Chapter 6. Function Table & Description
31
6.1 Pump Control Group
1
Pump Ctrl Mode
-
0: Manual 1: constant pressure 2: differential pressure
2
Pump Op. mode
-
0: Sequence 1: Part operation
3
Press Set mode
0: Keypad 1: AI1 Signal 2: AI2 Signal 3: COM input
4
Setting Press.
bar
Display Setting Pressure and Setup
5
Current Press.
bar
Display the current pressure
6
Discharge Press.
bar
When differential Pressure mode, display discharge pressure
7
Inlet Press.
bar
When differential Pressure mode, display inlet pressure
11
Sensor1 Cap.
bar
Setup Max. Capacity of Sensor1(discharge)
12
Sensor1 Gain
%
Setup Gain of Sensor1(discharge)
13
Sensor1 Offset
bar
Setup Offset of Sensor1(discharge)
14
Sensor2 Cap.
bar
Setup Max. Capacity of Sensor2(inlet)
15
Sensor2 Gain
%
Setup Gain of Sensor2(inlet)
16
Sensor2 Offset
bar
Setup Offset of Sensor2(inlet)
21
PID P gain
%
0 ~ 100% (1%)
22
PID I gain
sec
0.0 ~ 100 sec. (0.1 sec.)
23
PID D gain
ms
0 ~ 100 ms (1 ms ) PID Control Cycle
24
PID Con. Cycle
sec
0.1 ~ 0.5 sec. (0.1 sec.)
31
Start Init. %
%
~ 100% (1%) Ratio of Initial Output on Starting
32
On/OFF Band
bar
When interoperation, standby time for the next Start/Stop
33
ON/OFF Time
sec
Variation of Initial start/stop, and the next start/stop when interoperation
34
Freezing Prev.
-
0: Deactivate 1: Activate
35
Changeover Mod
-
0: Lowest ID 1: Low Integrating Watt hour 2: Half Pump
36
Changeover Sec
hour
Forced Alteration Time
Ratio of Partly Driving
37
Share Op. On %
%
41
Low-Flow Time
sec
0~200 sec. (1 sec.) Detection time of Low Level
42
Low-Flow Rate
%
0~100% (1%) Ratio of Low Level detection
50
TOP Level
bar
Trip Level of High Pressure
51
TOP Time
sec
Trip Time of High Pressure
52
TLP Level
1
0
0
3.00
-
-
-
16.00
100
0.00
16.00
100
0.00
10
1.0
0
0.2
50
0.30
5
0
0
12
100
30
100
16.00
5
0.5
0 ~2
0~1
0~2
0.00~25.00
0.00~25.00
0.00 ~ 25.00
0.00 ~ 25.00
1.00~25.00
50~200
2.00~2.00
1.00~25.00
50~200
2.00~2.00
0~100
0.0~100.0
0~100
0.1~0.5
5~100
0~2.00
0~100
0~1
0~2
0~24
70~100
0~200
0~100
0.00~25.00
0~600
0.00~25.00
bar
×
×
×
○
-
-
-
×
○
○
×
○
○
○
○
○
×
30
Stop-Rate of Drive
%
Stop-Rate of Drive
30
0~60
○
×
○
○
○
×
○
○
○
○
○
○
○
Trip Level of Low Pressure
LCD Display
Desciption
Unit
CODE
Factory
Setting
Range
Changable in
Operation