73
BIOCLASS iC 66
25
TECHNICAL DATA
MODEL
BioClass iC 66
Rated heat output (P
ח
)
kW
66,6
Efficiency at maximum heat output
% (NCV)
94,9
Minimum heat output (P
p
)
kW
20
Efficiency at minimum heat output
% (NCV)
95,2
CO at maximum heat output (10% O
2
)
mg/m
3
88
OGC (organic gaseous substances) at maximum
heat output (10% O
2
)
mg/m
3
2
Particles content at maximum heat output (10%
O2)
mg/m
3
12
CO at minimum heat output (10% O
2
)
mg/m
3
34
OGC (organic gaseous substances) at minimum
heat output (10% O
2
)
mg/m
3
1
Boiler class (according to EN 303-5)
-
Clase 5
Maximum operating pressure
bar
3
Maximum operating temperature
ºC
80
Maximum safety temperature
ºC
110
Water volume
litros
154
Minimum flue draught
mbar
0,10
Maximum flue draught
mbar
0,20
Electrical supply
-
230 V~, 50 Hz, 2,50 A
Boiler chimney diameter
mm
150
Maximum water content of the fuel
%
7
Minimum return temperature
ºC
50 ºC
Water pressure drop (dT = 20 K)
mbar
22
Weight (net)
Kg
486
Содержание BioClass iC 66
Страница 1: ...Bioclass iC 66 Biomass boiler EN INSTALLATION AND OPERATING INSTRUCTIONS ...
Страница 2: ......