Chapter 6. Function Table & Description
Input Range
0: Input Range
1~24: Alternation time setup. [Factory Setting 12(hour)]
Pump 36 : Master Pump Alternation Time
Alternation refers to an operation that when it reaches time specified by the user, the drive with a lot of power
consumed is to be stopped and the one with less power consumption is to be started alternatively at the same
time in order to prevent a specific drive(pump) being operated constantly. If the time is set, drives are forcedly
shifted.
Input Range
0: Low level detection interval off
1~200[sec]: Low Level Detection Time Setting [Factory setting 30(sec)]
Pump 41 : Low level detection interval after Reaching Setup Pressure
When the pump pressure reaches to setting and maintained for longer than setup time, it starts to reduce the
speed. If there is pressure difference as much as the variance of starting the Drive, the pump starts to operate
again and if not, it stops.
Input Range
Factory Setting
70~100[%]
100[%]
Pump 37 : Partly Driving On (%): Setup Output Ratio to start the next Drive when interoperaton(Preparing)
It is an output ratio to start the next drive by applying it centralized control method for interoperation.
If the output ratio of drive in operation is higher than the setting value, the next drive to be linked starts.
Input Range
Factory Setting
0~100[%]
100[%]
Pump 42 : Low level detection Ratio to Stop after Reaching Setup Pressure
In order to stop after reaching the setting pressure, the drive is able to stop only if the current output ratio is
less or equal to setup ratio.
Pump 50 : TOP- High Pressure Alarm Level
It sets standard pressure value to alert the high pressure.
※
When setup the setting pressure, it is automatically set to setup pr 2bar.
Input Range
Related Function
Factory Setting
0.00~25.00[bar]
Pump 51
High Pressure Alarm Time
16.0[bar]
Pump 51 : TOP- High Pressure Alarm Time
It sets maintaining time of high pressure alarm level to issue the high pressure alarm. That is, if the current
pressure increases above the high pressure alarm level (Pump 50) and maintains its state for a specified time,
a high pressure alarm is displayed and operation stops.
Input Range
Related Function
Factory Setting
0~600[sec]
High Pressure Alarm Time
5[sec]
Pump 50
Pump 52 : TLP- Low Pressure Alarm Level
It sets standard pressure value to issue the low pressure alarm.
Input Range
Related Function
Factory Setting
0.0~25.0[bar]
Low Pressure Alarm Time
0.5[bar]
Pump 52