlock
Bistable interlock
Bistable interlock with
status signalling contact (NO)
Monostable interlock (fail safe)
Night-/ Bank Hold open time
1.5 sec
2.5 sec
5
sec
8
sec
10 sec
15 sec
20 sec
25 sec
30 sec
Adjustment via PDA > 30 sec
Side lite function
Stop
Closing cycle
The hold-open time, adjusted via the PDA, is also indicated on the 7-segment display of the control unit.
As the display of the control unit follows a certain pattern (see above), it always indicates the next value below.
For example:
Adjustment of PDA = 14 sec => display of control unit = 5
Adjustment of PDA = 21 sec => display of control unit = 7
This is also the case with the Night-/ Bank hold-open time.
According to BHMA / ANSI 156.10, the Hold-open time and the Night-/Bank Hold-open time
have to be adjusted to at least 2.5 sec. when light barriers are applied.
Meaning of display codes
ESA II Controller
and Wiring Manual