Chapter 6. Function Table & Description
49
Input Range
Factory Setting
0.1 ~ 40.00[Hz]
0.50[Hz]
Drive 36 : Start Frequency
It refers to frequency that drive starts to generate output voltage.
Input Range
Factory Setting
40.00 ~ rated frequency of the motor[Hz]
60.00[Hz]
Drive 37 : Max Operation Frequency
· It can limit max operation frequency of the drive.
· It cannot exceed range of rated frequency (Drive 15) of the motor.
Input Range
Factory Setting
1.0 ~ 15.0[kHz]
5.0[kHz]
Drive 38 : Switching Frequency Settings
· In case of high noise or temperature, it is required to decrease the frequency.
· As the switching frequency becomes lower, the noise of motor will be increased while frequency noise or
leakage current is decreased.
Drive 39 : Fan Operation Method
It sets cooling fan operation method.
Functional Description
To operate upon application of drive power
To operate upon output of drive frequency
Drive 40 : TFF(Fan Trip Mode)
It sets whether stop the drive or not if cooling fan operation has a problem.
Drive 41 : Frequency of the Drive
It displays an output Frequency of the Drive
Drive 42 : Current of the Drive
It displays an output rate of the Drive.
Functional Description
OFF
Set – stop the drive when trip occurs