Chapter 6. Function Table & Description
41
6.2 Drive Control Group
RUN/Stop Mode
0: Keypad 1: Terminal Input 2: Comm. Input
Freq. Set Mode
When manual Mode, setup Frequency Input Mode 0: Keypad
0: Keypad 1: AI1 Signal 2: Comm.
Command Freq.
When manual mode, setup the target Frequency
Motor Select
0 : 0.75kW-2
5 : 7.5kW-2
10 : 4kW-4
15 : 18.5kW-4
1 : 1.5kW-2
6 : 11kW-2
11 : 5.5kW-4
16 : 22kW-4
2 : 2.2kW-2
7 : 0.75kW-4
12 : 7.5kW-4
3 : 4kW-2
8 : 1.5kW-4
13 : 11kW-4
4 : 5.5kW-2
9 : 2.2kW-4
14 : 15kW-4
Motor Pole
0: 2 Pole 1: 4 pole
Rated Motor Speed
The rated speed of the motor
Rated Current
The rated current of the motor
Rated Voltage
The rated current of the motor
No load current of
the motor
No load current of the motor
Rated Slip
The rated slip frequency
Rated Freq.
0: 50 Hz 1: 60 Hz
Rotation Dir.
0: Forward 1: Reverse
Stop Mode
0: Deceleration stop 1: Free Run (cut the Drive output)
Accel. Time
1.0~600.0 sec (0.1 sec)
Decel. Time
1.0~600.0 sec (0.1 sec)
TOL Mode
Setup overload trip of the motor 0: Disable(deactivation) 1: Enable(activation)
TOL Level
Setup overload trip level of the motor
TOL Time
Setup overload trip time of the motor
Stall Mode
0: Disable (deactivation) 1: Enable (activation)
Stall Level
100~200% (1%)
TMOH Mode
Setup overheating of the motor 0: Disable(deactivation) 1: Enable(activation)
TGF Mode
Ground Protection 0: Disable(deactivation) 1: Enable(activation)
TOO Mode
Output Open Phase Protection 0: Disable(deactivation) 1: Enable(activation)
The Number of Rebooting after trip
Retry Number
Retry Time
Standby time for rebooting after trip
DRV. Ctrl Mode
Drive Control Mode 0: V/F Control(V/F) 1: Slip compensation control
V/F Pattern
0: Linear 1: Square
Torque Boost
Setup Volume of torque boost
1
2
3
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
31
32
33
34
35
36
Start Freq.
X
X
○
X
○
○
X
X
○
○
X
X
X
○
○
X
○
○
X
○
X
X
X
○
○
X
X
X
X
0.10~40.00Hz(0.01Hz)
LCD Display
Description
-
-
Hz
-
-
RPM
Arms
Vrms
Arms
Hz
-
-
-
sec
sec
-
%
sec
-
%
-
-
-
Time
sec
-
-
%
Hz
Unit
CODE
0
0
30
-
-
3550
☆
☆
☆
☆
1
1
0
3
6
0
150
60
0
120
0
0
0
5
10
0
0
2.0
0.5
Factory
Setting
0~2
0~2
Start Freq.
(CODE-36)~
Max. Freq.
(CODE-37)
0~13
0~1
1~9999
1.0~100.0
180.0~500.0
0.00~100.00
0.1~10
0~1
0~1
0~1
1.0~600.0
1.0~600.0
0~1
100~200
5~200
0~1
100~200
0~1
0~1
0~1
1~100
1~250
0~1
0~1
0~10.0
0.10~40.00
Range
Changeable
in
operation