The final screen will contain the image of the refrigerant circuit and contain the valve position information.
To change the setpoint of the chilled water. The user must press the program button and scroll to Menu item B. Setpoint. The password
prompt will be displayed and 1234 must be entered to have access to change the value from the default.
Figure 14:
Main Menu Items: Screen Navigation Tree
Press enter to select items to view and up/down the screen will automatically return to the main
status screen.
Menu A: On/Off Unit
o
Unit Address:
1 (Default)
o
Power By Display:
ON (Default)
o
Status:
Unit ON
Menu B: Setpoints: Password required (1234)
o
Heating Setpoint
110 (Default)
o
Cooling Setpoint
48 (Default)
Current Limiting:
o
Mode:
Normal (Default) Econo or Boost
o
Econo:
4 Amps
o
Normal:
9 Amps
Configuration:
o
Temperature Units:
F (Default) Or C
o
Pressure Units:
PSI (Default) or Bar
Menu C: Clock/Scheduler
Содержание VARC 48
Страница 20: ...18 Appendix I Touchscreen Navigation MAIN PAGE Figure 15 CHILLER ENABLE Figure 16...
Страница 21: ...19 CHILLER SETPOINTS Figure 17...
Страница 22: ...20 Figure 18 CHILLER STAGE Figure 19...
Страница 24: ...22 TRENDS Figure 21 Figure 22...
Страница 25: ...23 ACTIVE ALARMS Figure 23 ALARM HISTORY Figure 24...
Страница 26: ...24 ALARM HELP Figure 25 Figure 26...
Страница 27: ...25 REMOTE SUPPORT Figure 27 REMOTE ENABLE Figure 28...
Страница 28: ...26 REMOTE CONFIGURATION Figure 29...
Страница 41: ...39 Basic wiring diagram...
Страница 55: ...53 7 Use Next or Back to scroll to Display Settings 8 Select Display Settings...
Страница 69: ...67 VARC Standard Wiring Diagram Figure...
Страница 70: ...68 NOTES...
Страница 71: ...69 NOTES...