Chapter 6. Function Table & Description
45
Drive 18 : Motor Stop Method
It sets motor stop method
Related Function
Functional Description
Deceleration Stop
Drive 20
Cutting off the drive output voltage
Deceleration Time
Drive 16 : The Rated Frequency of the Motor
·It sets the rated frequency of the motor.
Input Range
Factory Setting
1.0 ~ 600.0 [sec]
3.0 [sec]
Drive 19 : Acceleration Time
It is time to reach the max. frequency from 0[Hz].
If acceleration time is too short, it can cause over- current fault during motor operation.
Input Range
Factory Setting
1.0 ~ 600.0 [sec]
6.0 [sec]
Drive 20 : Deceleration Time
·It is time to decelerate to 0[Hz] from max frequency.
·If the Deceleration time is too short, over- voltage fault may be occurred during motor operation
Drive 17 : Direction of Motor Rotation Settings
·It sets rotation direction of the pump.
·Be sure to check the rotation direction of the pump for proper operation.
·As the rotation direction may change according to wiring, please check it before starting.
Functional Description
Forward Direction– CW(Clockwise)
Reverse - CCW(Counterclockwise)
Related Functions
Drive 37
Max. Operation Freq.
Functional Description
50[Hz]
60[Hz]