Chapter 6. Function Table & Description
44
Drive 15 : Sets the motor no load current.
·It displays the Rated Slip Freq. of the Motor.
·Settings are automatically set upon No. of motor poles, rated No. of rotations, and rated frequency.
Related Functions
Input Range
0.1 ~ 10.00[Hz]
Drive 11
Drive 10
Drive 16
Rated Motor Rev Count
Motor Pole
Rated motor frequency
Factory Setting
Automatic Setup
Input Range
Factory Setting
1 ~ 9999 [rpm]
Initial value is set upon motor capacity
Drive 10: Number of motor poles
·Setting the motor pole.
·Pump and drive is set at the factory
Drive 11: Rated Motor Speed
Rated Motor Speed.
Input Range
Factory Setting
180.0 ~ 500.0 [Vrms]
Initial value is set upon drive capacity
Drive 13: The Rated Voltage of the Motor
It sets the rated voltage of the motor. It is based on data indicated on the nameplate of the motor.
Input Range
Factory Setting
0.0 ~ 100.0 [Arms]
Initial value is set upon drive capacity
Drive 14 : Sets the motor no load current.
Input Range
Factory Setting
1 ~ 9999 [rpm]
Initial value is set upon drive capacity
Drive 12: Rated current of the motor
·It sets up the rated current (RMS) of the motor. It is based on the rated current indicated on the nameplate of
the motor.
·It is applied to Stall Prevention Level, Slip Compensation Control and Overload Trip Level
Functional Description
2 Pole Motor
4 Pole Motor
Содержание XQ-0075T-2